Security Advisory

CVE-2022-45788: Modicon Malicious Project File

Last updated:
  • CVE-2022-45788

CVE-2022-45788 is a flaw in Schneider Electric Modicon controllers and EcoStruxure Control Expert: a malicious project file loaded onto the controller can execute arbitrary code, stop the PLC or expose and change its logic. NVD scores it 9.8, Schneider 7.5. Fixes are Control Expert V15.3 plus M580 SV4.10, M340 SV3.51, MC80 SV1.90 and Momentum SV2.6 firmware.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-45788 · Source: NVD

Affected components

ComponentCPEVersion range
Schneider Electric EcoStruxure Control Expertcpe:2.3:a:schneider-electric:ecostruxure_control_expert:*:*:*:*:*:*:*:*Before V15.3; fixed in V15.3 (SEVD-2023-010-05). NVD CPE has no version limit
Schneider Electric EcoStruxure Process Expertcpe:2.3:a:schneider-electric:ecostruxure_process_expert:*:*:*:*:*:*:*:*All versions; Schneider lists no fix as of 2026-11-20 (SEVD-2023-010-05 v6.0.0). NVD CPE ends before 2021
Schneider Electric Modicon M580 CPU (BMEP*, BMEH*, excluding M580 CPU Safety)cpe:2.3:o:schneider-electric:modicon_m580_bmep582040_firmware:-:*:*:*:*:*:*:*Before SV4.10; fixed in SV4.10 (SEVD-2023-010-05)
Schneider Electric Modicon M580 CPU Safety (BMEP58*S, BMEH58*S)cpe:2.3:o:schneider-electric:modicon_m580_bmep582040s_firmware:-:*:*:*:*:*:*:*Before SV4.21; fixed in SV4.21, needs Control Expert V16.0 HF001 or later (SEVD-2023-010-05)
Schneider Electric Modicon M340 CPU (BMXP34*)cpe:2.3:o:schneider-electric:modicon_m340_bmxp342020_firmware:-:*:*:*:*:*:*:*Before SV3.51; fixed in SV3.51 (SEVD-2023-010-05)
Schneider Electric Modicon Momentum Unity M1E Processor (171CBU*)cpe:2.3:o:schneider-electric:modicon_momentum_171cbu98091_firmware:-:*:*:*:*:*:*:*Before SV2.6; fixed in SV2.6 (SEVD-2023-010-05)
Schneider Electric Modicon MC80 (BMKC80*)cpe:2.3:o:schneider-electric:modicon_mc80_bmkc8020301_firmware:-:*:*:*:*:*:*:*Before SV1.90; fixed in SV1.90 (SEVD-2023-010-05)
Schneider Electric legacy Modicon Quantum (140CPU65*) and Premium (TSXP57*) CPUscpe:2.3:o:schneider-electric:modicon_quantum_140cpu65150_firmware:-:*:*:*:*:*:*:*All versions; end of life, no fix, mitigations only (SEVD-2023-010-05)

What does this mean for affected devices?

NVD carries the Schneider Electric description: "A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller." NVD's Primary score is CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). The record was published on 2023-01-30 (NVD, CVE record).

Why is NVD's score so much higher than Schneider's?

Schneider scores it 7.5 (CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H) in SEVD-2023-010-05: attack complexity high and user interaction required, because someone has to load the malicious project onto the controller. NVD scores the same impact with low complexity and no interaction, which gives 9.8. Both agree that a successful attack means code execution on the PLC with full loss of confidentiality, integrity and availability. The notice credits Jos Wetzels and Daniel dos Santos of Forescout Technologies.

Which products are affected and which versions fix them?

Product (Schneider wording) Affected Fix
EcoStruxure Control Expert before V15.3 V15.3
EcoStruxure Process Expert all versions none listed; mitigations only
Modicon M580 CPU (BMEP*, BMEH*, excl. Safety) before SV4.10 SV4.10
Modicon M580 CPU Safety (BMEP58S, BMEH58S) before SV4.21 SV4.21 (needs Control Expert V16.0 HF001)
Modicon M340 CPU (BMXP34*) before SV3.51 SV3.51
Modicon Momentum Unity M1E (171CBU*) before SV2.6 SV2.6
Modicon MC80 (BMKC80*) before SV1.90 SV1.90
Legacy Modicon Quantum (140CPU65*) and Premium (TSXP57*) all versions none; end of life

The table follows SEVD-2023-010-05 version 6.0.0 (13 August 2024). Version 5.0.0 (8 August 2023) extended the Process Expert row to all versions; NVD's CPE still ends Process Expert before 2021 and lists Control Expert with no version limit.

