Security Advisory

CVE-2019-13946: Siemens PNIO Stack DCE-RPC DoS

Last updated:
  • CVE-2019-13946

CVE-2019-13946 is a memory exhaustion flaw in the Siemens PROFINET-IO (PNIO) stack before V06.00: repeated legitimate diagnostic requests to the DCE-RPC interface on 34964/udp exhaust memory on SCALANCE switches, ET 200 modules, communication processors and boards built on Siemens' development kits. NVD scores it 7.5. Siemens lists 198 entries, 34 with no fix.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2019-13946 · Source: NVD

Affected components

ComponentCPEVersion range
Siemens PROFINET-IO (PNIO) stack—before V06.00 (NVD, Siemens SSA-780073)
Siemens SCALANCE X, XM-400, XR-500 and W-700 switches and access pointscpe:2.3:o:siemens:scalance_x-300_firmware:*:*:*:*:*:*:*:*X-300 before V4.1.4; X-200 before V5.2.5; X-200IRT before V5.4.2; XM-400/XR-500 before V6.2.3; W-700 802.11n before V6.4 (SSA-780073)
Siemens RUGGEDCOM RM1224 and SCALANCE M-800cpe:2.3:o:siemens:ruggedcom_rm1224_firmware:*:*:*:*:*:*:*:*before V6.1.2 (SSA-780073; NVD CPE range differs)
Siemens ET 200MP and ET 200SP interface modules, CP 443-1, CP 1616/CP 1604—IM 155-5/155-6 PN ST before V4.1.0; IM 155-5 PN HF before V4.2.0; CP 443-1 before V3.3; CP 1616/1604 before V2.8.1 (SSA-780073)
Siemens EK-ERTEC 200/200P development kits and PROFINET Driver for Controllercpe:2.3:o:siemens:ek-ertec_200p_firmware:*:*:*:*:*:*:*:*EK-ERTEC 200 before V4.5 Patch 01; EK-ERTEC 200P before V4.6; PROFINET Driver before V2.1 Patch 03; DK Standard Ethernet Controller no fix (SSA-780073)
Siemens CP 343-1 line, ET 200M/pro/S/AL, ET200ecoPN, PN/PN Coupler, RF180C/RF182C, SOFTNET-IE PNIO—no fix; mitigation only (34 entries, SSA-780073)

What does this mean for affected devices?

CVE-2019-13946 is a memory exhaustion flaw in Siemens' PROFINET-IO (PNIO) stack, the code that many Siemens products and development kits share. NVD's description: "Profinet-IO (PNIO) stack versions prior V06.00 do not properly limit internal resource allocation when multiple legitimate diagnostic package requests are sent to the DCE-RPC interface. This could lead to a denial of service condition due to lack of memory for devices that include a vulnerable version of the stack." The attacker needs network access, but no privileges and no user interaction. NVD's analysis gives CVSS v3.1 7.5 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, with CWE-400. The API types that entry as Secondary; NVD's Primary metric is CVSS v2 7.8 (NVD).

The requests are legitimate diagnostic requests, not malformed packets, so input validation alone does not stop them. The DCE-RPC interface is PROFINET CM on 34964/udp, which IANA registers as profinet-cm.

Siemens ProductCERT SSA-780073, first published on 2020-02-11 and at revision 15 since 2024-07-09, lists 198 product entries. CISA's copy is ICSA-20-042-04 (CSAF). Fixed versions include:

  • SCALANCE X-300 switches: V4.1.4. X-200: V5.2.5. X-200IRT: V5.4.2. XM-400 and XR-500: V6.2.3. XB-200, XC-200, XF-200BA, XP-200, XR-300WG: V4.1.
  • RUGGEDCOM RM1224 and SCALANCE M-800 routers: V6.1.2. SCALANCE W-700 IEEE 802.11n: V6.4.
  • ET 200MP IM 155-5 PN ST and ET 200SP IM 155-6 PN ST: V4.1.0; ET 200MP IM 155-5 PN HF: V4.2.0. CP 443-1 family: V3.3. CP 1616 and CP 1604: V2.8.1.
  • Development kits: EK-ERTEC 200 V4.5 Patch 01, EK-ERTEC 200P V4.6; PROFINET Driver for Controller: V2.1 Patch 03.

