Two operators at a control-room desk with a row of monitors, a laptop and keyboards

OT/ICS security

Johnson Controls vulnerabilities: Metasys and Facility Explorer building automation, Software House C•CURE and iSTAR, exacqVision and Kantech, fixed versions and hardening

Last updated:

Johnson Controls' Metasys and Facility Explorer building automation systems, Software House C•CURE 9000 and iSTAR access control, exacqVision video and Kantech EntraPass had no CVE in CISA's KEV catalog as of 2026-11-24, but their advisories share five recurring families: unauthenticated or weakly authenticated web and API functions, command injection, hard-coded keys and credentials, credentials leaked into logs, and flaws in bundled third-party components such as SQL Express and Tridium Niagara. The most severe recent one, CVE-2025-26385 in the SQL Express that Metasys installs, scores CVSS v3.1 10.0 from CISA and is fixed by patch GIV-165989 and by closing TCP port 1433.

The rest of this guide places the products in a building network, lists the management paths the advisories name, walks through the CVEs by product with Johnson Controls' fixed versions, and ends with hardening, monitoring and a worked example. Every score names its scorer, because Johnson Controls, CISA and NVD often disagree.

Key takeaways

  • TCP 1433 for SQL Express is the only port number named in the Johnson Controls and CISA advisories used here: both JCI-PSA-2026-02 and CISA's ICSA-26-027-04 ask owners to close it to incoming traffic.
  • CVE-2025-26385 (JCI-PSA-2026-02, ICSA-26-027-04, 27 January 2026): command injection in the SQL Express instance deployed by the Metasys installer, which allows remote SQL execution.
  • Two version lines stand out for ADS/ADX/OAS 10 and 11: 10.1.5 and 11.0.2 fix the 2022 privilege, account takeover and SSRF flaws, but CVE-2021-36204 needs 10.1.6 or 11.0.3.
  • Facility Explorer inherits Tridium Niagara flaws.

Where do Metasys, Facility Explorer and the security products sit in a building network?

CISA lists critical manufacturing, commercial facilities, government services and facilities, transportation systems and energy as deployment sectors for its 2025 and 2026 Metasys and Facility Explorer advisories, with worldwide deployment and headquarters in Ireland. The product names in Johnson Controls' Product Security Advisories (JCI-PSA) and CISA's advisories fall into five groups:

Group Products named in advisories Typical place in the network
Metasys servers and tools Application and Data Server (ADS, ADS-Lite), Extended Application and Data Server (ADX), Open Data Server (ODS), Open Application Server (OAS), Metasys UI (MUI), Site Management Portal (SMP), Metasys Reporting Engine (MRE), System Configuration Tool (SCT), Controller Configuration Tool (CCT) Windows servers and engineering PCs at the supervisory level
Metasys engines NAE55, NIE55/NIE59, NAE85/NIE85, NAE8500, NCE, SNE, SNC, LonWorks Control Server (LCS8520, LCS8500) Building network, between the servers and field controllers
Facility Explorer FX Server, FX80, FX90 (built on Tridium Niagara 4), F4-SNC supervisory controllers Same supervisory and engine levels as Metasys
Access control Software House C•CURE 9000 with C•CURE Web and Portal, American Dynamics victor, iSTAR Pro, Edge, eX, Ultra, Ultra LT, Ultra SE, Ultra G2 and Edge G2 door controllers, iSTAR Configuration Utility (ICU), Kantech EntraPass, KT-1 door controllers Security network: a Windows server plus door controllers at each panel
Video exacqVision Server, Client, Web Service and Enterprise Manager Security network, often with a web front end for remote viewing

Building automation and physical security often share one site network, and the advisories show the same weak points in both: a Windows server with a web interface, an engineering or configuration tool, and embedded controllers that trust it. For the field protocols underneath, see the BACnet security guide and, for FX Server, FX80 and FX90, the Niagara Fox protocol guide. The Purdue model guide explains the zoning behind the table.

How are Metasys and the security systems managed and reached?

