CVE-2018-4832 is a denial of service in the RPC service of Siemens SIMATIC WinCC, PCS 7, WinCC Runtime Professional and SIMATIC NET PC Software: specially crafted messages stop remote and local communication, and only a reboot restores it. NVD and Siemens score it CVSS 7.5. Siemens fixed it in WinCC V7.4 SP1 Update 4, PCS 7 V8.2 SP1 and V9.0 SP1, among others, lists no fix for PCS 7 V8.1 and earlier, and says Encrypted Communication completely mitigates it.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
2.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2018-4832 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC WinCC and WinCC Runtime Professional | cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:* | WinCC V7.2 and earlier before 7.2 Upd 15, V7.3 before 7.3 Upd 16, V7.4 before V7.4 SP1 Upd 4; Runtime Professional V13 before V13 SP2 Upd2, V14 before V14 SP1 Upd5; fixed in those updates or later (Siemens SSA-348629) |
| Siemens SIMATIC PCS 7 with BATCH, Route Control and OpenPCS 7 | cpe:2.3:a:siemens:openpcs_7:*:*:*:*:*:*:*:* | PCS 7 V8.2 before V8.2 SP1 and V9.0 before V9.0 SP1 (fixed in those). No fix: PCS 7 V8.1 and earlier, OpenPCS 7 V8.0 and earlier, BATCH V7.1 and earlier, Route Control V8.1 and earlier. Fixed add-ons: OpenPCS 7 V8.1 Upd 5, BATCH V8.0 SP1 Upd21, V8.1 SP1 Upd16, V8.2 Upd10 |
| Siemens SIMATIC NET PC Software | — | V14 before V14 SP1 Update 14; V15 before V15 SP1; fixed in those versions or later |
| Siemens SPPA-T3000 Application Server | — | All versions before Service Pack R8.2 SP2; update via Siemens Energy service (CISA ICSA-19-351-02) |
What does this mean for affected devices?
NVD's description, from Siemens, says: "Specially crafted messages sent to the RPC service of the affected products could cause a Denial-of-Service condition on the remote and local communication functionality of the affected products. A reboot of the system is required to recover the remote and local communication functionality." It lists OpenPCS 7, SIMATIC BATCH, NET PC Software, PCS 7, Route Control, WinCC Runtime Professional, WinCC and the SPPA-T3000 Application Server. NVD's Primary scores are CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H) and CVSS v2 4.3, with CWE-20 (improper input validation), the CWE Siemens uses too (NVD, CVE record).
What does Siemens say?
Siemens advisory SSA-348629 ("Denial-of-Service Vulnerability in SIMATIC PCS 7, SIMATIC WinCC, SIMATIC WinCC Runtime Professional and SIMATIC NET PC Software", first published 2018-03-27, current version 10 of 2022-04-12) scores the flaw CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C), the same base score as NVD.
Fixed versions: WinCC 7.2 Upd 15, 7.3 Upd 16 and V7.4 SP1 Upd 4; WinCC Runtime Professional V13 SP2 Upd2 and V14 SP1 Upd5; NET PC Software V14 SP1 Update 14 and V15 SP1; PCS 7 V8.2 SP1, and PCS 7 V9.0 SP1, which includes OpenPCS 7 V9.0 Upd1, BATCH V9.0 SP1, Route Control V9.0 Upd1 and WinCC V7.4 SP1 Upd4; OpenPCS 7 V8.1 Upd 5; and BATCH V8.0 SP1 Upd21, V8.1 SP1 Upd16 and V8.2 Upd10. Siemens lists no fix for PCS 7 V8.1 and earlier, OpenPCS 7 V8.0 and earlier, BATCH V7.1 and earlier, and Route Control V8.1 and earlier.
For every listed product, Siemens says to make WinCC, Runtime Professional and PCS 7 stations communicate via encrypted channels, by activating "Encrypted Communication" in WinCC V7.3 or newer and PCS 7 V8.1 or newer, and states that enabling it "completely mitigates the vulnerability". It also recommends VPNs between cells.