Siemens lists no fix for 34 entries: the whole CP 343-1 line (incl. ERPC, Lean, Advanced and SIPLUS NET variants), CP 443-1 OPC UA, ET 200M IM 153-4 PN IO, ET 200pro IM 154-3/154-4 PN HF, ET 200SP IM 155-6 PN BA, ET 200S, ET 200AL, the ET200ecoPN modules, PN/PN Coupler, RF180C and RF182C, SOFTNET-IE PNIO, SIMATIC IPC Support Package for VxWorks and the DK Standard Ethernet Controller kit. For all entries Siemens recommends to "Block incoming DCE-RPC packets (port 34964/udp) from untrusted networks" and to disable PROFINET where it is optional and unused.

NVD's CPE ranges differ from the current SSA. NVD shows SCALANCE M-800 affected before 4.3, for example, while Siemens names V6.1.2 as the fix, so take versions from SSA-780073.

The development kits matter to device makers. A product built on an EK-ERTEC or DK kit inherits the stack, which is the point our PROFINET protocol security guide makes about tracking stacks; a firmware SBOM that names the PNIO stack version shows exposure. The Hilscher stack flaw CVE-2021-20986 and the Siemens UDP flood CVE-2019-10936 are related pages.

CVE-2019-13946 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.0146, the 74.0th percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Resource exhaustion. Our practical guide covers how to detect, fix, verify and disclose it: How to fix SQL injection, XSS, resource exhaustion and deserialization flaws in embedded firmware.

Evidence

  • PNIO stack before V06.00 does not limit resource allocation for multiple legitimate diagnostic requests to DCE-RPC; network access, no privileges, no user interaction; NVD CVSS 3.1 7.5 (typed Secondary), Primary CVSS v2 7.8; CWE-400; CPE scalance_m-800 before 4.3. — NVD
  • SSA-780073 first published 2020-02-11, revision 15 of 2024-07-09; 198 entries, 34 with no fix; fixed versions listed; block 34964/udp DCE-RPC from untrusted networks; disable PROFINET where optional. — Siemens ProductCERT SSA-780073
  • Per-product remediation and mitigation records (CSAF). — Siemens ProductCERT SSA-780073 (CSAF)
  • ICSA-20-042-04 (Update H, revision 15) lists 198 entries, 34 without a fix. — CISA ICSA-20-042-04 (CSAF)
  • 34964 is registered as profinet-cm. — IANA port registry
  • Not in the KEV catalog as of 2026-11-17 (catalog version 2026.11.13). — CISA KEV
  • EPSS 0.0146 (74.0th percentile), dataset 2026-11-16, read 2026-11-17. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT SSA-780073: Denial of Service Vulnerability in PROFINET Devices via DCE-RPC Packets
  3. Siemens ProductCERT SSA-780073 (CSAF)
  4. CISA ICSA-20-042-04: Siemens PROFINET-IO Stack (CSAF)
  5. IANA Service Name and Transport Protocol Port Number Registry
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which port does CVE-2019-13946 use?

The PROFINET DCE-RPC interface, 34964/udp, registered by IANA as profinet-cm. Siemens recommends blocking incoming DCE-RPC packets on that port from untrusted networks (per Siemens SSA-780073 and IANA).

Does CVE-2019-13946 need malformed packets?

No. NVD and Siemens describe multiple legitimate diagnostic package requests; the stack fails to limit the memory it allocates for them, so the device runs out of memory (per NVD).

Are PROFINET development kits affected by CVE-2019-13946?

Yes. EK-ERTEC 200 is fixed in V4.5 Patch 01 and EK-ERTEC 200P in V4.6, while the DK Standard Ethernet Controller kit has no fix (per SSA-780073).

Is CVE-2019-13946 in the CISA KEV catalog?

No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.0146, the 74.0th percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).