The management paths the advisories name are the attack paths:

Path Products What the sources say
Metasys web services and web API ADS, ADX, ODS, OAS, NAE, NIE, LCS, SCT Password hash disclosure and file upload (2014), XXE (2020), file system access through crafted web messages (2021), account takeover and unverified password change (2022)
Metasys UI and Site Management Portal ADS, ADX, OAS, engines Shared RSA key and hard-coded RC2 key for SMP encryption before 9.0, SSRF in MUI PDF export, stored XSS in Metasys 12 to 15
Engine login endpoint NAE55, SNE, SNC, F4-SNC Invalid credentials sent to the login endpoint cause denial of service (CVE-2023-4486)
SQL Express on TCP 1433 ADS, ADX, LCS8500, NAE8500, SCT, CCT Remote SQL execution through command injection (CVE-2025-26385)
iSTAR Configuration Utility (ICU) iSTAR Pro, Edge, eX, Ultra, Ultra LT Controllers before firmware 6.6.B accept ICU commands without authentication
Controller web server iSTAR Ultra family Command injection to root, both unauthenticated (2022) and authenticated (2025)
Video web service exacqVision Web Service, Enterprise Manager Unsigned executables, exposed server credentials, missing HTTPS enforcement
Controller to server link Kantech KT-1 and EntraPass Replayed TCP command messages (CVE-2021-27662)

TCP 1433 for SQL Express is the only port number named in the Johnson Controls and CISA advisories used here: both JCI-PSA-2026-02 and CISA's ICSA-26-027-04 ask owners to close it to incoming traffic. The advisories give no port for the Metasys web services, ICU or exacqVision, so take those from the hardening guides on the Johnson Controls Trust Center or from a capture. The BOD 23-02 guide on internet-exposed management interfaces shows how to test exposure from outside the site.

What are the newest Metasys vulnerabilities?

Two 2026 advisories cover current Metasys releases:

  • CVE-2025-26385 (JCI-PSA-2026-02, ICSA-26-027-04, 27 January 2026): command injection in the SQL Express instance deployed by the Metasys installer, which allows remote SQL execution. Affected are ADS installed with SQL Express from Metasys 14.1 and earlier, ADX from Metasys 14.1, LCS8500 and NAE8500 from releases 12.0 to 14.1, SCT 17.1 and earlier, and CCT 17.0 and earlier. CISA scores it CVSS v3.1 10.0 and Johnson Controls CVSS v4 9.5. NVD lists it as Deferred with no Primary score as of 2026-11-24. The fix is the Metasys patch for GIV-165989 from the Johnson Controls License Portal, plus closing incoming TCP 1433. The Johnson Controls PDF also asks owners to disable the SQL Express SA account, a step CISA's text does not repeat, while the patch appears in CISA's text and the CVE record but not in the PDF.
  • CVE-2026-34491 (JCI-PSA-2026-11, ICSA-26-225-14, 13 August 2026): stored cross-site scripting in the Metasys UI, where a crafted URL runs script in other users' sessions, including administrators. Johnson Controls lists Metasys 12 and 13 (all versions), 14 before 14.1.5 and 15 before 15.0.1; CISA adds that Metasys 11 and earlier are not affected and Metasys 16.0 was fixed before release. CISA scores it CVSS v3.1 8.0 and Johnson Controls CVSS v4 6.1; NVD shows Awaiting Analysis with no Primary score as of 2026-11-24. Metasys 12 and 13 are past end of support, so the fix there is an upgrade. The CVE record names only Metasys 14 and 15, so a scanner that reads it will miss 12 and 13.

Which Metasys server flaws came out between 2014 and 2023?

The older Metasys advisories cluster around the web services, the ADS/ADX/OAS servers and key handling:

