Security Advisory

CVE-2022-45789: Modicon Session Replay Auth Bypass

Last updated:
  • CVE-2022-45789

CVE-2022-45789 is an authentication bypass by capture-replay (CWE-294) in Schneider Electric Modicon controllers and EcoStruxure Control Expert: an attacker who hijacks an authenticated Modbus session can run unauthorized Modbus functions on the PLC. NVD scores it 9.8; Schneider scores it 8.1. Fixes: Control Expert V16.2 HF003, M580 SV4.20, M580 CPU Safety SV4.21, M340 SV3.70, Momentum SV2.90 and MC80 SV2.20.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-45789 · Source: NVD

Affected components

ComponentCPEVersion range
EcoStruxure Control Expertcpe:2.3:a:schneider-electric:ecostruxure_control_expert:*:*:*:*:*:*:*:*Versions before V16.2 HF003; fixed in V16.2 HF003 (Schneider SEVD-2023-010-06). NVD's CPE has no version limit
Modicon M340 CPU (part numbers BMXP34*)cpe:2.3:o:schneider-electric:modicon_m340_bmxp342020_firmware:*:*:*:*:*:*:*:*Versions before SV3.70; fixed in SV3.70 (Schneider SEVD-2023-010-06). NVD's CPEs have no version limit
Modicon M580 CPU (part numbers BMEP* and BMEH*, excluding M580 CPU Safety)cpe:2.3:o:schneider-electric:modicon_m580_bmep582040_firmware:*:*:*:*:*:*:*:*Versions before SV4.20; fixed in SV4.20 (Schneider SEVD-2023-010-06). NVD's CPEs have no version limit
Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S)cpe:2.3:o:schneider-electric:modicon_m580_bmep582040s_firmware:*:*:*:*:*:*:*:*Versions before SV4.21; fixed in SV4.21, which needs Control Expert V16.0 HF001 or later (Schneider SEVD-2023-010-06)
Modicon Momentum Unity M1E Processor (171CBU*)—Versions before SV2.90; fixed in SV2.90 (Schneider SEVD-2023-010-06). No NVD CPE
Modicon MC80 (BMKC80)—Versions before SV2.20; fixed in SV2.20, which needs Control Expert V16.4 or later (Schneider SEVD-2023-010-06 v7.0.0). No NVD CPE
EcoStruxure Process Expertcpe:2.3:a:schneider-electric:ecostruxure_process_expert:*:*:*:*:*:*:*:*NVD CPE: up to and including 2020; CNA record: all versions. Not in the current SEVD-2023-010-06 affected-products table; no fix named as of 2026-11-19

What does this mean for affected devices?

NVD carries Schneider Electric's description: "A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session." NVD's Primary score is CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H); the Schneider Electric CNA scores it 8.1 (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H). The record was published on 2023-01-31 (NVD, CVE record).

How severe is it, and why do the scores differ?

The only difference between the two v3.1 vectors is attack complexity. Schneider rates it high, because the attacker has to hijack a session that a legitimate engineer has already authenticated; NVD rates it low, which lifts the base score from 8.1 to 9.8. Schneider's notice SEVD-2023-010-06 (version 7.0.0, 8 September 2026) also gives a CVSS v4.0 score of 9.2 (CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N). CISA's ADP enrichment in the CVE record rates it under SSVC as exploitation "none", automatable "no" and technical impact "total" (2025-02-05).

What does an attacker gain by replaying a Modicon session?

Modicon M340 and M580 controllers are programmed and operated by EcoStruxure Control Expert over UMAS, which runs inside Modbus TCP on port 502/TCP. Once an engineer has logged in, the session can be captured and reused, so the attacker sends Modbus functions the controller treats as authorized, without knowing the application password. The researchers credited by Schneider, Jos Wetzels and Daniel dos Santos of Forescout, found it during the 2022 OT:ICEFALL work. Forescout's disclosure blog (February 2023) says the finding was held back at the vendor's request, calls it a broken authentication scheme, and shows that combined with CVE-2022-45788 it can lead to remote code execution on Modicon Unity PLCs. Forescout counted close to a thousand Modicon PLCs exposed online via Shodan.

Which products and versions are affected?

Product (Schneider wording) Affected Fixed
EcoStruxure Control Expert before V16.2 HF003 V16.2 HF003
Modicon M340 CPU (BMXP34*) before SV3.70 SV3.70
Modicon M580 CPU (BMEP*, BMEH*, excluding CPU Safety) before SV4.20 SV4.20
Modicon M580 CPU Safety (BMEP58S, BMEH58S) before SV4.21 SV4.21 (needs Control Expert V16.0 HF001 or later)
Modicon Momentum Unity M1E Processor (171CBU*) before SV2.90 SV2.90
Modicon MC80 (BMKC80) before SV2.20 SV2.20 (needs Control Expert V16.4 or later)

The table follows SEVD-2023-010-06 version 7.0.0. CISA's republication ICSA-23-227-01 (Update A, 2026-05-05) matches it except for MC80, which it still lists as all versions with no fix. NVD's CPE configuration lists Control Expert and M340/M580 firmware without a version limit and Process Expert up to 2020, and has no Momentum or MC80 entries. The notice's revision history says version 3.0.0 (August 2023) added all versions of EcoStruxure Process Expert, but the current affected-products table does not list Process Expert and names no fix for it.

How do you fix or mitigate it?

