Security Advisory

CVE-2023-27975: Control Expert Project Credential Leak

Last updated:
  • CVE-2023-27975

CVE-2023-27975 is a credential protection flaw (CWE-522) in Schneider Electric EcoStruxure Control Expert, the programming software for Modicon M340 and M580 PLCs: a local user who tampers with the engineering workstation's memory can get unauthorized access to the project file. NVD and Schneider score it 7.1. Control Expert v16.0 fixes it.

Vulnerability summary

CVSS base score

7.1

High severity

EPSS score (FIRST)

0.1%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-27975 · Source: NVD

Affected components

ComponentCPEVersion range
EcoStruxure Control Expertcpe:2.3:a:schneider-electric:ecostruxure_control_expert:*:*:*:*:*:*:*:*Before v16.0; fixed in v16.0 (Schneider SEVD-2024-044-01)
EcoStruxure Process Expertcpe:2.3:a:schneider-electric:ecostruxure_process_expert:*:*:*:*:*:*:*:*Before v2023; Schneider names 15.3 HF008 as the fixed version

What does this mean for affected devices?

NVD carries the Schneider Electric description: "CWE-522: Insufficiently Protected Credentials vulnerability exists that could cause unauthorized access to the project file in EcoStruxure Control Expert when a local user tampers with the memory of the engineering workstation." NVD's Primary score is CVSS v3.1 7.1 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N), the same as the Schneider CNA score, and the weakness is the CNA's CWE-522 (insufficiently protected credentials). NVD analysed the record, which was published on 2024-02-14 (NVD, CVE record).

How severe is CVE-2023-27975?

NVD and Schneider agree on 7.1: a local attacker with low privileges on the engineering workstation, low complexity and no user interaction, with high confidentiality and integrity impact and no availability impact. Schneider's SEVD-2024-044-01 also gives a CVSS v4.0 score of 7.2 (CVSS:4.0/AV:L/AC:L/AT:P/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N), and CISA's republication ICSA-24-331-03 of 2024-11-26 repeats 7.1. The CISA ADP SSVC entry in the CVE record reads exploitation none, automatable no, technical impact partial. Schneider credits Kaikai Yang with the report.

What does an attacker need for CVE-2023-27975?

The attacker needs a local account on the engineering workstation running Control Expert. By tampering with that workstation's memory, they can get unauthorized access to a project file, because the credential that protects it is not protected well enough in memory. Unlike CVE-2023-6409, where a hard-coded credential opens a protected project anywhere, this flaw needs access to the workstation itself. Shared engineering laptops, jump hosts used by several contractors and remote-access sessions are where a low-privileged user is most likely. With the project, the attacker can read or change the application logic that is later downloaded to Modicon M340 and M580 controllers. The controller-side flaw in the same notice is CVE-2023-6408.

Which products are affected, and what fixes them?

Product (Schneider wording) Affected Fixed
EcoStruxure Control Expert before v16.0 v16.0 (reboot the computer after installation)
EcoStruxure Process Expert before v2023 15.3 HF008, as the notice names it

NVD's CPEs match: ecostruxure_control_expert before 16.0 and ecostruxure_process_expert before 2023. Schneider's product status for this CVE lists only Control Expert and Process Expert. SEVD-2024-044-01 was first released on 2024-02-13 and is at version 5.0.0 (2026-09-08).

How do you mitigate CVE-2023-27975?

Update every engineering workstation to Control Expert v16.0 or later. Schneider's mitigations for Control Expert are: enable encryption on the application project and store application files in a secure location with access restricted to legitimate users; use application control software (Schneider names McAfee Application and Change Control); and follow the workstation, network and site hardening in its Recommended Cybersecurity Best Practices. For Process Expert, which keeps application files in its database, Schneider says not to export and store them outside the application. Limit interactive accounts on engineering workstations to the engineers who need them, since the attack needs a local user. Our Modicon and UMAS security guide covers Control Expert versions and workstation hardening, and the hard-coded credentials fix guide explains how credentials stored in software get recovered. Another Modicon project-file flaw is CVE-2022-45788.

CVE-2023-27975 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00149, the 4.1st percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-21): status Analyzed; published 2024-02-14; NVD Primary CVSS v3.1 7.1 CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N, Schneider CNA Secondary 7.1 same vector; CWE-522 (Schneider); CPEs ecostruxure_control_expert versionEndExcluding 16.0, ecostruxure_process_expert versionEndExcluding 2023. — NVD
  • Schneider Electric SEVD-2024-044-01 version 5.0.0 (released 2024-02-13, updated 2026-09-08), CSAF read 2026-11-21: CVE-2023-27975 CWE-522, CVSS v3.1 7.1, CVSS v4.0 7.2 CVSS:4.0/AV:L/AC:L/AT:P/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N; known affected Control Expert <v16.0 and Process Expert <v2023; fixed Control Expert 16.0 and Process Expert 15.3 HF008; mitigations: enable encryption on application project, store files in secure location, McAfee Application and Change Control, Recommended Cybersecurity Best Practices; credit Kaikai Yang. — Schneider Electric SEVD-2024-044-01
  • CISA ICSA-24-331-03 CSAF (republication released 2024-11-26, updated 2026-05-07), read 2026-11-21: CVE-2023-27975 CVSS v3 7.1; Control Expert <v16.0 and Process Expert <v2023 known affected. — CISA CSAF ICSA-24-331-03
  • CVE record (checked 2026-11-21): state PUBLISHED, CNA Schneider Electric, published 2024-02-14; CNA CWE-522, CVSS v3.1 7.1; CISA-ADP SSVC (exploitation none, automatable no, technical impact partial). — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21. — CISA KEV
  • EPSS 0.00149, 4.1st percentile, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2024-044-01: EcoStruxure Control Expert, Process Expert and Modicon M340, M580 and M580 Safety PLCs (PDF)
  3. Schneider Electric SEVD-2024-044-01 (CSAF)
  4. CISA CSAF: ICSA-24-331-03 Schneider Electric EcoStruxure Control Expert, Process Expert, and Modicon M340, M580 and M580 Safety PLCs (machine-readable advisory)
  5. CVE.org record CVE-2023-27975 (CNA: Schneider Electric)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which version fixes CVE-2023-27975?

EcoStruxure Control Expert v16.0. For Process Expert (affected before v2023), Schneider SEVD-2024-044-01 names version 15.3 HF008 as the fix.

Can CVE-2023-27975 be exploited over the network?

No. NVD and Schneider score it as a local attack that needs a low-privileged user on the engineering workstation who tampers with its memory.

How is it different from CVE-2023-6409?

CVE-2023-6409 is a hard-coded credential that opens a password-protected project file in Control Expert without any workstation access. CVE-2023-27975 needs a local user on the workstation running Control Expert. Both are fixed in v16.0.

Do Modicon controllers need a firmware update for this CVE?

No. Schneider lists only Control Expert and Process Expert as affected by CVE-2023-27975. The controller firmware updates in SEVD-2024-044-01 address CVE-2023-6408.