Security Advisory

CVE-2013-0700: SIMATIC S7-1200 Port 102 Defect-Mode DoS

Last updated:
  • CVE-2013-0700

CVE-2013-0700 is an improper input validation flaw (CWE-20) in Siemens SIMATIC S7-1200 PLCs: specially crafted packets sent to TCP port 102, the ISO-TSAP port used for S7 communication, push the CPU into defect mode and stop the controlled process. NVD scores it 7.8 under CVSS v2. Siemens fixed it in S7-1200 firmware V4.0.0.

Vulnerability summary

CVSS base score

7.8

High severity

EPSS score (FIRST)

2.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2013-0700 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Siemens SIMATIC S7-1200 CPU family (incl. SIPLUS variants): CPU 1211C, 1212C, 1212FC, 1214C, 1214FC, 1215C, 1215FC, 1217Ccpe:2.3:o:siemens:simatic_s7-1200_firmware:*:*:*:*:*:*:*:*All versions before V4.0.0 (Siemens SSA-724606; NVD CPE: before 4.0); update to V4.0.0

What does this mean for affected devices?

NVD's description: "Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port)." NVD's Primary score is CVSS v2 7.8 (AV:N/AC:L/Au:N/C:N/I:N/A:C), with the weakness recorded as NVD-CWE-noinfo. NVD's CPE configuration marks S7-1200 firmware before 4.0 for the CPU 1211C, 1212C, 1212FC, 1214C, 1214 FC, 1215C, 1215 FC and 1217C (NVD). The CVE record, assigned by ICS-CERT and published on 2013-04-22, carries no CNA score.

What does Siemens say?

Siemens ProductCERT's SSA-724606, "Denial-of-Service Vulnerabilities in SIMATIC S7-1200 CPU Family", was first published on 2012-12-20; the current version 1.3 is dated 2020-02-10. Siemens says that "specially crafted packets sent on port 102/tcp (ISO-TSAP) cause the device to go into defect mode" and that "further research has identified multiple instances of this vulnerability" (the V1.1 update of 2013-02-13 followed closer analysis by Arne Vidström of the Swedish Defence Research Agency, FOI). Siemens scores it CVSS v3.1 7.5 (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, with temporal metrics E:P/RL:O/RC:C) and CWE-20. The affected product is the SIMATIC S7-1200 CPU family, including SIPLUS variants, all versions before V4.0.0. The sibling CVE-2013-2780 in the same advisory does the same through SNMP on UDP port 161.

CISA published it as ICSA-14-079-01, "Siemens SIMATIC S7-1200 Improper Input Validation Vulnerabilities", on 2014-03-20 for the chemical, critical manufacturing, and food and agriculture sectors, per the ICS Advisory Project index; CISA's CSAF record lists the S7-1200 PLC family below V4.0.0 with CVSS v2 7.8 and CWE-20.

How do you fix CVE-2013-0700?

Update the S7-1200 CPUs to product release V4.0.0, the remediation both Siemens and CISA name; Siemens lists no specific workaround. Until the update, allow port 102 only from the engineering stations and HMIs that need S7 communication; Siemens' general recommendation is to "protect network access to devices with appropriate mechanisms" and to follow its operational guidelines for Industrial Security. Our S7-1200 and S7-1500 vulnerabilities guide tracks later CVEs such as CVE-2020-15782 and CVE-2019-10943, and the S7comm protocol security guide explains what runs over port 102.

CVE-2013-0700 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.02392, the 84th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD: SIMATIC S7-1200 PLCs 2.x and 3.x denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (ISO-TSAP); Primary CVSS v2 7.8 AV:N/AC:L/Au:N/C:N/I:N/A:C; NVD-CWE-noinfo; CPEs S7-1200 firmware before 4.0 for CPU 1211C-1217C; published 2013-04-22. — NVD
  • CVE record: assigner icscert, published 2013-04-22, no CNA metrics. — CVE Services (CVE.org record)
  • Siemens SSA-724606 V1.3 (published 2012-12-20, last update 2020-02-10): port 102/tcp crafted packets cause defect mode, multiple instances; CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C; CWE-20; S7-1200 CPU family incl. SIPLUS all versions < V4.0.0, update to V4.0.0; no specific workarounds; Arne Vidstrom (FOI); CVE-2013-2780 via 161/udp. — Siemens ProductCERT
  • CISA ICSA-14-079-01 CSAF: SIMATIC S7-1200 PLC family <V4.0.0; CVE-2013-0700 CVSS v2 7.8, CWE-20; Siemens product release V4.0.0 resolves. — CISA CSAF
  • ICS Advisory Project: ICSA-14-079-01 released 3/20/2014, last updated 9/6/2018; sectors chemical, critical manufacturing, food and agriculture. — ICS Advisory Project
  • CVE-2013-0700 is not in the CISA KEV catalog, version 2026.11.25 (1,805 entries), checked 2026-11-27. — CISA KEV
  • EPSS 0.02392, percentile 0.84709, dataset 2026-11-26. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens SSA-724606: Denial-of-Service Vulnerabilities in SIMATIC S7-1200 CPU Family
  3. CISA ICSA-14-079-01: Siemens SIMATIC S7-1200 Improper Input Validation Vulnerabilities
  4. CISA CSAF: icsa-14-079-01.json
  5. ICS Advisory Project: CISA ICS advisory index
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which S7-1200 firmware fixes CVE-2013-0700?

Product release V4.0.0. Siemens lists every S7-1200 CPU family version before V4.0.0, including SIPLUS variants, as affected (per Siemens SSA-724606 and CISA ICSA-14-079-01).

What happens to the PLC when CVE-2013-0700 is triggered?

The CPU goes into defect mode and the process it controls loses control; NVD describes the result as a defect-mode transition and control outage (per NVD and Siemens SSA-724606).

Why do NVD and Siemens give different scores?

NVD's Primary score is CVSS v2 7.8. Siemens, the vendor, scores CVSS v3.1 7.5 with the vector AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H. Both describe an unauthenticated network denial of service (per NVD and Siemens SSA-724606).

Is CVE-2013-0700 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.02392, the 84th percentile, in the 2026-11-26 dataset, so it ranks above most CVEs for predicted exploitation even without a KEV listing (per CISA KEV and FIRST EPSS).