Update both ends of the link: the controller firmware and every Control Expert workstation that talks to it. Where you cannot update, Schneider lists, per product: an application password in the project properties, network segmentation with a firewall that blocks unauthorized access to port 502/TCP, the controller's Access Control List, secured communication (IPsec through a BMENOC or BMENUA0100 module on M580, or an external VPN firewall such as the Belden EAGLE40-07), and M580 memory protection bound to a physical input (not available on M580 Hot Standby CPUs). For Control Expert itself it lists a VPN between the PLCs and the engineering workstation and a hardened workstation. Our Modicon UMAS protocol security guide covers the session mechanism and firmware thresholds, the Modbus security guide covers port 502 filtering, and the authentication bypass fix guide covers the weakness class. Earlier UMAS session findings are CVE-2018-7842 (session ID brute force), CVE-2018-7846 (session disconnect) and CVE-2018-7847.

CVE-2022-45789 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.01464, the 74.2nd percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • NVD (read 2026-11-19): status Modified; published 2023-01-31T06:15:07.920; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; Schneider Electric ([email protected]) Secondary 8.1 CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H; CWE-294 (Schneider); CPE: EcoStruxure Control Expert without version limit, Process Expert up to 2020 inclusive, Modicon M340 BMXP34 and M580 BMEP/BMEH firmware without version limit; reference SEVD-2023-010-06. — NVD
  • Schneider SEVD-2023-010-06 version 7.0.0 (first published 10 January 2023, updated 8 September 2026), read 2026-11-19: CWE-294 capture-replay, CVSS v3.1 8.1 and CVSS v4.0 9.2; affected Control Expert before V16.2 HF003, M340 before SV3.70, M580 before SV4.20, M580 CPU Safety before SV4.21, Momentum Unity M1E before SV2.90, MC80 before SV2.20, each fixed in that version; M580 CPU Safety needs Control Expert v16.0 HF001 and MC80 needs v16.4 minimum; mitigations application password, port 502/TCP firewall, ACL, IPsec via BMENOC/BMENUA0100 or EAGLE40-07 VPN, M580 memory protection (not on Hot Standby), VPN and workstation hardening for Control Expert; revision 3.0.0 (8 August 2023) says all versions of EcoStruxure Process Expert are impacted; credits Jos Wetzels and Daniel dos Santos, Forescout Technologies. — Schneider Electric SEVD-2023-010-06
  • CISA ICSA-23-227-01 Update A (CSAF, current release 2026-05-05), read 2026-11-19: verbatim republication of SEVD-2023-010-06; CVSS v3.1 8.1, CWE-294; fixed Control Expert 16.2 HF003, M340 SV3.70, M580 SV4.20, M580 CPU Safety SV4.21, Momentum SV2.90; Modicon MC80 all versions with mitigations only. — CISA ICSA-23-227-01
  • Forescout blog (published 2023-02-13), read 2026-11-19: CVE-2022-45789 found in 2022 OT:ICEFALL research, held back at vendor's request; auth bypass with Schneider CVSS 8.1; combined with CVE-2022-45788 can lead to RCE on Modicon Unity PLCs; close to a thousand Modicon PLCs exposed online via Shodan. — Forescout
  • CVE.org record (read 2026-11-19): CNA Schneider Electric (schneider), state PUBLISHED, published 2023-01-31; CISA ADP SSVC 2.0.3 (2025-02-05): exploitation none, automatable no, technical impact total. — CVE.org
  • CISA KEV catalog version 2026.11.18 (1,786 entries): CVE-2022-45789 not listed as of 2026-11-19. — CISA KEV
  • FIRST EPSS dataset 2026-11-18: CVE-2022-45789 EPSS 0.01464, percentile 0.74151. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2023-010-06: EcoStruxure Control Expert, and Modicon M340, Momentum, MC80, M580 and M580 CPU Safety (version 7.0.0, 8 September 2026; PDF)
  3. CISA CSAF: ICSA-23-227-01 Schneider Electric EcoStruxure Control Expert, Process Expert, Modicon M340, M580 and M580 CPU (Update A, machine-readable advisory)
  4. Forescout: Deep lateral movement in OT networks (disclosure of CVE-2022-45788 and CVE-2022-45789)
  5. CVE.org record CVE-2022-45789 (CNA: Schneider Electric)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2022-45789?

Modicon M340 SV3.70, M580 SV4.20, M580 CPU Safety SV4.21, Momentum Unity M1E SV2.90 and MC80 SV2.20, together with EcoStruxure Control Expert V16.2 HF003. M580 CPU Safety SV4.21 needs Control Expert V16.0 HF001 or later to connect, and MC80 SV2.20 needs Control Expert V16.4 or later (per Schneider SEVD-2023-010-06 version 7.0.0).

Why does NVD score it 9.8 when Schneider scores it 8.1?

The vectors differ only in attack complexity. Schneider rates it high because the attacker has to hijack a session a legitimate user has already authenticated; NVD rates it low. Schneider also publishes a CVSS v4.0 score of 9.2 (per NVD and Schneider SEVD-2023-010-06).

Does an application password stop the replay?

Not on its own. The flaw is the reuse of a session that was already authenticated, so the password has been entered by then. Schneider lists the application password as one mitigation among several, alongside a firewall on port 502/TCP, the Access Control List, IPsec or VPN between workstation and PLC, and M580 memory protection (per Schneider SEVD-2023-010-06).

Is CVE-2022-45789 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries), CISA's SSVC enrichment records exploitation as none, and FIRST EPSS gives it 0.01464 (74.2nd percentile) in the 2026-11-18 dataset. Forescout did build a proof of concept that chained it with CVE-2022-45788 (per CISA KEV, CVE.org, FIRST EPSS and Forescout).

Is MC80 fixed, given that CISA's advisory says no fix?

Yes. Schneider's version 7.0.0 of the notice (8 September 2026) adds MC80 firmware SV2.20 as the fix. CISA's ICSA-23-227-01 Update A of 2026-05-05 predates that and still lists MC80 as all versions with no fix (per Schneider SEVD-2023-010-06 and CISA ICSA-23-227-01).