CVE-2017-6032 is a session-related weakness in Schneider Electric's Modicon Modbus protocol that leaves it open to brute-force attacks. NVD scores it 5.3 (medium) with a low confidentiality impact. CISA advisory ICSA-17-101-01 of 11 April 2017 names the Modicon Momentum M1E controllers as having no built-in compensating controls.
Vulnerability summary
CVSS base score
5.3
Medium severity
EPSS score (FIRST)
1.7%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2017-6032 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Modicon Modbus protocol (Modbus service) | cpe:2.3:o:schneider-electric:modbus_firmware:-:*:*:*:*:*:*:* | all versions (NVD, CISA ICSA-17-101-01) |
| Modicon Momentum M1E 171CBU98090 and 171CBU98091 | — | all versions; no built-in compensating controls (CISA ICSA-17-101-01) |
| Modicon M340, Premium and Quantum | — | mitigate with Application Password, input or key switch, Access Control List (CISA ICSA-17-101-01) |
What does this mean for affected devices?
NVD describes CVE-2017-6032 as a "Violation of Secure Design Principles issue" in which "the Modicon Modbus protocol has a session-related weakness making it susceptible to brute-force attacks." NVD's Primary score is CVSS v3.0 5.3 (medium), vector CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N, and its CVSS v2 score is 5.0. NVD's Primary weakness is CWE-358, while CISA's record gives CWE-657 (NVD).
The finding comes from CISA's ICSA-17-101-01, published 11 April 2017, which scores it 5.3 as well. CISA rates the advisory as "remotely exploitable/low skill level to exploit" and lists sectors from critical manufacturing and energy to water and nuclear, deployed worldwide. Neither CISA nor NVD gives more technical detail about the session weakness; both treat the protocol, all versions, as the affected product.
The device angle comes from CISA's mitigation text, which applies to both findings in the advisory:
- Modicon Momentum M1E 171CBU98090 and 171CBU98091, all versions, "do not have built-in compensating controls to limit the exploitability of the identified vulnerabilities." Owners must protect them with a firewall blocking all remote access to port 502.
- On other Modicon PLCs, Schneider "introduced compensating controls" that the owner must switch on: the Application Password feature, an input (M340, Premium, Quantum) or a front-panel key switch (Quantum) that rejects remote connections or run/stop commands, and the Access Control List of pre-authorised IP addresses.
Schneider's own notice for this disclosure, SEVD-2017-065-01 (V3.0, 13 August 2019), covers only the companion replay finding, CVE-2017-6034, so the device list above is CISA's. A brute-force weakness matters less once a controller enforces an Application Password and an IP allow-list, which is why the configuration measures come first.
Both CVEs describe the protocol's design, not one coding bug. Our Modbus protocol security guide explains why classic Modbus has no session or authentication layer and what Modbus/TCP Security changes. For the general fix pattern, see the authentication bypass fix guide.
CVE-2017-6032 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.0165, the 77th percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).
Evidence
- Session-related weakness susceptible to brute force; NVD Primary CVSS v3.0 5.3, vector AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N; v2 5.0; Primary CWE-358, CISA CWE-657. — NVD
- ICSA-17-101-01 published 11 April 2017; CVSS 5.3; remotely exploitable/low skill level; M1E 171CBU98090/98091 lack built-in compensating controls; mitigations: port 502 firewall, Application Password, input or key switch, Access Control List. — CISA ICSA-17-101-01
- SEVD-2017-065-01 V3.0 lists CVE-2017-6034 only. — Schneider Electric SEVD-2017-065-01 V3.0
- Not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). — CISA KEV
- EPSS 0.0165 (77th percentile), dataset 2026-11-16, read 2026-11-17. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which controllers does CISA name for CVE-2017-6032?
CISA names Modicon Momentum M1E 171CBU98090 and 171CBU98091, all versions, as having no built-in compensating controls, and gives configuration measures for M340, Premium and Quantum (per CISA ICSA-17-101-01).
How do you mitigate CVE-2017-6032?
Firewall port 502 on Momentum M1E. On other Modicon PLCs, enable the Application Password, an input or key switch that rejects remote run/stop, and the Access Control List of allowed IP addresses (per CISA ICSA-17-101-01).
Does Schneider's notice SEVD-2017-065-01 cover CVE-2017-6032?
No. Version 3.0 of that notice, dated 13 August 2019, lists only CVE-2017-6034, the companion replay finding from the same CISA advisory (per Schneider SEVD-2017-065-01).
Is CVE-2017-6032 in the CISA KEV catalog?
No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.0165, the 77th percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).