CVE Advisory Weakness Score (scorer) Fix
CVE-2014-5427 ICSA-14-350-02 Password hashes readable through a POST request, Metasys 4.1 to 6.5 5.0 (NVD v2) Patches for 4.1, 5.x and 6.x from a branch office
CVE-2014-5428 ICSA-14-350-02 Unrestricted file upload in web services, Metasys 4.1 to 6.5 10.0 (NVD v2) Same patches
CVE-2018-10624 ICSA-18-212-02 Error handling in HTTP communication discloses technical information 4.3 (CISA); NVD v3.0 6.5 Metasys 8.1; BCPro 3.0.2
CVE-2019-7593 JCI-PSA-2019-06, ICSA-19-227-01 Shared RSA key pair for SMP encryption, before 9.0 6.8 (Johnson Controls, CISA); NVD 9.1 Release 9.0 with trusted certificates
CVE-2019-7594 JCI-PSA-2019-06, ICSA-19-227-01 Hard-coded RC2 key for SMP encryption, before 9.0 6.8 (Johnson Controls, CISA); NVD 9.1 Release 9.0 with trusted certificates
CVE-2020-9044 JCI-PSA-2020-3, ICSA-20-070-05 XXE in Metasys web services: DoS or reading ASCII server files 7.5 (Johnson Controls, CISA); NVD 9.1 Patch from a branch office
CVE-2020-9050 JCI-PSA-2021-02, ICSA-21-049-01 Path traversal in MRE Web Services 2.0 and 2.1, unauthenticated file download 7.5 (CISA, NVD) MRE 2.2
CVE-2021-27657 JCI-PSA-2021-05, ICSA-21-159-01 Authenticated user reaches the server file system through crafted web messages, 11.0 and earlier 8.8 (CISA, NVD) Patch for 9.0 (engines), 10.0, 10.1 and 11.0
CVE-2021-36202 JCI-PSA-2022-02, ICSA-22-095-02 SSRF in the MUI PDF export 8.4 (Johnson Controls, CISA); NVD 8.8 10.1.5 or 11.0.2
CVE-2021-36207 JCI-PSA-2022-08, ICSA-22-118-01 Authenticated user elevates to administrator on ADS/ADX/OAS 8.8 (CISA, NVD) 10.1.5 or 11.0.2
CVE-2022-21934 JCI-PSA-2022-09, ICSA-22-125-01 Authenticated user locks out or takes over other accounts 8.0 (Johnson Controls, CISA); NVD 8.8 10.1.5 or 11.0.2
CVE-2022-21935 JCI-PSA-2022-10, ICSA-22-165-01 Unverified password change on ADS/ADX/OAS 7.5 (CISA, NVD) 10.1.5 or 11.0.2
CVE-2021-36204 JCI-PSA-2022-05, ICSA-23-012-06 API calls expose credentials in plain text 7.8 (Johnson Controls, CISA); NVD 7.5 10.1.6 or 11.0.3
CVE-2022-21936 JCI-PSA-2022-11, ICSA-22-277-01 ADX 12.0 running MVE: Active Directory user runs validated actions without a valid password 8.1 (Johnson Controls, CISA); NVD 6.5 12.0.1
CVE-2022-21939 JCI-PSA-2022-07, ICSA-23-040-03 SCT session cookie without the HttpOnly flag 7.5 (Johnson Controls, CISA); NVD 6.1 SCT 14.2.3 or 15.0.3
CVE-2023-4486 JCI-PSA-2023-08 v2, ICSA-23-341-03 Invalid login credentials cause DoS on NAE55, SNE, SNC and F4-SNC 7.5 (Johnson Controls, CISA, NVD) 11.0.6 or 12.0.4

Two version lines stand out for ADS/ADX/OAS 10 and 11: 10.1.5 and 11.0.2 fix the 2022 privilege, account takeover and SSRF flaws, but CVE-2021-36204 needs 10.1.6 or 11.0.3. Metasys installations before 9.0 still carry the SMP key flaws, for which Johnson Controls' only fix is Release 9.0 plus trusted certificates. The hard-coded credentials fix guide explains why a key shipped in every copy of a product has to be replaced by a per-site certificate rather than hidden.

What about Facility Explorer and Niagara?

Facility Explorer inherits Tridium Niagara flaws. Johnson Controls says FX 14.10.10 aligns with Niagara 4.10u10 and FX 14.14.1 with Niagara 4.14u1:

  • CVE-2025-43867 (JCI-PSA-2025-09 v2, ICSA-25-219-02): FX Server, FX80 and FX90 depend on a vulnerable Niagara component, and exploitation could compromise the device's configuration files. Johnson Controls says it "could trigger CVEs CVE-2025-3936 through CVE-2025-3945", a range that runs from CVE-2025-3936 (permissions on Windows) to CVE-2025-3945 (argument injection on QNX) and includes CVE-2025-3944 (file permissions on QNX) and CVE-2025-3937 (weak password hashing); NVD scores all four 9.8. CISA scores CVE-2025-43867 CVSS v3.1 7.7 and Johnson Controls CVSS v4 8.5; NVD lists it as Received with no Primary score as of 2026-11-24. The fix is the 14.10.11 patch for 14.10.10 and earlier or the 14.14.2 patch for 14.14.1 and earlier, from the Facility Explorer software portal.
  • CVE-2017-16744 (ICSA-19-022-01): path traversal in Facility Explorer 6.x before 6.6 and 14.x before 14.4u1, usable with valid platform administrator credentials. CISA scores it 6.6 and NVD 7.2. Johnson Controls fixed it in Facility Explorer 14.6, 14.4u1 and 6.6, and recommends FX14.6.
  • CVE-2021-27661 (JCI-PSA-2021-11, ICSA-21-182-01): an authenticated F4-SNC user can reach the controller's file system through crafted web messages, the Facility Explorer twin of the Metasys CVE-2021-27657. CISA and NVD both score it 8.8, and Johnson Controls ships a patch.

The F4-SNC also shares CVE-2023-4486 with the Metasys engines, fixed in 11.0.6 or 12.0.4. When Tridium publishes a Niagara fix, check whether a matching FX patch exists before assuming the FX80 or FX90 is covered.

