Security Advisory

CVE-2020-6986: Omron CJ PLC FINS Packet-Flood DoS

Last updated:
  • CVE-2020-6986

CVE-2020-6986 is an uncontrolled resource consumption flaw (CWE-400) in Omron CJ series PLCs, all versions: a series of specific FINS packets sent within a short period causes a service error on the PLC's Ethernet module, which leaves the PLC denying service. NVD, CISA and OMRON all score it 7.5. There is no firmware fix; the controls are filtering FINS port 9600 and source IP addresses.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-6986 · Source: NVD

Affected components

ComponentCPEVersion range
Omron PLC CJ1 seriescpe:2.3:o:omron:plc_cj1_firmware:*:*:*:*:*:*:*:*All versions (NVD, CISA ICSA-20-063-03, OMRON); no fixed firmware
Omron PLC CJ2 seriescpe:2.3:o:omron:plc_cj2_firmware:*:*:*:*:*:*:*:*All versions (NVD, CISA ICSA-20-063-03, OMRON); no fixed firmware

What does this mean for affected devices?

NVD's description: "In all versions of Omron PLC CJ Series, an attacker can send a series of specific data packets within a short period, causing a service error on the PLC Ethernet module, which in turn causes a PLC service denied result." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), the same as the CISA-ADP secondary entry, with CWE-400 (Uncontrolled Resource Consumption) from both NVD and CISA as CNA. NVD's CPE configuration covers omron:plc_cj1_firmware and omron:plc_cj2_firmware, all versions. The record was published on 2020-03-05 (NVD).

What does OMRON say?

CISA released ICSA-20-063-03 on 2020-03-03 for Omron PLC CJ series, all versions, with the same 7.5 vector, crediting Jipeng You (XDU) with the report and stating that no known public exploits specifically target the flaw (CISA CSAF). OMRON's notice of 2020-02-28 calls it "FINS protocol has a risk of flooding attack by malformed packet" and describes improper resource management in excessive malformed packet processing (OMRON notice, PDF).

The Omron spoofing and replay flaws reported by the same researcher, CVE-2019-18259 and CVE-2019-13533, and the UM lock flaw CVE-2019-18269 share the same network controls. Other industrial Ethernet stacks have had the same class of packet-flood denial of service, for example Siemens PROFINET in CVE-2019-10936 and CVE-2020-28400.

How do you mitigate it?

No fixed firmware is listed. CISA and OMRON recommend protecting the PLC with a firewall that blocks unnecessary remote access to FINS port 9600 and filtering the devices connected to the PLC by IP address; OMRON adds VPN-restricted remote access. A rate limit or an alert on unusual FINS packet rates toward a CJ CPU is a practical detection step. Our OMRON FINS protocol security guide covers segmentation and monitoring.

CVE-2020-6986 is not in the CISA KEV catalog as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.01592, the 76th percentile, in the 2026-11-17 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Resource exhaustion. Our practical guide covers how to detect, fix, verify and disclose it: How to fix SQL injection, XSS, resource exhaustion and deserialization flaws in embedded firmware.

Evidence

  • NVD description: in all versions of Omron PLC CJ Series, an attacker can send a series of specific data packets within a short period, causing a service error on the PLC Ethernet module and a PLC service denied result. NVD Primary and CISA-ADP CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; CWE-400 from NVD and ICS-CERT; CPE plc_cj1_firmware, plc_cj2_firmware all versions; published 2020-03-05. — NVD
  • ICSA-20-063-03 (2020-03-03): Omron PLC CJ series all versions; CWE-400, CVSS v3 7.5; no known public exploits specifically target this vulnerability; reported by Jipeng You (XDU); mitigations: filter FINS port 9600, filter IP addresses. — CISA ICSA-20-063-03 (CSAF)
  • OMRON notice (2020-02-28): all versions of CJ series PLCs; 'FINS protocol has a risk of flooding attack by malformed packet', CWE-400, CVSSv3 7.5; countermeasures: firewall, VPN, filtering FINS port 9600. — OMRON
  • Not in the CISA KEV catalog, version 2026.11.17 (1,782 entries), checked 2026-11-18. — CISA KEV
  • EPSS 0.01592, percentile 0.76121, dataset 2026-11-17. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-20-063-03: Omron PLC CJ Series
  3. CISA CSAF: ICSA-20-063-03 (machine-readable advisory)
  4. OMRON: Vulnerabilities in Omron CJ series PLCs (2020-02-28, PDF)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which Omron PLCs are affected by CVE-2020-6986?

All versions of the Omron CJ series; NVD's CPE data names CJ1 and CJ2 firmware (per NVD, CISA ICSA-20-063-03 and OMRON).

What happens when CVE-2020-6986 is triggered?

A series of specific packets sent within a short period causes a service error on the PLC's Ethernet module, which results in a PLC denial of service (per NVD and CISA ICSA-20-063-03).

Is there a firmware fix for CVE-2020-6986?

No fixed firmware is listed. CISA and OMRON recommend a firewall that blocks unnecessary access to FINS port 9600 and filtering the devices allowed to reach the PLC by IP address (per CISA ICSA-20-063-03 and OMRON).

Is CVE-2020-6986 in the CISA KEV catalog?

No, not as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.01592, the 76th percentile, in the 2026-11-17 dataset (per CISA KEV and FIRST EPSS).