CVE-2023-6408 is a flaw in the engineering link between Schneider Electric EcoStruxure Control Expert and Modicon M340, M580, MC80 and Momentum PLCs: message integrity is not enforced (CWE-924), so a man-in-the-middle attacker can cause denial of service and loss of confidentiality and integrity of the controller. NVD scores it 8.1. Fixes: M340 SV3.60, M580 SV4.20, Control Expert v16.0.
Vulnerability summary
CVSS base score
8.1
High severity
EPSS score (FIRST)
0.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-6408 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Modicon M340 CPU (BMXP34*) | cpe:2.3:o:schneider-electric:modicon_m340_bmxp342020_firmware:*:*:*:*:*:*:*:* | Before SV3.60; fixed in SV3.60 (NVD lists 13 BMXP34 part numbers, versionEndExcluding 3.60) |
| Modicon M580 CPU (BMEP*, BMEH*, excluding CPU Safety) | cpe:2.3:o:schneider-electric:modicon_m580_bmep582040_firmware:*:*:*:*:*:*:*:* | Before SV4.20; fixed in SV4.20 |
| Modicon M580 CPU Safety (BMEP58*S, BMEH58*S) | cpe:2.3:o:schneider-electric:modicon_m580_bmep582040s_firmware:*:*:*:*:*:*:*:* | Before SV4.21; fixed in SV4.21 (Control Expert v16.0 HF001 or later needed to connect) |
| Modicon Momentum Unity M1E (171CBU*) | cpe:2.3:o:schneider-electric:modicon_momentum_171cbu98091_firmware:*:*:*:*:*:*:*:* | Before SV2.90; fixed in SV2.90 (SEVD-2024-044-01 v4.0.0, 2026-04-14); NVD CPE has no upper bound |
| Modicon MC80 (BMKC80) | cpe:2.3:o:schneider-electric:modicon_mc80_bmkc8020310_firmware:*:*:*:*:*:*:*:* | Before SV2.20; fixed in SV2.20 (SEVD-2024-044-01 v5.0.0, 2026-09-08); NVD CPE has no upper bound |
| EcoStruxure Control Expert | cpe:2.3:a:schneider-electric:ecostruxure_control_expert:*:*:*:*:*:*:*:* | Before v16.0; fixed in v16.0 |
| EcoStruxure Process Expert | cpe:2.3:a:schneider-electric:ecostruxure_process_expert:*:*:*:*:*:*:*:* | Before v2023; Schneider names 15.3 HF008 as the fixed version |
What does this mean for affected devices?
NVD carries the Schneider Electric description: "CWE-924: Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability exists that could cause a denial of service and loss of confidentiality, integrity of controllers when conducting a Man in the Middle attack." NVD's Primary score is CVSS v3.1 8.1 (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H), the same as the Schneider CNA score, and the weakness is the CNA's CWE-924. NVD analysed the record, which was published on 2024-02-14 (NVD, CVE record).
How severe is CVE-2023-6408?
NVD and Schneider agree on 8.1: a network attacker with no privileges and no user interaction, high impact on confidentiality, integrity and availability, but high attack complexity, because the attacker has to sit in the path between Control Expert and the controller. Schneider's SEVD-2024-044-01 also gives a CVSS v4.0 score of 9.2 (CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N). CISA republished the notice as ICSA-24-331-03 on 2024-11-26 with the same 8.1. The CISA ADP SSVC entry in the CVE record reads exploitation none, automatable no, technical impact total. Schneider credits Gao Jian with the report.
Which controllers and software are affected, and what fixes them?
| Product (Schneider wording) | Affected | Fixed |
|---|---|---|
| Modicon M340 CPU (BMXP34*) | before SV3.60 | SV3.60 |
| Modicon M580 CPU (BMEP*, BMEH*, excluding M580 CPU Safety) | before SV4.20 | SV4.20 |
| Modicon M580 CPU Safety (BMEP58S, BMEH58S) | before SV4.21 | SV4.21 (needs Control Expert v16.0 HF001 or later to connect) |
| Modicon Momentum Unity M1E (171CBU*) | before SV2.90 | SV2.90 (needs Control Expert v16.2 HF003 or later) |
| Modicon MC80 (BMKC80) | before SV2.20 | SV2.20 (needs Control Expert v16.4 or later) |
| EcoStruxure Control Expert | before v16.0 | v16.0 |
| EcoStruxure Process Expert | before v2023 | 15.3 HF008, as the notice names it |
The fix has two sides, the controller firmware and the engineering software, so update both. SEVD-2024-044-01 was first released on 2024-02-13; version 2.0.0 (2024-07-09) added the MC80 and Momentum, version 3.0.0 (2024-08-13) the M580 CPU Safety fix, version 4.0.0 (2026-04-14) the Momentum fix and version 5.0.0 (2026-09-08) the MC80 fix. CISA's republication was last updated on 2026-05-07, so it still lists all MC80 versions as affected. NVD's CPE list, built before those updates, has no fixed version for the MC80 (BMKC8020301, BMKC8020310, BMKC8030311) or Momentum (171CBU78090, 171CBU98090, 171CBU98091) part numbers, so CPE matching flags even fixed MC80 and Momentum firmware.
