CVE-2019-13533 is an authentication bypass by capture-replay (CWE-294) in Omron CS and CJ series PLCs, all versions: an attacker who can watch FINS traffic between the PLC and its controller can replay the captured requests, which CISA says could open and close industrial valves. NVD and CISA both score it 8.1. There is no firmware fix; FINS traffic has to be kept away from untrusted hosts.
Vulnerability summary
CVSS base score
8.1
High severity
EPSS score (FIRST)
0.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-13533 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Omron PLC CS series CPU Units | cpe:2.3:o:omron:plc_cs_firmware:*:*:*:*:*:*:*:* | All versions (NVD, CISA ICSA-19-346-02); no fixed firmware |
| Omron PLC CJ series CPU Units | cpe:2.3:o:omron:plc_cj_firmware:*:*:*:*:*:*:*:* | All versions (NVD, CISA ICSA-19-346-02); no fixed firmware |
| Omron NJ and NX series CPU Units (OMRON notice); NX1P2 series (CISA CSAF Update A) | — | All versions, per OMRON's notice last modified 2023-01-10 and CISA ICSA-19-346-02 Update A; not in NVD's CPE configuration |
What does this mean for affected devices?
NVD's description: "In Omron PLC CJ series, all versions, and Omron PLC CS series, all versions, an attacker could monitor traffic between the PLC and the controller and replay requests that could result in the opening and closing of industrial valves." NVD's Primary score is CVSS v3.1 8.1 (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:L/I:L/A:H), and a CISA-ADP secondary submission on the record gives the same score and vector. Both NVD and CISA as CNA record CWE-294 (Authentication Bypass by Capture-replay). The CPE configuration covers omron:plc_cj_firmware and omron:plc_cs_firmware, all versions; the record was published on 2019-12-16 (NVD).
Which Omron products are affected?
CISA published the flaw in ICSA-19-346-02 on 2019-12-12 with the same 8.1 vector. Its machine-readable version, revised as Update A on 2022-11-29, lists the CS, CJ and NX1P2 series, all versions (CISA CSAF). OMRON's notice, last modified on 2023-01-10, lists all versions of CS, CJ, NJ and NX series CPU Units and says "some functions may be executed unintentionally" (OMRON notice, PDF). The same notice covers the spoofing flaw CVE-2019-18259 and the UM password lock CVE-2019-18269.
Replay works because FINS frames carry no session token, nonce or message authentication: JPCERT/CC's note on FINS, written with OMRON, lists capture-replay among the consequences of FINS carrying no authentication and says alterations of FINS messages cannot be detected (JVNTA#91513661). The NJ/NX controllers later received a fix for a separate capture-replay weakness in their own connection process, CVE-2022-33208, and a related debug entry point, CVE-2022-33971, with hard-coded credentials tracked as CVE-2022-34151.
How do you mitigate it?
No firmware fixes CVE-2019-13533. CISA and OMRON recommend blocking unnecessary remote access to FINS port 9600 and filtering the hosts allowed to reach the PLC by IP address, and OMRON adds VPN-restricted remote access. Because the attacker needs to see the traffic first, keep FINS on a dedicated control VLAN, never route it across business networks, and alert on any new FINS client. Our OMRON FINS protocol security guide explains how to baseline FINS talkers with a passive parser.
CVE-2019-13533 is not in the CISA KEV catalog as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.0087, the 59th percentile, in the 2026-11-17 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD description: an attacker could monitor traffic between the PLC and the controller and replay requests that could result in the opening and closing of industrial valves. NVD Primary and CISA-ADP CVSS v3.1 8.1 AV:N/AC:H/PR:N/UI:N/S:C/C:L/I:L/A:H; CWE-294 from NVD and ICS-CERT; CPE plc_cj_firmware and plc_cs_firmware, all versions; published 2019-12-16. — NVD
- ICSA-19-346-02 (2019-12-12, Update A 2022-11-29): CVE-2019-13533 CWE-294, CVSS v3 8.1 AV:N/AC:H/PR:N/UI:N/S:C/C:L/I:L/A:H; products CS, NX1P2, CJ series, all versions; mitigations: filter FINS port 9600, filter IP addresses. — CISA ICSA-19-346-02 (CSAF)
- OMRON notice (last modified 2023-01-10): CVE-2019-13533 CWE-294, CVSSv3 8.1; CS, CJ, NJ and NX series PLCs, 'some functions may be executed unintentionally'. — OMRON
- FINS has no authentication; alterations of FINS messages cannot be detected; issues include Authentication Bypass by Capture-replay. — JPCERT/CC JVNTA#91513661
- Not in the CISA KEV catalog, version 2026.11.17 (1,782 entries), checked 2026-11-18. — CISA KEV
- EPSS 0.0087, percentile 0.59391, dataset 2026-11-17. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
What can an attacker do with CVE-2019-13533?
Capture FINS requests between the PLC and its controller and replay them; NVD and CISA say this could result in the opening and closing of industrial valves (per NVD and CISA ICSA-19-346-02).
Which versions are affected by CVE-2019-13533?
All versions of Omron CS and CJ series PLCs per NVD; CISA's Update A adds NX1P2, and OMRON's notice lists all versions of CS, CJ, NJ and NX series CPU Units (per NVD, CISA and OMRON).
Is there a fix for CVE-2019-13533?
No firmware fix. CISA and OMRON recommend filtering FINS port 9600 and the IP addresses allowed to reach the PLC, and VPN-restricted remote access (per CISA ICSA-19-346-02 and OMRON).
Is CVE-2019-13533 in the CISA KEV catalog?
No, not as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.0087, the 59th percentile, in the 2026-11-17 dataset (per CISA KEV and FIRST EPSS).