Which C•CURE 9000 and iSTAR vulnerabilities matter most?

Software House access control has two kinds of flaws: credentials in Windows server logs, and command injection or missing authentication on iSTAR door controllers.

  • CVE-2020-9045 (JCI-PSA-2020-4, ICSA-20-142-01): the C•CURE 9000 v2.70 and victor 5.2 installers log the installing user's credentials, and the log file persists. Johnson Controls and CISA score it 9.9; NVD says 6.5. The fix is C•CURE 9000 2.80 or victor 5.3, plus deleting the logs from c:\ProgramData\Tyco\InstallerTemp and changing that account's password.
  • CVE-2024-0912 (JCI-PSA-2024-04, ICSA-24-135-03): the IIS server that hosts the C•CURE 9000 web server logs Windows credentials in api.log. CISA scores it CVSS v3.1 7.7, Johnson Controls CVSS v4 8.5 and NVD 4.2. The fix is C•CURE 9000 3.00.2 CU02 or 3.00.3, then changing the affected passwords and deleting the log file.
  • CVE-2022-21941 (JCI-PSA-2022-13, ICSA-22-242-11): unauthenticated command injection with root access on iSTAR Ultra before 6.8.9.CU01. CISA scores it 10.0 and NVD 9.8.
  • CVE-2023-3127 (JCI-PSA-2023-05, ICSA-23-192-02): an unauthenticated user can log in with administrator rights to iSTAR Ultra, Ultra LT, Ultra G2 and Edge G2. CISA scores it 7.5 and NVD 9.8. Firmware 6.9.2 CU01 fixes it.
  • CVE-2024-32752 (JCI-PSA-2024-06 v2, ICSA-24-158-04): iSTAR controllers before firmware 6.6.B do not authenticate ICU communication. CISA scores it CVSS v3.1 9.1 and Johnson Controls CVSS v4 8.8; NVD lists it as Deferred with no Primary score. iSTAR Pro, Edge and eX get no fix: Johnson Controls asks owners to replace them with a current controller such as iSTAR Ultra G2. Ultra and Ultra LT need 6.6.B or later.
  • CVE-2025-53695 (JCI-PSA-2025-10 v2, ICSA-25-224-02): authenticated OS command injection to root in the web application of iSTAR Ultra, Ultra SE, Ultra G2, Ultra G2 SE and Edge G2 up to 6.9.2.CU02, reported by Reid Wightman of Dragos, which is also the CNA for the record. Dragos scores it CVSS v4 9.4 and CISA CVSS v3.1 8.8; NVD lists it as Deferred with no Primary score. The same advisory covers five related flaws that build on it or need physical access, including unchecked firmware regions, a default root password and a reachable firmware signing key. Firmware 6.9.3 fixes CVE-2025-53695; 6.9.8 adds protection against physical access on Ultra and Ultra SE.

Johnson Controls' 2025 advice for the iSTAR family is to disable the controller web server after installation, and CISA adds that Pro Mode should be turned off in favour of Ultra Mode. The command injection fix guide explains why the same class keeps recurring in controller web applications.

What about exacqVision and Kantech?

exacqVision is the Johnson Controls video line; the network video recorder and camera side is covered in the IP camera and NVR firmware guide.

CVE Product Weakness Score (scorer) Fix
CVE-2020-9047 exacqVision Web Service up to 20.06.3.0, Enterprise Manager up to 20.06.4.0 No signature check, so an administrator can be made to download and run a malicious executable 6.8 (Johnson Controls, CISA); NVD 7.2 Web Service 20.06.4, Enterprise Manager 20.06.5 (CISA)
CVE-2021-27664 exacqVision Web Service 21.06.11.0 and earlier Unauthenticated remote access to credentials stored in exacqVision Server 9.8 (Johnson Controls, CISA, NVD) Web Service 21.09
CVE-2024-32758 exacqVision Client and Server, all versions Insufficient key length and exchange between client and server 8.3 (CISA v3.1), 9.0 (Johnson Controls v4); NVD 7.5 Version 24.06 and the password strengthening steps of the exacqVision Hardening Guide
CVE-2019-7589 Kantech EntraPass Corporate and Global 8.0 and earlier SmartService API lets an unauthorized user upload code that runs with system privileges 9.8 (Johnson Controls, CISA, NVD) EntraPass 8.10
CVE-2020-9046 Kantech EntraPass editions 8.22 and earlier Low-privileged user replaces critical files to gain system privileges 8.8 (Johnson Controls, CISA); NVD 7.8 EntraPass 8.23
CVE-2021-27662 Kantech KT-1 door controller 3.01 and earlier Replay or man-in-the-middle of TCP command messages 8.6 (Johnson Controls, CISA); NVD 8.1 KT-1 3.04 together with EntraPass 8.40

For CVE-2020-9047, the CVE record names Web Service 20.06.2.0 and Enterprise Manager 20.06.3.0 as the fixed versions, below the affected versions in its own description; CISA's Update A gives 20.06.4 and 20.06.5, which is the consistent pair. The KT-1 fix needs both the controller and the EntraPass server updated together.

