CVE-2019-10922 lets an unauthenticated attacker with network access execute arbitrary code on a Siemens SIMATIC WinCC or PCS 7 installation that runs without the "Encrypted Communication" setting. Siemens lists every WinCC and PCS 7 version as affected and issued no code fix: the remediation is to enable Encrypted Communication, which is on by default from WinCC V7.5. NVD and Siemens both score it CVSS 9.8.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
2.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-10922 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC WinCC | cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:* | Siemens SSA-705517: WinCC V7.2 and earlier (all versions) and V7.3 and newer (all versions), when configured without Encrypted Communication. V7.3 and newer: enable Encrypted Communication (default from V7.5); V7.2 and earlier: upgrade and enable it, or apply defense in depth. NVD CPE: all simatic_wincc versions |
| Siemens SIMATIC PCS 7 | cpe:2.3:a:siemens:simatic_pcs_7:*:*:*:*:*:*:*:* | PCS 7 V8.0 and earlier (all versions) and V8.1 and newer (all versions). V8.1 and newer: enable Encrypted Communication; V8.0 and earlier: upgrade and enable it, or apply defense in depth. NVD CPE: all simatic_pcs_7 versions |
What does this mean for affected devices?
NVD's description, from Siemens, says: "An attacker with network access to affected installations, which are configured without 'Encrypted Communication', can execute arbitrary code. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected installation. No user interaction is required to exploit this security vulnerability." NVD's Primary scores are CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and CVSS v2 7.5. NVD records its own weakness as NVD-CWE-noinfo; Siemens, the CNA, gives CWE-306 (missing authentication for a critical function). NVD's CPE configuration covers every simatic_wincc and simatic_pcs_7 version (NVD, CVE record).
What does Siemens say?
Siemens advisory SSA-705517 (V1.0, 2019-05-14) lists four rows, all with "All versions" affected: PCS 7 V8.0 and earlier, PCS 7 V8.1 and newer, WinCC V7.2 and earlier, and WinCC V7.3 and newer. Siemens scores the flaw CVSS v3.0 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C) and says that at the time of publication no public exploitation was known. Vladimir Dashchenko and Sergey Temnikov of Kaspersky Lab ICS CERT reported it.
The remediation is configuration, not a patch. For WinCC V7.3 and newer and PCS 7 V8.1 and newer, Siemens says to enable "Encrypted Communication", and adds that starting with WinCC V7.5 it is enabled by default. For WinCC V7.2 and earlier and PCS 7 V8.0 and earlier, which do not offer the mode, the choice is to upgrade to a newer version and enable it, or to apply the defense-in-depth concept from Siemens' operational guidelines.
What does CISA say?
CISA advisory ICSA-19-134-02 (CSAF), "Siemens SIMATIC WinCC and SIMATIC PCS 7", gives CVSS v3.0 9.8 and CWE-306, the same four product rows and the same Encrypted Communication remediation, and adds CISA's standard practices: minimize network exposure, keep control networks behind firewalls and isolated from business networks, and use VPNs for remote access.
How do I check a plant?
- Check the Encrypted Communication setting on every WinCC and PCS 7 station. Siemens names it as the default only from V7.5, so stations on earlier versions need a manual check.
- Plan the move off WinCC V7.2 and PCS 7 V8.0 or earlier; these lines cannot enable the mode.
- Until then, keep the stations in their own cell, reachable only from the WinCC servers and clients that need them.
The Siemens WinCC and PCS 7 guide explains what Encrypted Communication covers across the WinCC CVE families. CVE-2014-8551 and CVE-2016-5743 are earlier unauthenticated code execution flaws on the WinCC server, and CVE-2018-4832 is a denial of service that Encrypted Communication also completely mitigates. The OT/ICS security guide for small manufacturers covers cell segmentation.
CVE-2019-10922 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0264, a percentile of 86.3, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2019-05-14; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H and CVSS v2 7.5; NVD CWE NVD-CWE-noinfo, Siemens CWE-306; CPEs simatic_pcs_7 up to 8.0 and from 8.1, simatic_wincc up to 7.2 and from 7.3. — NVD
- Siemens SSA-705517 V1.0 (read 2026-11-28): all WinCC and PCS 7 versions affected without Encrypted Communication; remediation enable Encrypted Communication, default from WinCC V7.5; older lines upgrade or defense in depth; CVSS v3.0 9.8; credit Kaspersky Lab ICS CERT. — Siemens ProductCERT SSA-705517
- CISA ICSA-19-134-02 CSAF (read 2026-11-28): CVSS v3.0 9.8, CWE-306, same product rows and remediation. — CISA ICSA-19-134-02
- CVE record (read 2026-11-28): state PUBLISHED, assigner siemens, CWE-306. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.02640, percentile 0.86323, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Is there a software update for CVE-2019-10922?
No code fix is listed. Siemens SSA-705517 says to enable "Encrypted Communication" on WinCC V7.3 and newer and PCS 7 V8.1 and newer; older lines must be upgraded to use it or protected with defense in depth.
Is Encrypted Communication on by default?
Siemens says it is enabled by default starting with WinCC V7.5. On WinCC V7.3 and V7.4 and on PCS 7 V8.1 and newer, Siemens' remediation is to enable it, so check each station.
Why does NVD list a different CWE from Siemens?
NVD records its own weakness as NVD-CWE-noinfo (insufficient information), while Siemens as the CNA and CISA's ICSA-19-134-02 use CWE-306, missing authentication for a critical function. Both score it CVSS 9.8.
Is CVE-2019-10922 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0264 (percentile 86.3) in the 2026-11-27 dataset.
Questions about this page?