Security Advisory

CVE-2014-8551: SIMATIC WinCC Server Remote Code Execution

Last updated:
  • CVE-2014-8551

CVE-2014-8551 is an unauthenticated remote code execution flaw in the server component of Siemens SIMATIC WinCC. Crafted packets sent to the WinCC server can run code on it, and because PCS 7 incorporates WinCC, PCS 7 V7.1 to V8.1 and TIA Portal V13 are affected too. NVD scores it CVSS v2 10.0. Siemens fixed it in WinCC V7.2 Update 9, V7.3 Update 2 and TIA Portal V13 Update 6.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

5.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2014-8551 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Siemens SIMATIC WinCC (V7.0, V7.2, V7.3)cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:*Siemens SSA-134508: V7.0 SP3 and earlier, V7.2 before Update 9, V7.3 before Update 2. Fixed in V7.0 SP2 Update 11, V7.0 SP3 Update 7, V7.2 Update 9 and V7.3 Update 2. NVD CPEs list 7.0 to 7.0 SP3, 7.2 Updates 1 to 8 and 7.3 Update 1
Siemens SIMATIC PCS 7 (WinCC incorporated)cpe:2.3:a:siemens:simatic_pcs7:*:*:*:*:*:*:*:*V7.1 SP4 and earlier; V8.0 before V8.0 SP2 with WinCC V7.2 Update 9; V8.1 before V8.1 with WinCC V7.3 Update 2. PCS 7 is fixed by the WinCC update plus the OpenPCS 7, Route Control and BATCH updates listed in SSA-134508
Siemens TIA Portal V13 (including WinCC Professional Runtime)cpe:2.3:a:siemens:simatic_tiaportal:13.0:*:*:*:*:*:*:*All versions before V13 Update 6; fixed in WinCC V13 Update 6

What does this mean for affected devices?

NVD's description reads: "The WinCC server in Siemens SIMATIC WinCC 7.0 through SP3, 7.2 before Update 9, and 7.3 before Update 2; SIMATIC PCS 7 7.1 through SP4, 8.0 through SP2, and 8.1; and TIA Portal 13 before Update 6 allows remote attackers to execute arbitrary code via crafted packets." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-94; there is no NVD v3 score. MITRE assigned the CVE, and the CVE record carries no CNA score (NVD, CVE record).

What does Siemens say?

Siemens advisory SSA-134508 (V1.4, last updated 2015-02-06, first published 2014-11-21) says "a component within WinCC could allow remote code execution for unauthenticated users if specially crafted packets are sent to the WinCC server". Siemens scores it CVSS v2 base 10.0, temporal 8.3 (AV:N/AC:L/Au:N/C:C/I:C/A:C/E:F/RL:OF/RC:C). The only mitigating factor it names is that the attacker must have network access to the affected system. The same advisory covers CVE-2014-8552, which let unauthenticated users extract arbitrary files from the WinCC server.

The fixed versions are WinCC V7.0 SP2 Update 11, V7.0 SP3 Update 7, V7.2 Update 9 and V7.3 Update 2, and WinCC V13 Update 6 for TIA Portal V13 including WinCC Professional Runtime. PCS 7 V7.1 SP4, V8.0 SP2 and V8.1 need the matching WinCC update plus updates for OpenPCS 7, Route Control and BATCH, which the advisory lists per release. Until the updates are installed, Siemens advises running WinCC servers and engineering stations only within a trusted network, letting them communicate only over encrypted channels (the "Encrypted Communications" feature in WinCC V7.3, or a VPN tunnel), restricting access to the WinCC server to trusted entities, and using application whitelisting and virus scanners.

What does CISA say?

CISA advisory ICSA-14-329-02D (CSAF), "Siemens SIMATIC WinCC, PCS7, and TIA Portal Vulnerabilities", republishes the Siemens product list and updates with CVSS v2 10.0. It classifies the flaw as CWE-284 (improper access control), where NVD uses CWE-94. CISA adds its standard practices: keep control system devices off the internet, put control networks behind firewalls isolated from business networks, and use up-to-date VPNs for remote access.

What should a WinCC or PCS 7 owner do?

  1. Record the full WinCC version, including the Update level, on every server, client and engineering station; a PCS 7 release number alone does not show whether the WinCC fix is installed.
  2. Install the fixed WinCC Update for the line (or a later one), and the OpenPCS 7, Route Control and BATCH updates on PCS 7.
  3. Keep the WinCC server reachable only from the stations that need it, and use Encrypted Communication or a VPN between them.

The Siemens WinCC and PCS 7 guide places this flaw among the other WinCC crafted-packet issues. CVE-2016-5743 repeated the same pattern two years later, CVE-2019-10922 made Encrypted Communication the fix, and CVE-2010-2772 is the older hard-coded WinCC database password. The OT/ICS security guide for small manufacturers covers segmenting SCADA servers.

CVE-2014-8551 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.05271, a percentile of 93.3, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Command injection. Our practical guide covers how to detect, fix, verify and disclose it: How to fix command injection in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2014-11-26; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no v3 metric; CWE-94; CPEs simatic_wincc 7.0 to 7.0 SP3, 7.2 Updates 1 to 8, 7.3 Update 1, simatic_pcs7 7.1 SP1 to 8.1, simatic_tiaportal 13.0. — NVD
  • Siemens SSA-134508 V1.4 PDF (read 2026-11-28): affected and fixed versions of WinCC, PCS 7 and TIA Portal V13; CVSS v2 base 10.0, temporal 8.3 AV:N/AC:L/Au:N/C:C/I:C/A:C/E:F/RL:OF/RC:C; mitigations: trusted network, Encrypted Communications or VPN, restrict access, whitelisting. — Siemens ProductCERT SSA-134508
  • CISA ICSA-14-329-02D CSAF (read 2026-11-28): CVSS v2 10.0, CWE-284; same affected products and Siemens updates. — CISA ICSA-14-329-02D
  • CVE record (read 2026-11-28): state PUBLISHED, assigner mitre, no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.05271, percentile 0.93336, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens SSA-134508: Vulnerabilities in SIMATIC WinCC, PCS 7 and WinCC in TIA Portal
  3. CISA ICSA-14-329-02D: Siemens SIMATIC WinCC, PCS7, and TIA Portal Vulnerabilities
  4. CISA ICSA-14-329-02D CSAF (machine-readable advisory)
  5. CVE record CVE-2014-8551 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which WinCC versions fix CVE-2014-8551?

Siemens SSA-134508 lists WinCC V7.0 SP2 Update 11, V7.0 SP3 Update 7, V7.2 Update 9 and V7.3 Update 2, and WinCC V13 Update 6 for TIA Portal V13 including WinCC Professional Runtime.

Why is PCS 7 affected by a WinCC flaw?

PCS 7 incorporates WinCC, so Siemens lists PCS 7 V7.1 SP4 and earlier, V8.0 and V8.1 as affected. The PCS 7 fix is the WinCC update for the release plus updates for OpenPCS 7, Route Control and BATCH.

Does an attacker need credentials?

No. Siemens says the component allows remote code execution for unauthenticated users who send crafted packets to the WinCC server. The only mitigating factor it names is that the attacker must have network access to the system.

Is CVE-2014-8551 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.05271 (percentile 93.3) in the 2026-11-27 dataset.