Are Johnson Controls vulnerabilities exploited in the wild?

No Johnson Controls, Software House, exacqVision or Tridium CVE is in the CISA KEV catalog as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). CISA's advisories ICSA-25-219-02, ICSA-25-224-02, ICSA-26-027-04 and ICSA-26-225-14 each say no known public exploitation targeting the flaws had been reported to CISA, and the 2019 Facility Explorer advisory says no known public exploits specifically target the flaws.

FIRST EPSS scores dated 2026-11-23, the latest as of 2026-11-24, put the older web-facing flaws at the top:

CVE Product EPSS Percentile
CVE-2020-9047 exacqVision Web Service 0.07770 0.948
CVE-2017-16744 Facility Explorer (Niagara) 0.06142 0.936
CVE-2014-5428 Metasys web services file upload 0.03871 0.905
CVE-2020-9050 Metasys Reporting Engine 0.03833 0.904
CVE-2022-21941 iSTAR Ultra 0.02173 0.828
CVE-2019-7589 Kantech EntraPass 0.01602 0.764
CVE-2021-27664 exacqVision Web Service 0.01601 0.764
CVE-2025-26385 Metasys SQL Express 0.01475 0.745
CVE-2025-53695 iSTAR Ultra family 0.00885 0.601
CVE-2024-0912 C•CURE 9000 0.00164 0.056

EPSS estimates internet-wide exploitation activity, not how reachable a door controller or engine is from a flat building network. The KEV and EPSS prioritization guide explains how to rank by reachability first.

How should Metasys and the security systems be hardened?

The steps below come from Johnson Controls' mitigations and CISA's recommended practices:

  1. Patch Metasys SQL ExpressApply the GIV-165989 patch, close incoming TCP 1433 and disable the SQL Express SA account on ADS, ADX, LCS8500, NAE8500, SCT and CCT installations.
  2. Bring Metasys to a supported releaseMetasys 14 needs 14.1.5 and Metasys 15 needs 15.0.1 for CVE-2026-34491; Metasys 12 and 13 are past end of support. Engines need at least 11.0.6 or 12.0.4 for CVE-2023-4486.
  3. Retire pre-9.0 MetasysRelease 9.0 with trusted certificates is Johnson Controls' only fix for the shared SMP keys.
  4. Patch Facility Explorer with the matching Niagara fixes: FX 14.10.11 or 14.14.2 for FX Server, FX80 and FX90.
  5. Update iSTAR firmware and turn off the web serverMove the Ultra family to 6.9.3 or later (6.9.8 on Ultra and Ultra SE), disable the web server after installation and use Ultra Mode instead of Pro Mode. Replace iSTAR Pro, Edge and eX controllers.
  6. Clean credentials out of C•CURE logsAfter upgrading to 3.00.2 CU02 or 3.00.3, delete api.log and the installer logs and change the affected Windows passwords.
  7. Update exacqVision and KantechexacqVision 24.06 with the hardening guide's password steps, EntraPass 8.40 with KT-1 3.04.
  8. Segment and restrictJohnson Controls asks for Metasys to sit on a segmented network not exposed to the internet and for UI access to be limited to trusted users. CISA asks owners to keep control system devices off the internet, put them behind firewalls isolated from business networks and use VPNs for remote access.

Run these updates through a change process such as the one in the IEC 62443-2-3 patch management guide, since many Metasys and Facility Explorer patches come only through a Johnson Controls branch office, an Authorized Building Control Specialist or a portal that needs a login.

How do you check which version a Johnson Controls system runs?

Johnson Controls fixes arrive as release numbers, patch builds and firmware levels, so record each one:

  1. Record the Metasys release and patch per server and engine"Metasys 11" alone does not show whether 11.0.2, 11.0.3 or 11.0.6 is installed, and those decide which advisories apply.
  2. Record which servers run the bundled SQL ExpressCVE-2025-26385 applies only where SQL Express was deployed by the Metasys, SCT or CCT installer.
  3. Record the FX release and its Niagara baseFX 14.10.10 and 14.14.1 map to Niagara 4.10u10 and 4.14u1.
  4. Record iSTAR model and firmwarePro, Edge and eX have no fix for CVE-2024-32752; the Ultra family splits at 6.6.B, 6.8.9.CU01, 6.9.2 CU01, 6.9.3 and 6.9.8.
  5. Do not rely on CPE matching aloneAs of 2026-11-24, NVD has no Primary analysis for CVE-2025-26385, CVE-2025-43867, CVE-2024-32752, CVE-2025-53695 or CVE-2026-34491, and the CVE-2026-34491 record omits Metasys 12 and 13. Read the JCI-PSA tables.

