Security Advisory

CVE-2025-3944: Niagara QNX dhcpd.conf Root Code Execution

Last updated:
  • CVE-2025-3944

**CVE-2025-3944** is a permission flaw in Tridium Niagara on QNX, published on 2025-05-22: the file transfer feature does not protect /etc/dhcpd/dhcpd.conf, so an authenticated Niagara administrator can overwrite it and run code as root on the device. NVD scores it 9.8 and Honeywell 7.2. It affects Niagara 4.10u10, 4.14u1 and 4.15.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

0.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2025-3944 · Source: NVD

Affected components

ComponentCPEVersion range
Tridium Niagara Framework on QNX onlycpe:2.3:a:tridium:niagara:*:*:*:*:*:*:*:*affected: 4.10u10, 4.14u1 and 4.15 (NVD CPE, SB 2025-Tridium-1); fixed in 4.10u.11, 4.14.2u2 and 4.15.u1 per the CVE record
Tridium Niagara Enterprise Security on QNX onlycpe:2.3:a:tridium:niagara_enterprise_security:*:*:*:*:*:*:*:*affected: 4.10u10, 4.14u1 and 4.15 (NVD CPE, SB 2025-Tridium-1); fixed in 4.10u.11, 4.14.2u2 and 4.15.u1 per the CVE record
Johnson Controls FX80, FX90 and FX Server (bundle Niagara 4.10u10 / 4.14u1)—FX 14.10.10 and FX 14.14.1 and earlier per CISA ICSA-25-219-02 (filed as CVE-2025-43867); patches FX 14.10.11 and 14.14.2

What does this mean for affected devices?

NVD describes CVE-2025-3944 as an "Incorrect Permission Assignment for Critical Resource vulnerability in Tridium Niagara Framework on QNX, Tridium Niagara Enterprise Security on QNX" that allows file manipulation, with CWE-732 from both NVD and Honeywell (NVD). The scores differ by 2.6 points: NVD's own CVSS 3.1 score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), while Honeywell, the CNA, scores it 7.2 with PR:H, because the attacker must already be a Niagara administrator. NVD's configuration ties the affected releases 4.10u10, 4.14u1 and 4.15 to QNX, which Nozomi calls the QNX-based Niagara operating system of Niagara devices.

Nozomi Networks Labs explains the mechanism. Niagara's secure file transfer feature is meant to stop administrators from reading or changing sensitive files, "however, it does not properly safeguard the /etc/dhcpd/dhcpd.conf file on devices running the QNX-based Niagara operating system." An administrator can overwrite the file and add DHCP hooks such as on commit, on release and on expiry, which then execute arbitrary commands with root privileges; Nozomi's example copies /etc/passwd and /etc/shadow to a readable file. Root on the controller is more than Niagara administrator rights, because it reaches the operating system underneath the station.

In Nozomi's attack chain this is the final step. An adjacent attacker first reads the anti-CSRF token from unencrypted Syslog (CVE-2025-3943), hijacks an administrator session, creates a backdoor administrator and steals the device's TLS private key to reach the Platform, and then uses CVE-2025-3944 for "root-level RCE on the device, achieving complete takeover." Nozomi's example target is a "Niagara-based Tridium Jace 8000" on a local network.

Johnson Controls ships the same code in its own building controllers. CISA's advisory ICSA-25-219-02, Update A of 2025-12-04 (CSAF), lists the FX80 and FX90 controllers and FX Server at FX 14.10.10 and FX 14.14.1 and earlier under CVE-2025-43867, notes that "FX 14.10.10 contains Niagara 4.10u10" and "FX 14.14.1 contains Niagara 4.14u1", and warns that exploiting it "could trigger CVEs CVE-2025-3936 through CVE-2025-3945". The fix there is the FX 14.10.11 or 14.14.2 patch from the Johnson Controls software portal.

CVE-2025-3944 is not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.0050, percentile 43.4, in the 2026-11-15 dataset (CISA KEV, FIRST EPSS).

Tridium's bulletin SB 2025-Tridium-1 lists Niagara Framework and Enterprise Security 4.10u10, 4.14u1 and 4.15 as affected and tells 4.14 sites to move to 4.14u2; the CVE record names 4.14.2u2, 4.15.u1 and 4.10u.11 as the fixed releases. The bulletin also asks sites to review the Security Dashboard for warnings and to follow the Niagara 4 Hardening Guide. Since the attacker needs administrator rights, the bulletin's other step also applies here: review and validate the list of users who can authenticate to Niagara. Our Niagara Fox protocol guide covers how these CVEs fit with the plaintext Fox exposure, and CVE-2025-3945 is a second QNX-only flaw in the same bulletin.

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

Related advisories

Sources

  1. NVD
  2. Honeywell/Tridium Security Bulletin SB 2025-Tridium-1: Niagara software vulnerabilities (PDF)
  3. Nozomi Networks Labs: Critical Vulnerabilities Found in Tridium Niagara Framework (2025-07-23)
  4. CISA ICSA-25-219-02: Johnson Controls FX Server, FX80 and FX90, Update A (CSAF)
  5. Tridium: Niagara 4 Hardening Guide (2025-01-17, PDF)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Does CVE-2025-3944 affect Niagara on Windows or Linux?

No. NVD and the CVE description limit it to Niagara Framework and Niagara Enterprise Security on QNX, the operating system Nozomi calls the QNX-based Niagara operating system (per NVD and Nozomi Networks Labs).

Does an attacker need credentials to exploit CVE-2025-3944?

Yes. Nozomi describes an authenticated attacker with administrative privileges, and Honeywell scores it with PR:H. NVD's own 9.8 score uses PR:N. In Nozomi's chain the administrator session is first stolen through CVE-2025-3943 (per Nozomi Networks Labs and NVD).

Which file does CVE-2025-3944 abuse?

/etc/dhcpd/dhcpd.conf. An administrator can overwrite it through the file transfer feature and add on commit, on release or on expiry hooks that run commands as root (per Nozomi Networks Labs).

How is CVE-2025-3944 fixed?

Upgrade to Niagara Framework and Enterprise Security 4.14.2u2, 4.15.u1 or 4.10u.11 as named in the CVE record; Johnson Controls FX80, FX90 and FX Server take the FX 14.10.11 or 14.14.2 patch (per NVD and CISA ICSA-25-219-02).

Is CVE-2025-3944 in the CISA KEV catalog?

No, as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.0050, percentile 43.4, in the 2026-11-15 dataset (per CISA KEV and FIRST EPSS).