Security Advisory

CVE-2013-2824: Vijeo Citect and CitectSCADA Crash Flaw

Last updated:
  • CVE-2013-2824

CVE-2013-2824 is an unhandled exception flaw (CWE-248) in Schneider Electric's Vijeo Citect, CitectSCADA, PowerSCADA Expert and PowerLogic SCADA 7.20 to 7.40: a remote attacker can send a crafted packet that crashes the SCADA software. NVD scores it 7.8 under CVSS v2, the only version it uses for this 2014 record. Schneider fixed it with a hotfix for each affected version.

Vulnerability summary

CVSS base score

7.8

High severity

EPSS score (FIRST)

1.8%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2013-2824 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric StruxureWare SCADA Expert Vijeo Citect and Vijeo Citectcpe:2.3:a:schneider-electric:struxureware_scada_expert_vijeo_citect:*:*:*:*:*:*:*:*7.20 through 7.30 SP1, and 7.40; hotfixes HF720SP460769.1 (7.20 SP4), HF730SP160775.1 (7.30 SP1), HF740RTM60777.1 (7.40)
Schneider Electric CitectSCADAcpe:2.3:a:schneider-electric:citectscada:*:*:*:*:*:*:*:*7.20 through 7.30 SP1 (NVD CPE: 7.20 to 7.20 SP4, 7.30, 7.30 SP1); CISA also lists hotfix HF740RTM60777.1 for CitectSCADA 7.40
Schneider Electric StruxureWare PowerSCADA Expertcpe:2.3:a:schneider-electric:struxureware_powerscada_expert:*:*:*:*:*:*:*:*7.30 through 7.30 SR1; hotfix HF730SP1608004 for 7.30 SR1
Schneider Electric PowerLogic SCADAcpe:2.3:a:schneider-electric:powerlogic_scada:*:*:*:*:*:*:*:*7.20 through 7.20 SR1; hotfix HF720SP460803 for 7.20 SR1

What does this mean for affected devices?

The CVE record from ICS-CERT says that "Schneider Electric StruxureWare SCADA Expert Vijeo Citect 7.40, Vijeo Citect 7.20 through 7.30SP1, CitectSCADA 7.20 through 7.30SP1, StruxureWare PowerSCADA Expert 7.30 through 7.30SR1, and PowerLogic SCADA 7.20 through 7.20SR1 do not properly handle exceptions, which allows remote attackers to cause a denial of service via a crafted packet" (CVE.org record).

How severe is it?

NVD's Primary score is CVSS v2 7.8, AV:N/AC:L/Au:N/C:N/I:N/A:C: network reachable, no authentication, complete loss of availability and no confidentiality or integrity impact (NVD). NVD has no CVSS v3 score for this record and labels the weakness NVD-CWE-Other; CISA uses CWE-248, uncaught exception. CISA's ICSA-13-350-01A, first released on 16 December 2013 with Update A on 25 February 2014, says the flaw could be exploited remotely by an attacker with low skill and that no public exploits were known. Carsten Eiram of Risk Based Security reported it.

What is the fix?

Schneider issued a hotfix per version: HF740RTM60777.1 for SCADA Expert Vijeo Citect 7.40 and CitectSCADA 7.40, HF730SP160775.1 for Vijeo Citect and CitectSCADA 7.30 SP1, HF720SP460769.1 for Vijeo Citect and CitectSCADA 7.20 SP4, HF730SP1608004 for PowerSCADA Expert 7.30 SR1 and HF720SP460803 for PowerLogic SCADA 7.20 SR1 (CISA CSAF). The first release, on 16 December 2013, combined the security fix with a quality fix; some customers saw crashes, Schneider traced them to the quality part and reissued patches that contain only the security update. Install the security-only patch for the exact version you run.

The Schneider EcoStruxure HMI and SCADA software guide lists this flaw among older Citect issues and traces the product line to AVEVA Plant SCADA, whose improper authorization flaw is CVE-2023-1256. The UnitelWay driver overflow CVE-2011-3330 also covered Vijeo Citect, and CVE-2023-22610 is a comparable network-triggered denial of service in Geo SCADA Expert.

Is CVE-2013-2824 exploited?

It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.01786, the 78.8th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS). The KEV and EPSS prioritization guide explains how to rank an old availability flaw against newer ones.

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): published 2014-02-26, status Modified; NVD Primary CVSS v2 7.8 AV:N/AC:L/Au:N/C:N/I:N/A:C; no CVSS v3; NVD-CWE-Other; CPE citectscada 7.20 to 7.30 sp1, powerlogic_scada 7.20 and 7.20 sr1, struxureware_powerscada_expert 7.30 and 7.30 sr1, struxureware_scada_expert_vijeo_citect 7.20 to 7.40. — NVD
  • CISA ICSA-13-350-01A page (read 2026-11-28 via a page fetch): original 2013-12-16, Update A 2014-02-25, last revised 2018-09-06; CVSS v2 7.8; CWE-248; Carsten Eiram of Risk Based Security; exploitable remotely, low skill, no known public exploits; hotfix list per version. — CISA
  • CISA ICSA-13-350-01A CSAF (read 2026-11-28): affected product list; hotfixes HF740RTM60777.1, HF730SP160775.1, HF720SP460769.1, HF730SP1608004, HF720SP460803; security & quality fix of 16 December 2013 caused crashes in the quality part, reissued as security-only patch. — CISA ICSA-13-350-01A
  • CVE.org record (read 2026-11-28): assigner ICS-CERT, description as quoted. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.01786, percentile 0.78833, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-13-350-01A: Schneider Electric CitectSCADA Products Exception Handler Vulnerability (Update A)
  3. CISA ICSA-13-350-01A (CSAF)
  4. CVE.org record (JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which hotfix do I need for CVE-2013-2824?

It depends on the version: HF740RTM60777.1 for Vijeo Citect or CitectSCADA 7.40, HF730SP160775.1 for 7.30 SP1, HF720SP460769.1 for 7.20 SP4, HF730SP1608004 for PowerSCADA Expert 7.30 SR1 and HF720SP460803 for PowerLogic SCADA 7.20 SR1, per CISA ICSA-13-350-01A.

Why did Schneider reissue the patches?

The first patch of 16 December 2013 combined the security fix with a quality fix. Some customers saw crashes after applying it; Schneider found the problem in the quality part and issued new patches containing only the security update.

Can CVE-2013-2824 expose data or run code?

No impact of that kind is listed. NVD's CVSS v2 vector rates confidentiality and integrity impact as none and availability impact as complete: a crafted packet crashes the software.

Is CVE-2013-2824 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.01786, the 78.8th percentile, in the 2026-11-27 dataset.