Security Advisory

CVE-2016-5743: SIMATIC WinCC and PCS 7 Remote Code Execution

Last updated:
  • CVE-2016-5743

CVE-2016-5743 is an unauthenticated remote code execution flaw in Siemens SIMATIC WinCC and WinCC Runtime Professional: specially crafted packets sent to a station can run code on it. PCS 7 V7.1 SP4 to V8.2 is affected through its WinCC, BATCH, Route Control and OpenPCS 7 components. NVD and Siemens both score it CVSS 9.8. Siemens fixed it in WinCC V7.3 Update 10, V7.4 Update 1 and Runtime Professional V13 SP1 Update 9, among others.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

10.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2016-5743 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Siemens SIMATIC WinCC V7.0 to V7.4cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:*Siemens SSA-378531: V7.0 SP2 and earlier before V7.0 SP2 Update 12, V7.0 SP3 before Update 8, V7.2 before Update 13, V7.3 before Update 10, V7.4 before Update 1. NVD CPE: simatic_wincc up to and including 7.4
Siemens SIMATIC PCS 7 (WinCC, BATCH, Route Control, OpenPCS 7)cpe:2.3:a:siemens:simatic_openpcs_7:*:*:*:*:*:*:*:*V7.1 SP4 and earlier, V8.0, V8.1 and V8.2 before the WinCC, BATCH, Route Control and OpenPCS 7 updates in SSA-378531 (for example V8.2 with WinCC V7.4 Update 1 and OpenPCS 7 V8.2 Update 1). NVD CPEs: simatic_batch up to 7.1, simatic_openpcs_7 up to 8.2
Siemens SIMATIC WinCC Runtime Professional—All versions before V13 SP1 Update 9; fixed in V13 SP1 Update 9 (no separate NVD CPE)

What does this mean for affected devices?

NVD's description reads: "Siemens SIMATIC WinCC before 7.3 Update 10 and 7.4 before Update 1, SIMATIC BATCH before 8.1 SP1 Update 9 as distributed in SIMATIC PCS 7 through 8.1 SP1, SIMATIC OpenPCS 7 before 8.1 Update 3 as distributed in SIMATIC PCS 7 through 8.1 SP1, SIMATIC OpenPCS 7 before 8.2 Update 1 as distributed in SIMATIC PCS 7 8.2, and SIMATIC WinCC Runtime Professional before 13 SP1 Update 9 allow remote attackers to execute arbitrary code via crafted packets." NVD's Primary scores are CVSS v3.0 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and CVSS v2 10.0, with CWE-20. MITRE assigned the CVE; the CVE record has no CNA score (NVD, CVE record).

What does Siemens say?

Siemens advisory SSA-378531 (V1.3, published 2016-07-22, last updated 2016-11-07) says "specially crafted packets sent to SIMATIC WinCC or WinCC Runtime Professional could allow remote code execution for unauthenticated users". Siemens scores it CVSS v3.0 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C), the same base score as NVD, and notes that the attacker must have network access to the affected system. Sergey Temnikov and Vladimir Dashchenko of Kaspersky Lab reported it. The same advisory covers CVE-2016-5744, a file extraction flaw that affects only WinCC V7.0 and V7.2.

The fixed versions are WinCC V7.0 SP2 Update 12, V7.0 SP3 Update 8, V7.2 Update 13, V7.3 Update 10 and V7.4 Update 1, and WinCC Runtime Professional V13 SP1 Update 9. For PCS 7, Siemens lists a WinCC, BATCH, Route Control and OpenPCS 7 update per release (V7.1 SP4, V8.0 SP2, V8.1 SP1 and V8.2). Until the updates are applied, Siemens recommends running WinCC, Runtime Professional and PCS 7 stations within a trusted network, letting them communicate only via encrypted channels ("Encrypted Communications" in WinCC V7.3 and PCS 7 V8.1 SP1, or a VPN tunnel), restricting access to trusted entities, and using application whitelisting and virus scanners.

What does CISA say?

CISA advisory ICSA-16-208-01C (CSAF), "Siemens SIMATIC WinCC, PCS 7, and WinCC Runtime Professional Vulnerabilities (Update C)", gives the same CVSS v3.0 9.8, CWE-20 and update list, and repeats CISA's standard advice to keep control networks off the internet and behind firewalls.

What should a WinCC or PCS 7 owner do?

  1. Check every WinCC station against the Update level for its line; V7.3 needs Update 10 and V7.4 needs Update 1 or later.
  2. On PCS 7, install the WinCC update and the BATCH, Route Control and OpenPCS 7 updates for the release; updating WinCC alone leaves the add-ons exposed.
  3. Enable Encrypted Communication between stations and keep them in a segmented cell with no route from the office network.

The Siemens WinCC and PCS 7 guide lists this flaw among the WinCC crafted-packet issues. CVE-2014-8551 is the 2014 predecessor with the same pattern, and CVE-2019-10922 is the 2019 flaw for which Siemens made Encrypted Communication the fix. The KEV and EPSS prioritization guide explains how to weigh an EPSS percentile like this one.

CVE-2016-5743 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.10491, a percentile of 96.5, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2016-07-22; NVD Primary CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H and CVSS v2 10.0; CWE-20; CPEs simatic_wincc up to 7.3 and 7.4, simatic_batch up to 7.1, simatic_openpcs_7 up to 8.1 and 8.2. — NVD
  • Siemens SSA-378531 V1.3 PDF (read 2026-11-28): affected and fixed versions of WinCC, PCS 7 and WinCC Runtime Professional; CVSS v3.0 9.8 with temporal vector E:P/RL:O/RC:C; CVE-2016-5744 affects only WinCC V7.0 and V7.2; credit Kaspersky Lab; mitigations. — Siemens ProductCERT SSA-378531
  • CISA ICSA-16-208-01C CSAF (read 2026-11-28): CVSS v3.0 9.8, CWE-20, same update list. — CISA ICSA-16-208-01C
  • CVE record (read 2026-11-28): state PUBLISHED, assigner mitre, no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.10491, percentile 0.96493, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens SSA-378531: Vulnerabilities in SIMATIC WinCC, PCS 7 and WinCC Runtime Professional
  3. CISA ICSA-16-208-01C: Siemens SIMATIC WinCC, PCS 7, and WinCC Runtime Professional
  4. CISA ICSA-16-208-01C CSAF (machine-readable advisory)
  5. CVE record CVE-2016-5743 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which WinCC updates fix CVE-2016-5743?

Siemens SSA-378531 lists WinCC V7.0 SP2 Update 12, V7.0 SP3 Update 8, V7.2 Update 13, V7.3 Update 10 and V7.4 Update 1, and WinCC Runtime Professional V13 SP1 Update 9.

Is updating WinCC enough on a PCS 7 system?

No. Siemens lists separate BATCH, Route Control and OpenPCS 7 updates for each PCS 7 release (V7.1 SP4, V8.0 SP2, V8.1 SP1 and V8.2) alongside the WinCC update.

What can be done before the update is installed?

Siemens recommends running the stations within a trusted network, using Encrypted Communications (WinCC V7.3, PCS 7 V8.1 SP1) or a VPN tunnel between them, restricting access to trusted entities, and using application whitelisting and virus scanners.

Is CVE-2016-5743 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.10491 (percentile 96.5) in the 2026-11-27 dataset.