Security Advisory

CVE-2023-22610: Geo SCADA Expert Database Port DoS

Last updated:
  • CVE-2023-22610

CVE-2023-22610 is an incorrect authorization flaw (CWE-863) in Schneider Electric EcoStruxure Geo SCADA Expert, formerly ClearSCADA. Specific messages sent to the server's database TCP port, 5481 by default, could cause denial of service. NVD scores it 7.5 and Schneider 9.1. The October 2022 updates of Geo SCADA Expert 2019, 2020 and 2021 fix it.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

0.8%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-22610 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric EcoStruxure Geo SCADA Expert 2019cpe:2.3:a:schneider-electric:ecostruxure_geo_scada_expert_2019:*:*:*:*:*:*:*:*81.8267.1 and prior (NVD lists builds 81.7268.1 to 81.8267.1); fixed in 81.8333.1 (October 2022 update)
Schneider Electric EcoStruxure Geo SCADA Expert 2020cpe:2.3:a:schneider-electric:ecostruxure_geo_scada_expert_2020:*:*:*:*:*:*:*:*83.8267.1 and prior; fixed in 83.8332.1 (October 2022 update)
Schneider Electric EcoStruxure Geo SCADA Expert 2021cpe:2.3:a:schneider-electric:ecostruxure_geo_scada_expert_2021:*:*:*:*:*:*:*:*84.8269.1 and prior; fixed in 84.8335.2 (October 2022 update)
Schneider Electric ClearSCADA (former product name)—All versions; Schneider advises upgrading to the latest Geo SCADA Expert release

What does this mean for affected devices?

Schneider Electric's notice SEVD-2023-010-02, released on 10 January 2023 and revised to version 1.1 on 14 March 2023, describes "a CWE-863: Incorrect Authorization vulnerability" "that could cause Denial of Service against the Geo SCADA server when specific messages are sent to the server over the database server TCP port". Schneider describes Geo SCADA Expert as software for telemetry and remote SCADA solutions. The March revision replaced a deprecated CWE; NVD keeps its own NVD-CWE-Other label.

How severe is CVE-2023-22610?

NVD's Primary score is CVSS v3.1 7.5, AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H: network, no privileges, availability impact only (NVD). Schneider, the CNA, scores it CVSS v3.1 9.1, AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H, adding high integrity impact; the CVE.org record carries that 9.1 score. The same notice covers CVE-2023-22611, an information disclosure over the same port scored 7.5 by both. The UK National Cyber Security Centre reported both flaws.

Which versions are affected and what is the fix?

Affected are Geo SCADA Expert 2019 build 81.8267.1 and prior, 2020 build 83.8267.1 and prior, 2021 build 84.8269.1 and prior, and ClearSCADA, all versions. The October 2022 updates fix both CVEs: 2019 build 81.8333.1, 2020 build 83.8332.1 and 2021 build 84.8335.2. Installing new server software needs a system restart or a changeover of redundant servers; ClearSCADA owners should move to the latest Geo SCADA release.

Until updated, Schneider asks owners to restrict the server's database port (default 5481) to ViewX clients only, use the Geo SCADA Expert 2021 server-side client certificate checks, disable "Allow guest user to execute SQL", and use the Client Access Control list to block unknown IP addresses and restrict the web services port (default 443).

The Schneider EcoStruxure HMI and SCADA software guide lists the Geo SCADA and ClearSCADA flaws together. The closest relatives are AVEVA Plant SCADA's improper authorization CVE-2023-1256 and the Citect crash CVE-2013-2824. The OT security guide for small manufacturers covers firewalling SCADA servers.

Is CVE-2023-22610 exploited?

It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0076, the 51.6th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): published 2023-01-31, status Modified; NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; Schneider Secondary CVSS v3.1 9.1 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H; CWE-863 (Schneider), NVD-CWE-Other (NVD); CPE ecostruxure_geo_scada_expert_2019 builds 81.7268.1 to 81.8267.1, 2020 builds 83.7551.1 to 83.8267.1, 2021 builds 84.8027.1 to 84.8269.1. — NVD
  • Schneider SEVD-2023-010-02 V1.1 (10 January 2023, revised 14 March 2023, read 2026-11-28, PDF and Schneider CSAF): affected Geo SCADA Expert 2019 <=81.8267.1, 2020 <=83.8267.1, 2021 <=84.8269.1, ClearSCADA all versions; fixed 81.8333.1, 83.8332.1, 84.8335.2 (October 2022 updates); restart or redundant changeover; mitigations port 5481 to ViewX clients, client certificate checks, disable Allow guest user to execute SQL, Client Access Control list, web port 443; sibling CVE-2023-22611 CWE-200 7.5; credited to the UK NCSC; V1.1 adjusted the deprecated CWE. — Schneider Electric
  • CVE.org record (read 2026-11-28): assigner Schneider Electric, CWE-863, CVSS v3.1 9.1, affected EcoStruxure Geo SCADA Expert 2019-2021 (formerly ClearSCADA) versions before October 2022. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.0076, percentile 0.51601, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2023-010-02 V1.1: EcoStruxure Geo SCADA Expert
  3. CVE.org record (JSON)
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Which Geo SCADA builds fix CVE-2023-22610?

The October 2022 updates: Geo SCADA Expert 2019 build 81.8333.1, 2020 build 83.8332.1 and 2021 build 84.8335.2, per Schneider's SEVD-2023-010-02. They also fix CVE-2023-22611.

Which port is involved?

The Geo SCADA server's database port, default TCP 5481. Schneider asks owners to allow it only from ViewX clients and to use the Client Access Control list, which can also restrict the web services port (default 443).

Is ClearSCADA affected?

Yes. Schneider lists ClearSCADA, the former product name, as affected in all versions and tells ClearSCADA owners to upgrade to the latest Geo SCADA Expert release.

Is CVE-2023-22610 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0076, the 51.6th percentile, in the 2026-11-27 dataset.