CVE-2024-27774 is a hard-coded password weakness in Unitronics UniStream PLC/HMI firmware that may disclose manufacturer production information stored in the firmware. Unitronics advisory 2024-008 lists all UniStream products with UniLogic before 1.35.227 as affected and names 1.35.227 or later as the fix. NVD scores it CVSS 3.1 6.5; the CNA INCD scores it 7.5.
Vulnerability summary
CVSS base score
6.5
Medium severity
EPSS score (FIRST)
0.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2024-27774 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Unitronics UniStream PLC/HMI series, all products (Unitronics advisory 2024-008), programmed with UniLogic | cpe:2.3:a:unitronics:unilogic:*:*:*:*:*:*:*:* | UniLogic before 1.35.227 (NVD CPE and Unitronics advisory); fixed in UniLogic 1.35.227 or later |
What does this mean for affected devices?
The CVE record for CVE-2024-27774 reads "CWE-259: Use of Hard-coded Password may allow disclosing Sensitive Information Embedded inside Device's Firmware" for UniLogic versions prior to 1.35.227. The Israel National Cyber Directorate (INCD) published it as CNA on 2024-03-18 and credits Noam Moshe and Vera Mens of Claroty Team82. NVD maps it to CWE-798 (hard-coded credentials) and its CPE covers UniLogic before 1.35.227 (NVD, CVE record).
Why do NVD and INCD score it differently?
NVD's Primary score is CVSS 3.1 6.5 (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N): a confidentiality impact only. INCD scores it 7.5 (AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H), with high attack complexity but high impact on integrity and availability as well. Claroty Team82's per-CVE list on its write-up also shows 7.5. The difference comes from what the disclosed information lets an attacker do next, which the public sources do not describe.
Which Unitronics products are affected?
Unitronics Cybersecurity Advisory 2024-008, titled "Use of Hard-coded Password" and dated 18 March 2024, names the component as UniStream, the product as "All Products" and the affected version as UniLogic below 1.35.227. Its summary says that "manufacturer production information is embedded inside the device's firmware" and its description that "device production information is stored as part of the firmware". A hard-coded secret is the same on every unit that runs a given firmware, so it cannot be changed by the owner and is fixed only by an update.
How does it fit with the other UniStream flaws?
Claroty Team82 reported eight UniStream flaws together and says some of them chain to full control of the PLC. This is the lowest scored by NVD. The flaws that matter most for an exposed controller are the authentication bypass CVE-2024-27767 and the information exposure CVE-2024-27769, which the CNA says may allow taking ownership of a device. Team82 counted about 480 vulnerable UniStream devices reachable from the internet.
How do you fix or mitigate it?
Unitronics' advisory gives five steps: update to UniLogic 1.35.227 or later; verify that PLCs are not directly accessible from the internet and allow access only from defined addresses or through a VPN or ZTNA; apply long complex passwords and change the default installed password; use UniCloud for two-factor access, particularly for admin access; and keep devices on the latest security updates. Changing the user password does not remove a password built into the firmware, so the update is the fix. The advisory does not say whether the controller needs a separate update, so after updating UniLogic, check the operating system version reported by each controller against Unitronics' release notes. Our Unitronics Vision and UniStream vulnerability guide covers the full Unitronics set, and the hard-coded credentials fix guide covers the weakness class.
Is it exploited?
CVE-2024-27774 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). The only Unitronics entry is CVE-2023-6448, a default (not hard-coded) password on Vision and Samba controllers. FIRST EPSS gives CVE-2024-27774 0.00431, the 38.2nd percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-21): status Analyzed; published 2024-03-18, source [email protected]; description 'Unitronics Unistream Unilogic – Versions prior to 1.35.227 - CWE-259: Use of Hard-coded Password may allow disclosing Sensitive Information Embedded inside Device's Firmware'; NVD Primary CVSS 3.1 6.5 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N; CNA Secondary 7.5 AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H; CWE-259 (CNA), CWE-798 (NVD); CPE cpe:2.3:a:unitronics:unilogic versions before 1.35.227. — NVD
- Unitronics Cybersecurity Advisory 2024-008 'Use of Hard-coded Password', publication date 18 March 2024, read 2026-11-21: component UniStream, product All Products, affected UniLogic < 1.35.227; summary 'Manufacturer production information is embedded inside the device's firmware'; description 'Device production information is stored as part of the firmware'; mitigations: update to UniLogic 1.35.227 or later, no direct internet access (defined addresses, VPN or ZTNA), long complex passwords and change the default, UniCloud 2FA, regular updates. — Unitronics
- CVE record (CVE Services API, checked 2026-11-21): state PUBLISHED, CNA INCD, published 2024-03-18; affected 'Unitronics Unistream Unilogic' less than 1.35.227; CVSS 3.1 7.5; finder Noam Moshe, Vera Mens of Claroty Team82; solution 'Upgrade to version 1.35.227 or later.' — CVE.org
- Claroty Team82 'New Critical Vulnerabilities in Unitronics UniStream Devices Uncovered', published 2024-03-18, read 2026-11-21: eight vulnerabilities that bypass UniStream authentication and authorization and can be chained to remote code execution; around 480 internet-exposed and vulnerable UniStream devices found with Shodan and Censys; devices are not preconfigured to be reachable online; disclosed to Unitronics, CISA and the Israel National Cyber Directorate; per-CVE list with CWE and CVSS v3. CVE-2024-27774 listed as CWE-259, CVSS v3 7.5. — Claroty Team82
- Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21; the only Unitronics entry is CVE-2023-6448 (added 2023-12-11). — CISA KEV
- EPSS 0.00431, percentile 0.38226, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which version fixes CVE-2024-27774?
UniLogic 1.35.227 or later. Unitronics advisory 2024-008, the CVE record and NVD's CPE all say UniLogic versions before 1.35.227 are affected, and Unitronics lists every UniStream product.
Can I fix it by changing the controller password?
No. The hard-coded password is part of the firmware, not a user setting, so only the update removes it. Changing the default user password is still one of Unitronics' recommended steps, because it closes a different route into the controller.
Which score should I use, 6.5 or 7.5?
NVD's Primary score is 6.5 with a confidentiality impact only; INCD and Claroty give 7.5 with higher complexity but full impact. If your process uses NVD's Primary metric, use 6.5, and note INCD's 7.5 for the worst case.
Is this the flaw used in the 2023 water utility attacks?
No. The 2023 attacks on US water facilities used Unitronics Vision controllers and the default password weakness CVE-2023-6448, the only Unitronics entry in the CISA KEV catalog as of 2026-11-21. Claroty Team82 says that campaign prompted its research into the newer UniStream series, which found this and seven other flaws.
Questions about this page?