How do you monitor Metasys and access control networks?

Start with a baseline of which hosts talk to each server, engine and controller, and on which ports, then alert on changes:

  • Connections to TCP 1433 on Metasys servers, SCT or CCT hosts from anything other than the Metasys applications that need it, which fits CVE-2025-26385.
  • Web sessions to Metasys UI, engines or MRE from outside the building management subnet, which fits CVE-2020-9050, CVE-2023-4486 and CVE-2026-34491.
  • Any host other than the C•CURE server and the engineering PC reaching iSTAR controllers, which fits CVE-2024-32752 and CVE-2025-53695.
  • New hosts on the segment between KT-1 controllers and the EntraPass server, which fits the replay attack in CVE-2021-27662.
  • exacqVision Web Service reachable from outside the security network, which fits CVE-2021-27664.

Flow records show who connected to which port and when, not which Metasys object or iSTAR command was sent. Map alerts to MITRE ATT&CK for ICS techniques such as exploitation of remote services and valid accounts.

Worked example: what does a review of an office campus find?

Synthetic example, not a real site. An office campus runs Metasys 11.0.2 on an ADS server with the bundled SQL Express, NAE55 engines on 11.0.4, two FX80 controllers on FX 14.10.10 in a car park building, C•CURE 9000 3.00.2 without CU02 with iSTAR Ultra controllers on 6.8.9.CU01, and exacqVision Web Service 21.06.

Observation Why it matters Action
ADS on 11.0.2 with SQL Express CVE-2021-36204 needs 11.0.3; CVE-2025-26385 applies to the SQL Express instance Move to a supported release, apply GIV-165989, close TCP 1433, disable the SA account
NAE55 engines on 11.0.4 Below 11.0.6, so CVE-2023-4486 lets bad logins stop them Update to 11.0.6 or later
FX80 on FX 14.10.10 CVE-2025-43867 and the Niagara CVEs behind it apply Apply the 14.10.11 patch
iSTAR Ultra on 6.8.9.CU01 with the web server on Fixed for CVE-2022-21941 but open to CVE-2023-3127 and CVE-2025-53695 Update to 6.9.8, disable the web server, use Ultra Mode
C•CURE 9000 on 3.00.2 without CU02 CVE-2024-0912 credentials may sit in api.log Upgrade to 3.00.3, delete api.log, change the passwords
exacqVision Web Service 21.06 reachable from the guest Wi-Fi CVE-2021-27664 exposes stored credentials before 21.09 Upgrade, then restrict access to the security network

Where does passive monitoring fit in a Johnson Controls review?

A passive capture shows who talks to building and security systems without logging in to anything. SoftWSP's OT Snapshot reads Zeek and ICSNPP logs from a mirror-port recording and builds a host-by-port inventory at connection level, including hosts using TCP 1433 and web ports, and lists remote-access sessions that cross from outside the private address range. It does not decode Metasys, ICU or iSTAR messages or read Metasys releases from traffic, so those come from the asset list. For that list, Device & Firmware Security identifies components and versions and matches them against NVD, CISA KEV, FIRST EPSS and CISA ICS advisories. An engineer reviews every AI-drafted, cited report before it is sent.

What are the common pitfalls?

  • Patching the Metasys application but leaving the SQL Express instance it installed listening on TCP 1433.
  • Treating FX80 and FX90 as separate from Niagara, when Facility Explorer releases map directly to Niagara updates.
  • Keeping iSTAR Pro, Edge or eX controllers in service, when CVE-2024-32752 has no firmware fix for them.
  • Upgrading C•CURE 9000 without deleting the logs that already hold Windows credentials.
  • Reading one score: NVD rates CVE-2019-7593 and CVE-2020-9044 at 9.1 where Johnson Controls and CISA say 6.8 and 7.5, and rates CVE-2020-9045 at 6.5 where they say 9.9.
  • Trusting the CVE record over the advisory: the CVE-2026-34491 record omits Metasys 12 and 13, and the CVE-2020-9047 record gives fixed versions lower than the affected ones.

