Security Advisory

CVE-2025-3945: Niagara QNX Argument Injection

Last updated:
  • CVE-2025-3945

**CVE-2025-3945** is an argument injection flaw (CWE-88) in Tridium Niagara Framework and Niagara Enterprise Security on QNX, published on 2025-05-22, that lets command delimiters reach a command the system runs. It affects Niagara 4.10u10, 4.14u1 and 4.15 on QNX-based devices. NVD scores it 9.8, while Honeywell scores it 7.2 because an administrator account is needed.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

0.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2025-3945 · Source: NVD

Affected components

ComponentCPEVersion range
Tridium Niagara Framework on QNX onlycpe:2.3:a:tridium:niagara:*:*:*:*:*:*:*:*affected: 4.10u10, 4.14u1 and 4.15 (NVD CPE, SB 2025-Tridium-1); fixed in 4.10u.11, 4.14.2u2 and 4.15.u1 per the CVE record
Tridium Niagara Enterprise Security on QNX onlycpe:2.3:a:tridium:niagara_enterprise_security:*:*:*:*:*:*:*:*affected: 4.10u10, 4.14u1 and 4.15 (NVD CPE, SB 2025-Tridium-1); fixed in 4.10u.11, 4.14.2u2 and 4.15.u1 per the CVE record
Johnson Controls FX80, FX90 and FX Server (bundle Niagara 4.10u10 / 4.14u1)—FX 14.10.10 and FX 14.14.1 and earlier per CISA ICSA-25-219-02 (filed as CVE-2025-43867); patches FX 14.10.11 and 14.14.2

What does this mean for affected devices?

NVD describes CVE-2025-3945 as an "Improper Neutralization of Argument Delimiters in a Command ('Argument Injection') vulnerability in Tridium Niagara Framework on QNX, Tridium Niagara Enterprise Security on QNX" that "allows Command Delimiters", with CWE-88 from both NVD and Honeywell (NVD). NVD's own CVSS 3.1 score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). Honeywell, the CNA, scores it 7.2 with PR:H, the same rating it gives the other QNX-only flaw in the batch. NVD's configuration lists releases 4.10u10, 4.14u1 and 4.15 running on QNX.

Neither the CVE record nor Tridium's bulletin says which command or input is involved. Nozomi Networks Labs, which reported the batch, lists CVE-2025-3945 at 7.2 among the ten CVEs and shows its own product detecting an exploitation attempt, but its write-up details only CVE-2025-3943 and CVE-2025-3944. The bulletin's summary of fixes for the batch includes "properly escaping characters or rejecting characters stored in some configuration files" (SB 2025-Tridium-1). In argument injection, a value that should be one argument is split by the program into extra options or commands. On a QNX-based Niagara device, an injected command would run on the device itself.

Because the Honeywell vector needs high privileges, the realistic route is the one Nozomi shows for the sister bug CVE-2025-3944: an attacker first takes an administrator session, for example through the token leak in CVE-2025-3943, and then uses a QNX-only flaw to go beyond what the station allows. Nozomi's example target is a "Niagara-based Tridium Jace 8000" on a local network.

Johnson Controls ships the same code in its own building controllers. CISA's advisory ICSA-25-219-02, Update A of 2025-12-04 (CSAF), lists the FX80 and FX90 controllers and FX Server at FX 14.10.10 and FX 14.14.1 and earlier under CVE-2025-43867, notes that "FX 14.10.10 contains Niagara 4.10u10" and "FX 14.14.1 contains Niagara 4.14u1", and warns that exploiting it "could trigger CVEs CVE-2025-3936 through CVE-2025-3945". The fix there is the FX 14.10.11 or 14.14.2 patch from the Johnson Controls software portal.

CVE-2025-3945 is not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.0062, percentile 50.2, in the 2026-11-15 dataset (CISA KEV, FIRST EPSS).

Tridium's bulletin SB 2025-Tridium-1 lists Niagara Framework and Enterprise Security 4.10u10, 4.14u1 and 4.15 as affected and tells 4.14 sites to move to 4.14u2; the CVE record names 4.14.2u2, 4.15.u1 and 4.10u.11 as the fixed releases. The bulletin also asks sites to review the Security Dashboard for warnings and to follow the Niagara 4 Hardening Guide. Our Niagara Fox protocol guide explains how this batch fits with the long history of Niagara exposure, and CVE-2025-3937 is the bulletin's weak password hash flaw.

How to fix this class of issueThis advisory's weakness class is Command injection. Our practical guide covers how to detect, fix, verify and disclose it: How to fix command injection in embedded firmware.

Evidence

Related advisories

Sources

  1. NVD
  2. Honeywell/Tridium Security Bulletin SB 2025-Tridium-1: Niagara software vulnerabilities (PDF)
  3. Nozomi Networks Labs: Critical Vulnerabilities Found in Tridium Niagara Framework (2025-07-23)
  4. CISA ICSA-25-219-02: Johnson Controls FX Server, FX80 and FX90, Update A (CSAF)
  5. Tridium: Niagara 4 Hardening Guide (2025-01-17, PDF)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which Niagara platforms does CVE-2025-3945 affect?

Only Niagara Framework and Niagara Enterprise Security on QNX, in releases 4.10u10, 4.14u1 and 4.15 (per NVD).

Why do the CVE-2025-3945 scores differ?

NVD scored it 9.8 with no privileges required (PR:N). Honeywell, the CNA, scored it 7.2 with high privileges required (PR:H), so an attacker must already hold an administrator account (per NVD and SB 2025-Tridium-1).

Has the exact injection point of CVE-2025-3945 been published?

No. The CVE record and Tridium's bulletin name only the weakness class, and Nozomi Networks Labs details CVE-2025-3943 and CVE-2025-3944 but not this one (per NVD, SB 2025-Tridium-1 and Nozomi Networks Labs).

What fixes CVE-2025-3945?

Niagara Framework and Enterprise Security 4.14.2u2, 4.15.u1 or 4.10u.11, as named in the CVE record; on Johnson Controls FX80, FX90 and FX Server, the FX 14.10.11 or 14.14.2 patch (per NVD and CISA ICSA-25-219-02).

Is CVE-2025-3945 known to be exploited?

It is not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13), and FIRST EPSS gives it 0.0062, percentile 50.2, in the 2026-11-15 dataset (per CISA KEV and FIRST EPSS).