CVE-2021-22779 is an authentication bypass in Schneider Electric Modicon M580 and M340 controllers and EcoStruxure Control Expert: an attacker who spoofs the Modbus traffic between engineering software and controller gets read and write access to the PLC. NVD scores it 9.1, Schneider 9.8. The fix needs both Control Expert V15.1 and new controller firmware.
Vulnerability summary
CVSS base score
9.1
Critical severity
EPSS score (FIRST)
1.1%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-22779 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric EcoStruxure Control Expert (incl. Unity Pro) | cpe:2.3:a:schneider-electric:ecostruxure_control_expert:*:*:*:*:*:*:*:* | Before V15.1, including V15.0 SP1 and all Unity Pro versions; V15.1 is step one of the fix (SEVD-2021-194-01) |
| Schneider Electric EcoStruxure Process Expert (incl. Hybrid DCS) | cpe:2.3:a:schneider-electric:ecostruxure_process_expert:*:*:*:*:*:*:*:* | Before V2021; V2021 is step one of the fix (SEVD-2021-194-01) |
| Schneider Electric Modicon M580 CPU (BMEP*, BMEH*, excluding M580 CPU Safety) | cpe:2.3:o:schneider-electric:modicon_m580_bmep582040_firmware:*:*:*:*:*:*:*:* | Before SV4.10; fixed in SV4.10 (SEVD-2021-194-01). SV4.02 was retracted |
| Schneider Electric Modicon M580 CPU Safety (BMEP58*S, BMEH58*S) | cpe:2.3:o:schneider-electric:modicon_m580_bmep582040s_firmware:*:*:*:*:*:*:*:* | Before SV4.21; fixed in SV4.21, needs Control Expert V16.0 HF001 or later (SEVD-2021-194-01) |
| Schneider Electric Modicon M340 CPU (BMXP34*) | cpe:2.3:o:schneider-electric:modicon_m340_bmxp342020_firmware:*:*:*:*:*:*:*:* | Before V3.50; fixed in V3.50 with an application password (SEVD-2021-194-01) |
| Schneider Electric SCADAPack RemoteConnect for x70 | cpe:2.3:a:schneider-electric:remoteconnect:*:*:*:*:*:*:scadapack_x70:* | Listed in NVD's description and CPE; SEVD-2021-194-01 v4.0.0 states versions before R2.7.3 are not affected by CVE-2021-22779 |
What does this mean for affected devices?
NVD carries the Schneider Electric description of an "Authentication Bypass by Spoofing vulnerability ... that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller." NVD's Primary score is CVSS v3.1 9.1 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N); Schneider scores it 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) in SEVD-2021-194-01, counting availability as well. Schneider classes it CWE-290 (authentication bypass by spoofing). The record was published on 2021-07-14 (NVD, CVE record).
What does the attacker gain?
The engineering software, Control Expert or Process Expert, talks to the controller over Modbus on 502/tcp. An attacker who can imitate that conversation gets the same read and write access, which on a PLC means reading and changing the program and its data. CISA republished the original notice as ICSA-21-194-02 (CSAF), also scoring 9.8. The current notice says a proof-of-concept script that could exploit some of its vulnerabilities has been found, and it credits five researchers for this CVE, from Fortinet FortiGuard Labs, Tenable, Kaspersky ICS CERT, Armis and Bolean Tech.
Which products are affected and how is it fixed?
| Product (Schneider wording) | Affected | Fix |
|---|---|---|
| EcoStruxure Control Expert (incl. Unity Pro) | before V15.1 | V15.1 (step one) |
| EcoStruxure Process Expert (incl. Hybrid DCS) | before V2021 | V2021 (step one) |
| Modicon M580 CPU (BMEP*, BMEH*, excl. Safety) | before SV4.10 | SV4.10 |
| Modicon M580 CPU Safety (BMEP58S, BMEH58S) | before SV4.21 | SV4.21 (needs Control Expert V16.0 HF001) |
| Modicon M340 CPU (BMXP34*) | before V3.50 | V3.50 plus application password |
Schneider calls the software update "the first step in a two steps process"; the second is the controller firmware. The firmware took time: M340 V3.50 arrived in notice version 3.0.0 (April 2022); an M580 SV4.02 release was retracted for quality issues in version 7.0.0 (December 2022), SV4.10 followed in version 8.0.0 (March 2023), and the M580 CPU Safety fix in version 9.0.0 (13 August 2024). NVD's description and CPE also list SCADAPack RemoteConnect for x70, but version 4.0.0 of the notice states that RemoteConnect versions before R2.7.3 are not affected by CVE-2021-22779.
How do you mitigate it until both sides are updated?