This guide draws on Johnson Controls Product Security Advisories JCI-PSA-2019-06 to JCI-PSA-2026-11, CISA ICS advisories ICSA-14-350-02, ICSA-18-212-02, ICSA-19-022-01, ICSA-19-227-01, ICSA-20-070-04, ICSA-20-070-05, ICSA-20-142-01, ICSA-20-147-02, ICSA-20-170-01, ICSA-21-049-01, ICSA-21-159-01, ICSA-21-182-01, ICSA-21-257-02, ICSA-21-280-01, ICSA-22-095-02, ICSA-22-118-01, ICSA-22-125-01, ICSA-22-165-01, ICSA-22-242-11, ICSA-22-277-01, ICSA-23-012-06, ICSA-23-040-03, ICSA-23-192-02, ICSA-23-341-03, ICSA-24-135-03, ICSA-24-158-04, ICSA-24-214-01, ICSA-25-219-02, ICSA-25-224-02, ICSA-26-027-04 and ICSA-26-225-14 and their CSAF records, NVD and CVE.org records, CISA KEV and FIRST EPSS, all checked as of 2026-11-24.

Put this guide to work

Frequently asked questions

Are any Johnson Controls Metasys or iSTAR vulnerabilities in the CISA KEV catalog?

No. As of 2026-11-24, CISA's Known Exploited Vulnerabilities catalog (version 2026.11.23, 1,792 entries) has no entry for Johnson Controls, Software House, Tridium or exacqVision, and none of the 37 CVEs in this guide is listed. CISA's Johnson Controls advisories from 2025 and 2026 (ICSA-25-219-02, ICSA-25-224-02, ICSA-26-027-04 and ICSA-26-225-14) say no known public exploitation targeting the flaws had been reported to CISA. The highest FIRST EPSS score among the 37 CVEs, dated 2026-11-23, belongs to the exacqVision flaw CVE-2020-9047 at 0.078.

How do you fix the 2026 Metasys SQL Express vulnerability CVE-2025-26385?

Johnson Controls' JCI-PSA-2026-02 and CISA's ICSA-26-027-04 (27 January 2026) cover a command injection in the SQL Express instance that the Metasys installer deploys with ADS (14.1 and earlier), ADX (14.1), LCS8500 and NAE8500 (12.0 to 14.1), SCT (17.1 and earlier) and CCT (17.0 and earlier). CISA scores it CVSS v3.1 10.0 and Johnson Controls CVSS v4 9.5. The fixes are the Metasys patch for GIV-165989 from the Johnson Controls License Portal, closing incoming TCP port 1433, disabling the SQL Express SA account and keeping Metasys on a segmented network that is not reachable from the internet.

Which iSTAR firmware fixes the 2025 Dragos command injection?

Johnson Controls' JCI-PSA-2025-10 v2 says firmware 6.9.3, available since 2024, fixes CVE-2025-53695 in iSTAR Ultra, Ultra SE, Ultra G2, Ultra G2 SE and Edge G2 (6.9.2.CU02 and earlier are affected) and lowers the risk from three related flaws. It recommends 6.9.8 on iSTAR Ultra and Ultra SE to protect against attackers with physical access, and turning off the controller web server after installation. CISA's ICSA-25-224-02 adds that Pro Mode should be disabled in favour of Ultra Mode, and that the iSTAR Ultra is scheduled to reach end of service within a year of that advisory.

Do the Tridium Niagara vulnerabilities affect Johnson Controls Facility Explorer?

Yes. FX Server, FX80 and FX90 run Facility Explorer releases built on Niagara 4: Johnson Controls says FX 14.10.10 aligns with Niagara 4.10u10 and FX 14.14.1 with Niagara 4.14u1. JCI-PSA-2025-09 v2 and CISA's ICSA-25-219-02 track this as CVE-2025-43867 and say exploiting it could trigger the Niagara CVEs CVE-2025-3936 through CVE-2025-3945. The fix is the FX 14.10.11 patch for 14.10.10 and earlier, or the 14.14.2 patch for 14.14.1 and earlier.

Where does Johnson Controls publish its security advisories?

Johnson Controls lists every Product Security Advisory (JCI-PSA) on its Trust Center security advisories page, with affected products, CVE ids, initial and last-updated dates and a PDF for each. CISA republishes most of them as ICS advisories with CSAF files on GitHub, and Johnson Controls is the CNA that writes most of the CVE records. Johnson Controls' hardening guides for Metasys, exacqVision and other products are on the Trust Center cybersecurity resources page.