How do you mitigate it?

Update Control Expert and the controller firmware together. Where you cannot, Schneider's mitigations for the controllers are to set an application password in the project, block unauthorized access to 502/tcp with segmentation and a firewall, configure the Access Control List, protect the link to the engineering workstation with IPsec (BMENOC or BMENUA0100 modules on the M580) or a VPN, and enable CPU memory protection through a physical input. For the engineering side, Schneider recommends the project file encryption feature, encrypted storage with restricted access, opening project files only from trusted sources and checking a hash of each project file before use. Quantum and Premium are end of life; Schneider recommends the M580 as replacement.

Our Modicon UMAS protocol guide lists this CVE with the other Modicon notices. Related Modicon pages are CVE-2022-45789, CVE-2021-22779, CVE-2019-6808 and CVE-2019-6828.

CVE-2022-45788 is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.0118, the 68.4th percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-20): status Modified; published 2023-01-30; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; Schneider Secondary 7.5 CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H; CWE-754 (Schneider); CPE Control Expert without version limit, Process Expert before 2021, M340, M580, Momentum, MC80, Quantum and Premium part numbers; reference SEVD-2023-010-05. — NVD
  • Schneider SEVD-2023-010-05 v6.0.0 (published 2023-01-10, updated 2024-08-13), read 2026-11-20: CVE-2022-45788 CVSS v3.1 7.5, CWE-754, malicious project file loaded onto the controller; affected Control Expert before V15.3, Process Expert all versions, M340 before SV3.51, M580 before SV4.10, M580 CPU Safety before SV4.21, Momentum before SV2.6, MC80 before SV1.90, Quantum 140CPU65* and Premium TSXP57* all versions; fixes Control Expert V15.3, M580 SV4.10, M580 Safety SV4.21 (Control Expert V16.0 HF001 minimum), M340 SV3.51, Momentum SV2.6, MC80 SV1.90; mitigations listed; v5.0.0 (2023-08-08) all Process Expert versions affected; credits Jos Wetzels and Daniel dos Santos, Forescout Technologies. — Schneider Electric SEVD-2023-010-05
  • CVE record (checked 2026-11-20): state PUBLISHED, CNA Schneider Electric, published 2023-01-30; CNA CVSS v3.1 7.5, CWE-754; affected Control Expert, Process Expert, M340, M580, M580 Safety, Momentum, MC80, legacy Quantum and Premium, all versions at publication. — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries, released 2026-11-18), checked 2026-11-20. — CISA KEV
  • EPSS 0.0118, percentile 0.68356, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2023-010-05: EcoStruxure Control Expert, Process Expert and Modicon PLCs and PACs (PDF)
  3. CVE.org record CVE-2022-45788 (CNA: Schneider Electric)
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Do I need to update the software, the PLC or both?

Both. SEVD-2023-010-05 fixes EcoStruxure Control Expert in V15.3 and the controllers in M580 SV4.10, M580 CPU Safety SV4.21, M340 SV3.51, Momentum SV2.6 and MC80 SV1.90. The M580 CPU Safety firmware needs Control Expert V16.0 HF001 or later to connect.

How does an attacker get a malicious project onto the PLC?

The flaw triggers when a malicious project file is loaded onto the controller, which is why Schneider scores it with user interaction. Its mitigations therefore cover both the project files (encryption, trusted sources, hash checks) and the network path to the controller (application password, 502/tcp firewall, IPsec or VPN).

Is EcoStruxure Process Expert fixed?

No fix is listed. Version 6.0.0 of SEVD-2023-010-05 lists all Process Expert versions as affected, with mitigations only: a VPN to the controllers, encrypted project storage with restricted access, trusted sources only and hash checks of project files. Status as of 2026-11-20.

What about Modicon Quantum and Premium?

Legacy Quantum 140CPU65* and Premium TSXP57* CPUs are affected in all versions and receive no fix because they are end of life. Schneider recommends network mitigations such as blocking 502/tcp and the Access Control List, and migration to the Modicon M580.