How do you mitigate CVE-2023-6408 before you update?
For controllers you cannot update right away, Schneider's mitigations are: set up an application password in the project properties; segment the network and block all unauthorized access to port 502/TCP with a firewall; configure the controller's Access Control List as its user manual describes; and set up the secure (encrypted) communication described in the Modicon Controllers Platform Cyber Security Reference Manual. For the M580 it adds IPsec through a BMENOC module, and for the M340 and M580 it suggests an external firewall such as Belden's EAGLE40-07 for VPN connections. Our Modicon and UMAS security guide covers the secure engineering link and these firmware thresholds, and the weak cryptography fix guide explains why unprotected message integrity enables man-in-the-middle attacks. Related Modicon engineering-link flaws are CVE-2022-45789 (session replay), CVE-2021-22779 and CVE-2018-7842. The same notice covers the Control Expert flaws CVE-2023-6409 and CVE-2023-27975.
CVE-2023-6408 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00314, the 25.0th percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-21): status Analyzed; published 2024-02-14; NVD Primary CVSS v3.1 8.1 CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H, Schneider CNA Secondary 8.1 same vector; CWE-924 (Schneider); CPEs: 13 M340 BMXP34 firmware <3.60, M580 BMEP/BMEH firmware <4.20 (CPU Safety S parts <4.21), MC80 BMKC8020301/8020310/8030311 and Momentum 171CBU78090/98090/98091 firmware without version bound, Control Expert <16.0, Process Expert <2023. — NVD
- Schneider Electric SEVD-2024-044-01 version 5.0.0 (released 2024-02-13, updated 2026-09-08), CSAF read 2026-11-21: CVE-2023-6408 CWE-924, CVSS v3.1 8.1, CVSS v4.0 9.2 CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N; affected/fixed: M340 <SV3.60 / SV3.60, M580 <SV4.20 / SV4.20, M580 CPU Safety <SV4.21 / SV4.21 (Control Expert v16.0 HF001 minimum), Momentum Unity M1E <SV2.90 / SV2.90 (Control Expert v16.2 HF003 minimum), MC80 <SV2.20 / SV2.20 (Control Expert v16.4 minimum), Control Expert <v16.0 / v16.0, Process Expert <v2023 / 15.3 HF008; revision history 2.0.0 2024-07-09 MC80 and Momentum added, 3.0.0 2024-08-13 M580 Safety fix, 4.0.0 2026-04-14 Momentum fix, 5.0.0 2026-09-08 MC80 fix; mitigations: application password, firewall 502/TCP, Access Control List, secure communication per EIO0000001999, BMENOC IPsec for M580, external firewall such as Belden EAGLE40-07; credit Gao Jian. — Schneider Electric SEVD-2024-044-01
- CISA ICSA-24-331-03 CSAF (republication released 2024-11-26, updated 2026-05-07), read 2026-11-21: CVE-2023-6408 CVSS v3 8.1; Modicon MC80 (BMKC80) all versions known affected; Momentum SV2.90 fixed. — CISA CSAF ICSA-24-331-03
- CVE record (checked 2026-11-21): state PUBLISHED, CNA Schneider Electric, published 2024-02-14; CNA CWE-924, CVSS v3.1 8.1; CISA-ADP SSVC (exploitation none, automatable no, technical impact total). — CVE.org
- Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21. — CISA KEV
- EPSS 0.00314, 25.0th percentile, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories
Sources
- NVD
- Schneider Electric SEVD-2024-044-01: EcoStruxure Control Expert, Process Expert and Modicon M340, M580 and M580 Safety PLCs (PDF)
- Schneider Electric SEVD-2024-044-01 (CSAF)
- CISA CSAF: ICSA-24-331-03 Schneider Electric EcoStruxure Control Expert, Process Expert, and Modicon M340, M580 and M580 Safety PLCs (machine-readable advisory)
- CVE.org record CVE-2023-6408 (CNA: Schneider Electric)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Which firmware fixes CVE-2023-6408?
Per Schneider SEVD-2024-044-01 version 5.0.0: M340 SV3.60, M580 SV4.20, M580 CPU Safety SV4.21, Momentum Unity M1E SV2.90 and MC80 SV2.20. Control Expert must be v16.0 or later, and the newer Safety, Momentum and MC80 firmware needs Control Expert v16.0 HF001, v16.2 HF003 and v16.4 respectively to connect.
Do I need to update both the PLC and Control Expert?
Yes. Schneider lists both the controller firmware and EcoStruxure Control Expert (before v16.0) and Process Expert (before v2023) as affected, with separate fixes for each.
Why does my scanner still flag fixed MC80 or Momentum firmware?
NVD's CPE entries for the MC80 and Momentum part numbers have no version bound, because Schneider added fixes for them in April and September 2026 after NVD's analysis. Check the installed firmware against SV2.20 (MC80) and SV2.90 (Momentum) instead.
What can I do if I cannot update the controller?
Set an application password, block unauthorized access to port 502/TCP, configure the controller's Access Control List and set up the encrypted communication from Schneider's cybersecurity manual; on the M580, IPsec through a BMENOC module is another option (per SEVD-2024-044-01).