Sources

  1. Johnson Controls Trust Center: Security Advisories
  2. Johnson Controls JCI-PSA-2026-02: Metasys SQL Express (CVE-2025-26385)
  3. Johnson Controls JCI-PSA-2026-11: Metasys 12 to 15 (CVE-2026-34491)
  4. Johnson Controls JCI-PSA-2025-10 v2: iSTAR Ultra, Ultra SE, Ultra G2, Ultra G2 SE and Edge G2
  5. Johnson Controls JCI-PSA-2025-09 v2: Facility Explorer FX Server, FX80 and FX90 (CVE-2025-43867)
  6. Johnson Controls JCI-PSA-2024-06 v2: iSTAR Configuration Utility (CVE-2024-32752)
  7. Johnson Controls JCI-PSA-2023-08 v2: Metasys and Facility Explorer engines (CVE-2023-4486)
  8. Johnson Controls JCI-PSA-2021-14: Kantech KT-1 door controller (CVE-2021-27662)
  9. CISA CSAF: ICSA-26-027-04 Johnson Controls Metasys Products
  10. CISA CSAF: ICSA-26-225-14 Johnson Controls Metasys
  11. CISA CSAF: ICSA-25-224-02 Johnson Controls iSTAR Ultra, Ultra SE, Ultra G2, Ultra G2 SE, Edge G2 (Update A)
  12. CISA CSAF: ICSA-25-219-02 Johnson Controls FX Server, FX80 and FX90 (Update A)
  13. CISA CSAF: ICSA-24-214-01 Johnson Controls exacqVision Client and Server
  14. CISA CSAF: ICSA-24-158-04 Johnson Controls Software House iStar Door Controller (Update A)
  15. CISA CSAF: ICSA-24-135-03 Johnson Controls Software House C•CURE 9000
  16. CISA CSAF: ICSA-23-341-03 Johnson Controls Metasys and Facility Explorer (Update A)
  17. CISA CSAF: ICSA-23-192-02 Sensormatic Electronics iSTAR
  18. CISA CSAF: ICSA-23-040-03 Johnson Controls System Configuration Tool (SCT)
  19. CISA CSAF: ICSA-23-012-06 Johnson Controls Metasys
  20. CISA CSAF: ICSA-22-277-01 Johnson Controls Metasys ADX Server
  21. CISA CSAF: ICSA-22-242-11 Sensormatic Electronics iSTAR
  22. CISA CSAF: ICSA-22-165-01 Johnson Controls Metasys ADS ADX OAS Servers
  23. CISA CSAF: ICSA-22-125-01 Johnson Controls Metasys
  24. CISA CSAF: ICSA-22-118-01 Johnson Controls Metasys
  25. CISA CSAF: ICSA-22-095-02 Johnson Controls Metasys
  26. CISA CSAF: ICSA-21-280-01 Johnson Controls exacqVision Server Bundle
  27. CISA CSAF: ICSA-21-257-02 Johnson Controls Sensormatic Electronics KT-1
  28. CISA CSAF: ICSA-21-182-01 Johnson Controls Facility Explorer
  29. CISA CSAF: ICSA-21-159-01 Johnson Controls Metasys
  30. CISA CSAF: ICSA-21-049-01 Johnson Controls Metasys Reporting Engine (MRE) Web Services
  31. CISA CSAF: ICSA-20-170-01 Johnson Controls exacqVision (Update A)
  32. CISA CSAF: ICSA-20-147-02 Johnson Controls Kantech EntraPass
  33. CISA CSAF: ICSA-20-142-01 Johnson Controls Software House C-CURE 9000 and American Dynamics victor VMS
  34. CISA CSAF: ICSA-20-070-05 Johnson Controls Metasys
  35. CISA CSAF: ICSA-20-070-04 Johnson Controls Kantech EntraPass
  36. CISA CSAF: ICSA-19-227-01 Johnson Controls Metasys
  37. CISA CSAF: ICSA-19-022-01 Johnson Controls Facility Explorer
  38. CISA CSAF: ICSA-18-212-02 Johnson Controls Metasys and BCPro
  39. CISA CSAF: ICSA-14-350-02 Johnson Controls Metasys Vulnerabilities
  40. NVD: CVE-2025-26385 (Metasys SQL Express command injection)
  41. NVD: CVE-2022-21941 (iSTAR Ultra command injection)
  42. NVD: CVE-2020-9047 (exacqVision Web Service signature verification)
  43. NVD: CVE-2019-7593 (Metasys shared RSA key pair)
  44. CVE.org: CVE-2025-53695 (iSTAR Ultra OS command injection, Dragos CNA)
  45. CISA Known Exploited Vulnerabilities catalog
  46. FIRST: Exploit Prediction Scoring System (EPSS)
Was this guide helpful?