CVE-2020-7484 is a denial-of-service flaw in the former 'password' feature of Schneider Electric TriStation 1131, the Triconex safety controller engineering software, exploitable when sites do not follow the dedicated-connection and keyswitch guidelines. NVD and CISA both score it 7.5. Schneider's bulletin lists versions 1.0 to 4.12.0 as affected and 4.13.0 as the fix.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
1.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-7484 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric TriStation 1131 (Triconex engineering software on Windows NT, XP or 7) | cpe:2.3:a:schneider-electric:tristation_1131:*:*:*:*:*:*:*:* | 1.0 to 4.12.0; fixed in 4.13.0, released 2015-01-26 (Schneider SESB-2020-105-01 V2.1, CISA ICSA-20-205-01; NVD CPE 1.0 up to excluding 4.13.0) |
What does this mean for affected devices?
NVD carries Schneider Electric's current CNA description, tagged "VERSION NOT SUPPORTED WHEN ASSIGNED": "A vulnerability with the former 'password' feature could allow a denial of service attack if the user is not following documented guidelines pertaining to dedicated TriStation connection and key-switch protection." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), with CVSS v2 4.3. NVD lists NVD-CWE-noinfo; CISA classes it CWE-400 (uncontrolled resource consumption). The record was published on 2020-04-16 and is PUBLISHED on CVE.org (NVD, CVE record).
Which TriStation 1131 versions are affected?
Schneider's SESB-2020-105-01 (V2.1, 23 June 2020) says the flaw affects TriStation 1131 "versions 1.0 through 4.12.0" and "was remediated in version 4.13.0", released 26 January 2015. CISA's ICSA-20-205-01 CSAF (23 July 2020) agrees, and NVD's CPE covers 1.0 up to, but excluding, 4.13.0. The NVD description text says the feature was removed in v4.9.1 and v4.10.1 on 30 May 2013, and the CVE.org record lists "v4.0.0 to v4.9.0, v4.10.0"; the bulletin's V2 and V2.1 revisions updated the affected and fixed versions, so treat anything below 4.13.0 as affected.
| Product | Affected (SESB-2020-105-01 V2.1, CISA, NVD CPE) | Fixed |
|---|---|---|
| TriStation 1131 on Windows NT, XP or 7 | 1.0 to 4.12.0 | 4.13.0 (26 January 2015) |
What does the denial of service depend on?
Both the vendor and CISA tie it to site practice: the attack works "if the user is not following documented guidelines pertaining to dedicated TriStation 1131 connection and key-switch protection". CISA and NVD both score it 7.5 with availability impact only (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H in the CSAF file). Schneider's bulletin gives no score.
Which other Triconex issues came out with it?
SESB-2020-105-01 lists five CVEs that the then-Invensys Triconex team had already fixed and that an independent researcher reported again in 2019: CVE-2020-7483 (cleartext data from the same password feature), CVE-2020-7484, CVE-2020-7485 (legacy support account), and two Tricon Communication Module issues, CVE-2020-7486 and CVE-2020-7491. The controller firmware flaws found after the TRITON incident are CVE-2018-8872 and CVE-2018-7522.
How do you fix or mitigate it?
Upgrade TriStation 1131 to 4.13.0 or later from Schneider's Process Automation support portal. Then apply the guidelines the CVE refers to: a dedicated TriStation connection on an isolated safety network, the workstation connected to no other network, controllers in locked cabinets, the keyswitch never left in PROGRAM and an operator-station alarm whenever it is. Our TriStation protocol guide covers monitoring that link, the IEC 61511 guide covers the SIS security risk assessment, and the input handling fix guide covers resource-exhaustion weaknesses.
CVE-2020-7484 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.01328, the 71.6th percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-20): status Modified; published 2020-04-16; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, v2 4.3; CWE NVD-CWE-noinfo; CPE tristation_1131 from 1.0 up to excluding 4.13.0 on Windows NT, XP or 7; description tagged VERSION NOT SUPPORTED WHEN ASSIGNED, names v4.9.1 and v4.10.1 (May 30, 2013). — NVD
- CVE record (checked 2026-11-20): state PUBLISHED, CNA Schneider Electric, published 2020-04-15; problem type denial of service; affected 'TriStation TS1131 (v4.0.0 to v4.9.0, v4.10.0)'; no CNA CVSS metric. — CVE.org
- Schneider Electric SESB-2020-105-01 V2.1 (updated 23 June 2020), read 2026-11-20: CVE-2020-7484, password feature in TriStation 1131 versions 1.0 through 4.12.0 could allow denial of service if the user is not following guidelines on dedicated TriStation 1131 connection and key-switch protection; remediated in 4.13.0 (1/26/2015); bulletin also lists CVE-2020-7483, 7485, 7486, 7491. — Schneider Electric SESB-2020-105-01
- CISA ICSA-20-205-01 CSAF (2020-07-23), read 2026-11-20: CVE-2020-7484 CWE-400, CVSS v3.0 7.5 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; TriStation 1131 1.0 through 4.12.0; 4.13.0 released January 26, 2015. — CISA CSAF ICSA-20-205-01
- Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-20. — CISA KEV
- EPSS 0.01328, percentile 0.71632, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories
Sources
- NVD: CVE-2020-7484
- CVE.org record CVE-2020-7484 (CNA: Schneider Electric)
- Schneider Electric Security Bulletin SESB-2020-105-01: Legacy Triconex Product Vulnerabilities (V2.1, PDF)
- CISA ICS Advisory ICSA-20-205-01: Schneider Electric Triconex TriStation and Tricon Communication Module
- CISA CSAF record for ICSA-20-205-01
- CISA Known Exploited Vulnerabilities catalog
- FIRST EPSS score for CVE-2020-7484
Frequently asked questions
Which TriStation 1131 version fixes CVE-2020-7484?
Version 4.13.0, released on 26 January 2015. Schneider SESB-2020-105-01 V2.1, CISA ICSA-20-205-01 and NVD's CPE all treat 1.0 to 4.12.0 as affected, although the NVD description text still names v4.9.1 and v4.10.1.
What site practices make the denial of service possible?
Not following Schneider's documented guidelines on a dedicated TriStation 1131 connection and keyswitch protection. Keep the TriStation link on the isolated safety network and the keyswitch out of PROGRAM, with an alarm when it is in PROGRAM (per Schneider SESB-2020-105-01 and CISA ICSA-20-205-01).
How severe is CVE-2020-7484?
NVD and CISA both score it 7.5, network attack with high availability impact and no confidentiality or integrity impact. Schneider's bulletin gives no CVSS score (per NVD and CISA ICSA-20-205-01).
Is CVE-2020-7484 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18). FIRST EPSS gives it 0.01328, the 71.6th percentile, in the 2026-11-19 dataset.
Questions about this page?