Security Advisory

CVE-2023-6409: Control Expert Project Hard-Coded Creds

Last updated:
  • CVE-2023-6409

CVE-2023-6409 is a hard-coded credential (CWE-798) in Schneider Electric EcoStruxure Control Expert, the programming software for Modicon M340 and M580 PLCs: it lets someone open a Control Expert project file protected with an application password without knowing that password. NVD and Schneider score it 7.7. Control Expert v16.0 fixes it.

Vulnerability summary

CVSS base score

7.7

High severity

EPSS score (FIRST)

0.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-6409 · Source: NVD

Affected components

ComponentCPEVersion range
EcoStruxure Control Expertcpe:2.3:a:schneider-electric:ecostruxure_control_expert:*:*:*:*:*:*:*:*Before v16.0; fixed in v16.0 (Schneider SEVD-2024-044-01)
EcoStruxure Process Expertcpe:2.3:a:schneider-electric:ecostruxure_process_expert:*:*:*:*:*:*:*:*Before v2023; Schneider names 15.3 HF008 as the fixed version

What does this mean for affected devices?

NVD carries the Schneider Electric description: "CWE-798: Use of Hard-coded Credentials vulnerability exists that could cause unauthorized access to a project file protected with application password when opening the file with EcoStruxure Control Expert." NVD's Primary score is CVSS v3.1 7.7 (CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N), the same as the Schneider CNA score, and the weakness is the CNA's CWE-798 (use of hard-coded credentials). NVD analysed the record, which was published on 2024-02-14 (NVD, CVE record).

How severe is CVE-2023-6409?

NVD and Schneider agree on 7.7: a local attack vector with low complexity and no privileges or user interaction, high confidentiality and integrity impact and no availability impact. "Local" here means the attacker has the project file and opens it in Control Expert; they do not need the controller. Schneider's SEVD-2024-044-01 also gives a CVSS v4.0 score of 8.5 (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N), and CISA's republication ICSA-24-331-03 of 2024-11-26 repeats 7.7. The CISA ADP SSVC entry in the CVE record reads exploitation none, automatable no, technical impact total. Schneider credits Jianshuang Ding with the report.

Why does the application password matter for the PLC?

The application password protects a Control Expert project, and the same password is the first mitigation Schneider gives for controller-side flaws such as CVE-2023-6408 in this notice. CVE-2023-6409 means a hard-coded credential in Control Expert lets someone open a password-protected project file without knowing that password. An attacker who gets a copy of a project from a share, a backup or a removable drive can then read and change the application logic offline. That makes project files as sensitive as the controllers themselves. The same notice lists CVE-2023-27975, where a local user tampers with workstation memory to reach the project file, and CVE-2022-45788 is a related Modicon flaw triggered by a malicious project file.

Which products are affected, and what fixes them?

Product (Schneider wording) Affected Fixed
EcoStruxure Control Expert before v16.0 v16.0 (reboot the computer after installation)
EcoStruxure Process Expert before v2023 15.3 HF008, as the notice names it

NVD's CPEs match: ecostruxure_control_expert before 16.0 and ecostruxure_process_expert before 2023. Schneider's product status for this CVE lists only Control Expert and Process Expert; the controller firmware updates in the same notice fix CVE-2023-6408, not this flaw. SEVD-2024-044-01 was first released on 2024-02-13 and is at version 5.0.0 (2026-09-08).

How do you mitigate CVE-2023-6409?

Update every engineering workstation to Control Expert v16.0 or later. Schneider's mitigations for Control Expert are: enable encryption on the application project and store application files in a secure location with access restricted to legitimate users; use application control software (Schneider names McAfee Application and Change Control); and follow the workstation, network and site hardening in its Recommended Cybersecurity Best Practices. For Process Expert, which keeps application files in its database, Schneider says not to export and store them outside the application. Treat any project file saved by an affected version as readable by whoever holds a copy. Our Modicon and UMAS security guide covers application passwords and Control Expert versions, and the hard-coded credentials fix guide explains this class of flaw.

CVE-2023-6409 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.0023, the 14.1st percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.

Evidence

  • NVD (read 2026-11-21): status Analyzed; published 2024-02-14; NVD Primary CVSS v3.1 7.7 CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N, Schneider CNA Secondary 7.7 same vector; CWE-798 (Schneider); CPEs ecostruxure_control_expert versionEndExcluding 16.0, ecostruxure_process_expert versionEndExcluding 2023. — NVD
  • Schneider Electric SEVD-2024-044-01 version 5.0.0 (released 2024-02-13, updated 2026-09-08), CSAF read 2026-11-21: CVE-2023-6409 CWE-798, CVSS v3.1 7.7, CVSS v4.0 8.5 CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N; known affected Control Expert <v16.0 and Process Expert <v2023; fixed Control Expert 16.0 (reboot after installation) and Process Expert 15.3 HF008; mitigations: enable encryption on application project, store files in secure location, McAfee Application and Change Control, Recommended Cybersecurity Best Practices; Process Expert: do not export and store files outside the application; credit Jianshuang Ding. — Schneider Electric SEVD-2024-044-01
  • CISA ICSA-24-331-03 CSAF (republication released 2024-11-26, updated 2026-05-07), read 2026-11-21: CVE-2023-6409 CVSS v3 7.7; Control Expert <v16.0 and Process Expert <v2023 known affected. — CISA CSAF ICSA-24-331-03
  • CVE record (checked 2026-11-21): state PUBLISHED, CNA Schneider Electric, published 2024-02-14; CNA CWE-798, CVSS v3.1 7.7; CISA-ADP SSVC (exploitation none, automatable no, technical impact total). — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21. — CISA KEV
  • EPSS 0.0023, 14.1st percentile, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2024-044-01: EcoStruxure Control Expert, Process Expert and Modicon M340, M580 and M580 Safety PLCs (PDF)
  3. Schneider Electric SEVD-2024-044-01 (CSAF)
  4. CISA CSAF: ICSA-24-331-03 Schneider Electric EcoStruxure Control Expert, Process Expert, and Modicon M340, M580 and M580 Safety PLCs (machine-readable advisory)
  5. CVE.org record CVE-2023-6409 (CNA: Schneider Electric)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which version fixes CVE-2023-6409?

EcoStruxure Control Expert v16.0; Schneider says to reboot the computer after installation. For Process Expert (affected before v2023), SEVD-2024-044-01 names version 15.3 HF008 as the fix.

Do I need to update the PLC firmware for CVE-2023-6409?

No. Schneider lists only Control Expert and Process Expert as affected by this CVE. The M340, M580, MC80 and Momentum firmware updates in the same notice fix CVE-2023-6408.

Is the application password still worth setting?

Yes. Schneider lists it first among the mitigations for controller-side flaws in the same notice. Use a Control Expert version from v16.0, encrypt the application project and restrict access to where project files are stored.

What does an attacker need to exploit it?

A copy of the project file and Control Expert. NVD and Schneider score it as a local attack with no privileges or user interaction, so the protection is controlling who can reach project files.