For the controllers, Schneider lists network segmentation and a firewall that blocks unauthorized access to 502/tcp, the Access Control List, IPsec through BMENOC (M580) or BMENUA0100 (M580 Safety) modules or a VPN between the PLC and the engineering workstation, and CPU memory protection through a physical input (not available on Hot Standby CPUs, where IPsec is the alternative). For M580 CPU Safety it adds keeping the CPU in Safety mode. On the workstation side, store and exchange project files securely and harden the engineering PC.
Our Modicon UMAS protocol guide explains how the UMAS session works and why fixes need both sides, and the authentication bypass fix guide covers the class. Earlier and later session flaws on the same controllers are CVE-2018-7842 and CVE-2022-45789; CVE-2022-45788 and CVE-2019-6828 are other Modicon flaws.
CVE-2021-22779 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.01051, the 65.0th percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-20): status Modified; published 2021-07-14; NVD Primary CVSS v3.1 9.1 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N, v2 6.4; CWE-290 (Schneider); CPE Control Expert before 15.0 and 15.0/15.0 SP1, Process Expert all versions, SCADAPack RemoteConnect x70, M580 and M340 part-number firmware without version limit; reference SEVD-2021-194-01. — NVD
- Schneider SEVD-2021-194-01 v9.0.0 (published 2021-07-13, updated 2024-08-13), read 2026-11-20: CVE-2021-22779 CVSS v3.1 9.8, CWE-290, spoofing the Modbus communication between engineering software and controller; affected Control Expert before V15.1 (incl. Unity Pro), Process Expert before V2021, M580 before SV4.10, M580 CPU Safety before SV4.21, M340 before V3.50; Control Expert V15.1 and Process Expert 2021 are the first step of a two-step fix, controller firmware the second; M340 V3.50 with application password; M580 SV4.10; M580 Safety SV4.21 needs Control Expert V16.0 HF001; mitigations: firewall 502/tcp, ACL, IPsec via BMENOC/BMENUA0100, VPN, memory protection, Safety mode; proof-of-concept script discovered; history v3.0.0 (2022-04-12) M340, v4.0.0 (2022-07-12) RemoteConnect before R2.7.3 not affected by CVE-2021-22779, v7.0.0 (2022-12-13) M580 SV4.02 retracted, v8.0.0 (2023-03-14) M580 remediation, v9.0.0 (2024-08-13) M580 Safety remediation; researchers from Fortinet FortiGuard Labs, Tenable, Kaspersky ICS CERT, Armis, Friday Lab (Bolean Tech). — Schneider Electric SEVD-2021-194-01
- CISA ICSA-21-194-02 CSAF (Schneider Electric Modicon Controllers and Software, Update A, current release 2021-07-27), read 2026-11-20: CVE-2021-22779 CWE-290, CVSS v3.0 9.8. — CISA CSAF ICSA-21-194-02
- CVE record (checked 2026-11-20): state PUBLISHED, CNA Schneider Electric, published 2021-07-14; CNA CWE-290; no CNA CVSS metric; affected list as in the NVD description. — CVE.org
- Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries, released 2026-11-18), checked 2026-11-20. — CISA KEV
- EPSS 0.01051, percentile 0.64993, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories
Sources
- NVD
- Schneider Electric SEVD-2021-194-01: EcoStruxure Control Expert, Process Expert, SCADAPack RemoteConnect x70 and Modicon M580 and M340 (PDF)
- CISA CSAF: ICSA-21-194-02 Schneider Electric Modicon Controllers and Software (machine-readable advisory)
- CVE.org record CVE-2021-22779 (CNA: Schneider Electric)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Is updating Control Expert enough to fix CVE-2021-22779?
No. Schneider calls Control Expert V15.1 (or Process Expert 2021) the first step of a two-step fix. The second step is controller firmware: M580 SV4.10, M580 CPU Safety SV4.21 or M340 V3.50, with an application password on the M340.
Which M580 firmware should I use?
SV4.10 or later for the standard M580 CPU and SV4.21 or later for the M580 CPU Safety, per SEVD-2021-194-01. Schneider retracted an earlier SV4.02 release for quality issues in December 2022, and SV4.21 needs Control Expert V16.0 HF001 or later.
Is SCADAPack RemoteConnect affected?
NVD still lists SCADAPack RemoteConnect for x70 in its description and CPE. Schneider's notice, from version 4.0.0 (July 2022), states that RemoteConnect versions before R2.7.3 are not affected by CVE-2021-22779; R2.7.3 fixes other CVEs in the same notice.
How do I reduce the risk before the firmware update?
Block unauthorized access to 502/tcp with segmentation and a firewall, configure the Access Control List, and protect the engineering link with IPsec or a VPN, as Schneider recommends. Enable CPU memory protection through a physical input where the CPU is not a Hot Standby model.
Questions about this page?