Security Advisory

CVE-2010-2965: VxWorks WDB debug agent on RTU500 firmware

Last updated:
  • CVE-2010-2965

CVE-2010-2965 is the Wind River VxWorks WDB debug agent left enabled in shipped products, which gives anyone who can reach UDP port 17185 read and write access to memory and function calls. In 2026 Hitachi Energy listed it for end-of-life RTU500 CMU firmware 11.x and prior. NVD's Primary metric is CVSS v2 10.0; Hitachi Energy and CISA-ADP give 9.8.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

57.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2010-2965 · Source: NVD

Affected components

ComponentCPEVersion range
Hitachi Energy RTU500 series CMU firmware (end-of-life)—CMU firmware 11.x and prior (end-of-life, "few of the" legacy versions per Hitachi Energy); upgrade to 12.7.8 or 13.9.1 or latest (CISA ICSA-26-279-06, Hitachi Energy 8DBD000251); no NVD CPE for the RTU500
Wind River VxWorks WDB target agentcpe:2.3:o:windriver:vxworks:*:*:*:*:*:*:*:*VxWorks 6.x, 5.x and earlier with the WDB agent included (NVD CPE: up to excluding 6.9.4.12)
Rockwell Automation 1756-ENBT series Acpe:2.3:o:rockwellautomation:1756-enbt\/a_firmware:3.6.1:*:*:*:*:*:*:*firmware 3.2.6 and 3.6.1 (CERT/CC VU#362332 addendum, NVD CPE)

What does this mean for affected devices?

NVD's description: the WDB target agent debug service in Wind River VxWorks 6.x, 5.x and earlier "allows remote attackers to read or modify arbitrary memory locations, perform function calls, or manage tasks via requests to UDP port 17185." CERT/CC's VU#362332, first published on 2010-08-02, explains that WDB is a development component enabled by default in the VxWorks configuration, that its access "is not secured", and that an attacker can use it to fully compromise the device. NVD's Primary metric is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C). The CISA ADP container adds CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), labelled Secondary by NVD, and Hitachi Energy uses the same 9.8. NVD and CISA-ADP list CWE-863. The record was published on 2010-08-05 (NVD, CVE record).

Why it appears in a 2026 RTU500 advisory

Hitachi Energy's advisory 8DBD000251 of 2026-09-29, republished by CISA as ICSA-26-279-06 (CSAF), answers findings reported by Dragos in end-of-life RTU500 CMU firmware 9.x. Hitachi Energy says the findings do not affect supported CMU firmware, but that end-of-life versions 11.x and prior are likely affected, and that the WDB service is present on "few of the Hitachi Energy RTU500 CMU firmware legacy versions." The same advisory lists CVE-2026-8065, an unauthenticated firmware upload, and other CVEs. The only remedy is to upgrade to CMU firmware 12.7.8, 13.9.1 or later, because end-of-life versions get no security updates. CISA lists the energy sector, deployed worldwide. Outside ABB and Hitachi Energy, the CERT/CC note names many other VxWorks-based products, for example Rockwell Automation 1756-ENBT series A on firmware 3.2.6 and 3.6.1.

What to do on old RTUs

Inventory RTU500 units on CMU firmware 11.x or earlier, including spares, and upgrade or replace them. Until then, block UDP port 17185 to and from the RTU at the firewall; CERT/CC recommends restricting the debug service to trusted sources, and Hitachi Energy's general mitigation factors call for physically protected systems, no direct Internet connection and a firewall with a minimal number of open ports. The ABB AC500, RTU500 and Relion guide covers the RTU500 firmware lines, CVE-2021-35533 is an RTU500 12.x flaw, CVE-2021-35535 is an older VxWorks reached during Relion boot, and CVE-2016-20009 is another VxWorks network stack flaw.

CVE-2010-2965 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.57544, the 99.1st percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2010-08-05; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; CISA-ADP Secondary CVSS v3.1 9.8; CWE-863 (NVD Primary and CISA-ADP); CPE windriver vxworks up to excluding 6.9.4.12, Rockwell 1756-ENBT/A firmware 3.2.6 and 3.6.1. — NVD
  • CISA ICSA-26-279-06 CSAF, republication of Hitachi Energy PSIRT 8DBD000251 (initial release 2026-09-29, CISA republication 2026-10-06), read 2026-11-23: Dragos findings in EOL CMU firmware 9.x; 11.x and prior likely affected; CVE-2010-2965 CWE-863, CVSS v3.1 9.8, WDB on UDP 17185 on few legacy RTU500 CMU firmware versions; vendor fix: upgrade to 12.7.8 or 13.9.1 or latest; general mitigation factors; energy sector, worldwide. — CISA ICSA-26-279-06
  • CERT/CC VU#362332 (original release 2010-08-02, last revised 2020-09-02), read 2026-11-23: WDB enabled by default, access not secured, attacker can fully compromise the device; remove INCLUDE_WDB and INCLUDE_DEBUG; restrict 17185/udp to trusted sources; addendum: Rockwell Automation 1756-ENBT series A firmware 3.2.6 and 3.6.1 vulnerable. — CERT/CC VU#362332
  • CVE record (checked 2026-11-23): state PUBLISHED; MITRE-assigned 2010 record; references include VU#362332 and the Rockwell technote. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.57544, percentile 0.99101, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-26-279-06: Hitachi Energy RTU500
  3. CISA ICSA-26-279-06 CSAF (republication of Hitachi Energy 8DBD000251)
  4. CERT/CC VU#362332: VxWorks debug service enabled by default
  5. CVE.org record CVE-2010-2965
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which RTU500 firmware is affected by CVE-2010-2965?

Hitachi Energy's advisory, republished by CISA as ICSA-26-279-06, lists end-of-life CMU firmware 11.x and prior and says the WDB service is present on a few legacy versions. Supported CMU firmware is not affected.

Is there a patch for the old RTU500 firmware?

No. End-of-life versions get no security updates; the only remedy is to upgrade to CMU firmware 12.7.8, 13.9.1 or later. Until then, block UDP port 17185 and keep the RTU off direct Internet connections.

Why is there no NVD CVSS v3 score?

NVD analysed the record in 2010, so its Primary metric is CVSS v2 10.0. The CVSS v3.1 9.8 shown on NVD comes from the CISA ADP container and is Secondary; Hitachi Energy's advisory uses the same 9.8.

Is CVE-2010-2965 in the CISA KEV catalog?

No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.57544 (99.1st percentile) in the 2026-11-22 dataset.