What does CISA say?
CISA advisory ICSA-18-088-03 (CSAF), at Update G, gives the same 7.5 score, CWE-20 and product list. The same CVE also appears in CISA's ICSA-19-351-02 (CSAF) for Siemens Energy SPPA-T3000: the Application Server is affected before Service Pack R8.2 SP2, which owners obtain through Siemens Energy service management, and CISA's mitigations include restricting access to the Application Highway with the SPPA-T3000 firewall and connecting external components only to the SPPA-T3000 DMZ.
What should an owner do?
- Enable Encrypted Communication on WinCC V7.3 or newer and PCS 7 V8.1 or newer, which Siemens says fully mitigates the flaw.
- Install the fixed update for each product; plan the move off PCS 7 V8.1 and earlier, which has no fix.
- Keep RPC traffic to WinCC and PCS 7 stations inside the cell, with VPNs between cells.
The Siemens WinCC and PCS 7 guide lists the lines that drop out of Siemens' fix tables, including PCS 7 V8.1 for this CVE. CVE-2019-10922 is another flaw for which Encrypted Communication is the remediation, and CVE-2016-5743 is an earlier crafted-packet flaw in the same products. The KEV and EPSS prioritization guide explains how to rank a denial of service against code execution flaws.
CVE-2018-4832 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0242, a percentile of 84.9, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2018-04-24; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H and CVSS v2 4.3 AV:N/AC:M/Au:N/C:N/I:N/A:P; CWE-20; CPEs openpcs_7, simatic_batch and other affected products. — NVD
- Siemens SSA-348629 CSAF version 10, 2022-04-12 (read 2026-11-28): CVSS v3.1 7.5 with E:P/RL:O/RC:C; fixed versions per product; no fix for PCS 7 V8.1 and earlier, OpenPCS 7 V8.0 and earlier, BATCH V7.1 and earlier, Route Control V8.1 and earlier; Encrypted Communication completely mitigates; VPN between cells. — Siemens ProductCERT SSA-348629
- CISA ICSA-18-088-03 (Update G) CSAF (read 2026-11-28): CVSS v3.1 7.5, CWE-20, same products. — CISA ICSA-18-088-03
- CISA ICSA-19-351-02 CSAF (read 2026-11-28): SPPA-T3000 Application Server before Service Pack R8.2 SP2; update via Siemens Energy service management; restrict Application Highway with SPPA-T3000 firewall; external components only to the DMZ. — CISA ICSA-19-351-02
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.02420, percentile 0.84918, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
- NVD
- Siemens SSA-348629: Denial-of-Service Vulnerability in SIMATIC PCS 7, WinCC, WinCC Runtime Professional and NET PC Software
- CISA ICSA-18-088-03: Siemens SIMATIC PCS 7, WinCC, WinCC Runtime Professional, and NET PC Software
- CISA ICSA-18-088-03 CSAF (machine-readable advisory)
- CISA ICSA-19-351-02: Siemens SPPA-T3000
- CVE record CVE-2018-4832 (CVE Services JSON)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Does Encrypted Communication stop CVE-2018-4832?
Yes. Siemens SSA-348629 says enabling "Encrypted Communication" in WinCC V7.3 or newer and PCS 7 V8.1 or newer completely mitigates the vulnerability.
Which PCS 7 versions have no fix?
Siemens lists no fix for PCS 7 V8.1 and earlier, OpenPCS 7 V8.0 and earlier, BATCH V7.1 and earlier, and Route Control V8.1 and earlier. PCS 7 V8.2 is fixed in V8.2 SP1 and V9.0 in V9.0 SP1.
How does a station recover after an attack?
Siemens says a reboot of the system is required to recover the remote and local communication functionality.
Is CVE-2018-4832 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0242 (percentile 84.9) in the 2026-11-27 dataset.