CVE-2013-0659 is an open debugging interface in the Siemens CP 1604 and CP 1616 PROFINET IO interface cards: it is enabled by default on UDP port 17185 and lets a remote attacker run code on the card. NVD scores it 10.0 under CVSS v2. Siemens fixed it in firmware V2.5.2, which closes the debug port.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
5.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2013-0659 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens CP 1616 (6GK1 161-6AA00, 6GK1 161-6AA01, 6GK1 161-6AA02) and CP 1616 onboard card of SIMATIC IPCs (6GK1 160-4AU01) | cpe:2.3:a:siemens:cp_1616_firmware:*:*:*:*:*:*:*:* | Firmware before V2.5.2 (NVD: up to and including 2.5.1); fixed in V2.5.2 (Siemens SSA-628113) |
| Siemens CP 1604 (6GK1 160-4AA00, 6GK1 160-4AA01) and CP 1604 Microbox package (6GK1 160-4AU00) | cpe:2.3:a:siemens:cp_1604_firmware:*:*:*:*:*:*:*:* | Firmware before V2.5.2 (NVD: up to and including 2.5.1); fixed in V2.5.2 (Siemens SSA-628113) |
What does this mean for affected devices?
NVD's description: "The debugging feature on the Siemens CP 1604 and CP 1616 interface cards with firmware before 2.5.2 allows remote attackers to execute arbitrary code via a crafted packet to UDP port 17185." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C); NVD records the weakness as NVD-CWE-noinfo, and its CPE configuration marks CP 1604 and CP 1616 firmware up to and including 2.5.1 as vulnerable (NVD). The CVE record, assigned by ICS-CERT and published on 2013-03-29, carries no CNA score.
What does Siemens say about the debug port?
Siemens ProductCERT's SSA-628113, "Open Debugging Port in CP 1616 and CP 1604", was published on 2013-02-13 (V1.1, 2013-02-18). It explains that the cards connect PCs and PCI-104 systems to PROFINET IO and that "a debugging interface has been enabled in these products by default", allowing denial of service, loss of confidentiality and remote code execution through crafted packets to port 17185/UDP. Siemens gives a CVSS v2 base score of 10.0 and an overall score of 8.3 after temporal factors, and lists CP 1616 (6GK1 161-6AA00, -6AA01, -6AA02), CP 1604 (6GK1 160-4AA00, -4AA01), the CP 1604 Microbox package (6GK1 160-4AU00) and the CP 1616 onboard card of SIMATIC IPCs (6GK1 160-4AU01). Siemens credits Daimler TSS for the report.
CISA republished it as ICSA-13-084-01, "Siemens CP 1604 and CP 1616 Improper Access Control", on 2013-03-25 for critical manufacturing and energy (oil and gas), per the ICS Advisory Project index. CISA's CSAF record lists the products as affected below 2.5.2 and labels the weakness CWE-284.
How do you fix CVE-2013-0659?
Install firmware V2.5.2, which Siemens says "closes the debugging port and protects against all mentioned attacks", and check the version on every card, including those built into SIMATIC IPCs and Microbox systems. Until then, the attacker needs network access to UDP 17185, so keep the PROFINET network inside a protected cell as Siemens' operational guidelines describe. UDP 17185 is also the port of the VxWorks WDB debug agent behind CVE-2010-2965; a port scan for it is a quick check for debug services left open on field devices. Our PROFINET protocol security guide covers cell segmentation, and other PROFINET device flaws include CVE-2019-13946 and CVE-2020-28400. For device makers, our JTAG and SWD debug port guide covers how to close debug access before shipping.
CVE-2013-0659 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0592, the 94th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD: debugging feature on CP 1604 and CP 1616 with firmware before 2.5.2 allows remote code execution via crafted packet to UDP 17185; Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; NVD-CWE-noinfo; CPE firmware up to and including 2.5.1; published 2013-04-01. — NVD
- CVE record: assigner icscert, published 2013-03-29, no CNA metrics. — CVE Services (CVE.org record)
- Siemens SSA-628113: published 2013-02-13, V1.1 2013-02-18; debugging interface enabled by default, port 17185/UDP; CVSS base 10.0, overall 8.3; affected order numbers; firmware update V2.5.2 closes the debugging port; thanks Daimler TSS GmbH. — Siemens ProductCERT
- CISA ICSA-13-084-01 CSAF: CP 1604/CP 1616 <2.5.2; CWE-284; CVSS v2 10.0; Siemens firmware update. — CISA CSAF
- ICS Advisory Project: ICSA-13-084-01 released 3/25/2013, last updated 5/8/2013; sectors critical manufacturing; energy, oil and gas. — ICS Advisory Project
- CVE-2013-0659 is not in the CISA KEV catalog, version 2026.11.25 (1,805 entries), checked 2026-11-27. — CISA KEV
- EPSS 0.0592, percentile 0.94016, dataset 2026-11-26. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Siemens cards and firmware does CVE-2013-0659 affect?
CP 1616 (6GK1 161-6AA00/-6AA01/-6AA02), CP 1604 (6GK1 160-4AA00/-4AA01), the CP 1604 Microbox package and the CP 1616 onboard card of SIMATIC IPCs, all with firmware before V2.5.2 (per Siemens SSA-628113 and NVD).
Why is the score 10.0 when Siemens shows 8.3?
Both use CVSS v2 with the same 10.0 base score. Siemens also publishes an overall score of 8.3 that applies temporal factors (functional exploit, official fix, confirmed report); NVD scores only the base metrics (per NVD and Siemens SSA-628113).
What should operators do about CVE-2013-0659?
Update every CP 1604 and CP 1616 card to firmware V2.5.2, which closes the debug port, and keep UDP port 17185 unreachable from outside the protected PROFINET cell (per Siemens SSA-628113 and CISA ICSA-13-084-01).
Is CVE-2013-0659 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.0592, the 94th percentile, in the 2026-11-26 dataset, so it ranks above most CVEs for predicted exploitation even without a KEV listing (per CISA KEV and FIRST EPSS).