Security Advisory

CVE-2013-6143: Telvent SAGE 3030 RTU DNP3 DoS

Last updated:
  • CVE-2013-6143

CVE-2013-6143 is a denial-of-service flaw in the DNP3 service of Schneider Electric Telvent SAGE 3030 remote terminal units used in energy utilities. Malformed DNP3 traffic makes the RTU drop its master-slave communication for a while and spikes its CPU. NVD scores it CVSS v2 5.0 and CISA 4.3. Schneider Electric released a patch through customer service.

Vulnerability summary

CVSS base score

5

Medium severity

EPSS score (FIRST)

1.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2013-6143 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric Telvent SAGE 3030 RTUcpe:2.3:o:schneider-electric:telvent_sage_3030_firmware:c3413-500-001f0_pb:*:*:*:*:*:*:*Products released before 2013-12-01, including firmware C3413-500-001D3_P4 and C3413-500-001F0_PB (CISA ICSA-14-006-01); patch for C3414 LX-800-based RTUs on VxWorks 6.9.3 via Schneider Electric customer service

What does this mean for affected devices?

NVD says the Telvent SAGE 3030 RTU with firmware C3413-500-001D3_P4 and C3413-500-001F0_PB "allows remote attackers to cause a denial of service (temporary outage and CPU consumption) via malformed DNP3 traffic." NVD maps it to CWE-20 and CWE-399; CISA to CWE-20, improper input validation. The record was assigned by ICS-CERT and published on 2014-01-31 (NVD, CVE record).

How severe is CVE-2013-6143?

NVD's Primary score is CVSS v2 5.0, AV:N/AC:L/Au:N/C:N/I:N/A:P. CISA scores it 4.3, AV:N/AC:M/Au:N/C:N/I:N/A:P, in its ICSA-14-006-01, released on 2014-01-06; the CVE record carries no CNA score. The impact is availability only: CISA says an attacker could affect the availability of DNP3 master-slave communication, which for an RTU means lost telemetry and control from the SCADA master. CISA rated it remotely exploitable with low skill, with no known public exploit.

Which SAGE RTUs are affected and what fixes it?

CISA lists Schneider Electric products released before 2013-12-01, naming SAGE 3030 firmware C3413-500-001D3_P4 (2010) and C3413-500-001F0_PB (then the latest). The researchers were Adam Crain of Automatak and Chris Sistrunk, who found it with DNP3 fuzzing. The RTUs serve the energy sector and are deployed mainly in North America. The advisory CSAF records that Schneider Electric created a patch for C3414 LX-800-based RTUs running VxWorks 6.9.3, obtained through Schneider Electric customer service, and that RTU software security bulletin RTUSW 13001 (2013-12-30, customer login needed) carries the release notes. The researchers also suggest blocking DNP3 from business networks with an IPS or firewall that has DNP3-specific rules. The DNP3 protocol guide covers those controls, and the input handling fix guide covers the class. Other DNP3 parsing flaws on this site: CVE-2013-2811 and CVE-2013-2783.

Is CVE-2013-6143 exploited?

CVE-2013-6143 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01358, the 71.82nd percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2014-01-31; NVD Primary CVSS v2 5.0 AV:N/AC:L/Au:N/C:N/I:N/A:P; CWE-20 and CWE-399 (NVD); CPEs telvent_sage_3030_firmware c3413-500-001d3_p4 and c3413-500-001f0_pb. — NVD
  • CISA ICSA-14-006-01 CSAF (read 2026-11-27): SAGE 3030 products before December 1, 2013, C3413-500-001D3_P4 and C3413-500-001F0_PB; CWE-20; CVSS v2 4.3 AV:N/AC:M/Au:N/C:N/I:N/A:P; patch for C3414 LX-800-based RTUs with VxWorks 6.9.3 via customer service; bulletin RTUSW 13001 published December 30, 2013, customer login required; block DNP3 with IPS or firewall with DNP3-specific rules. — CISA ICSA-14-006-01
  • CISA advisory page (read 2026-11-27 via a page fetch): released January 06, 2014; Adam Crain (Automatak), Chris Sistrunk; affects availability of DNP3 master-slave communication; energy sector, deployed primarily in US and North America; remotely exploitable, no known public exploits, low skill. — CISA
  • CVE record (read 2026-11-27): CNA ICS-CERT; no CNA CVSS in the record. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.01358, percentile 0.71816, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-14-006-01: Schneider Electric Telvent SAGE RTU DNP3 Improper Input Validation Vulnerability (CSAF)
  3. CISA ICSA-14-006-01 advisory page
  4. CVE.org record CVE-2013-6143 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which SAGE RTU firmware is affected by CVE-2013-6143?

CISA lists SAGE products released before 2013-12-01, naming SAGE 3030 firmware C3413-500-001D3_P4 and C3413-500-001F0_PB.

How do I get the fix for CVE-2013-6143?

Schneider Electric created a patch for C3414 LX-800-based RTUs running VxWorks 6.9.3, available from Schneider Electric customer service. The release notes are in RTU software security bulletin RTUSW 13001, which needs a customer login.

What does CVE-2013-6143 do to the RTU?

Malformed DNP3 traffic causes a temporary outage and high CPU load, so the RTU loses DNP3 communication with its master. It does not affect confidentiality or integrity, per NVD and CISA.

Is CVE-2013-6143 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01358 (71.82nd percentile) in the 2026-11-26 dataset.