Security Advisory

CVE-2023-30765: Delta InfraSuite Privilege Escalation

Last updated:
  • CVE-2023-30765

CVE-2023-30765 is an improper access control flaw in Delta Electronics InfraSuite Device Master before version 1.0.7. An attacker can change the product's privilege management configuration and so raise their own privileges. NVD scores it 9.8; CISA, which assumes the attacker already holds a low-privileged account, scores 8.8. Delta fixed it in 1.0.7, and later advisories require 1.0.13.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-30765 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Delta Electronics InfraSuite Device Mastercpe:2.3:a:deltaww:infrasuite_device_master:*:*:*:*:*:*:*:*Before 1.0.7 (CISA ICSA-23-180-01, NVD, CVE record); fixed in 1.0.7; later advisories require 1.0.13 or later

What does this mean for affected devices?

CISA's ICSA-23-180-01, published on 29 June 2023, says InfraSuite Device Master "versions prior to 1.0.7 contain improper access controls that could allow an attacker to alter privilege management configurations, resulting in privilege escalation." The weakness is CWE-269, improper privilege management. The NVD record was published on 2023-07-10 (NVD).

Why do NVD and CISA score it differently?

NVD's Primary score is CVSS v3.1 9.8, CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with no privileges required. CISA ICS, the CNA, scores 8.8, CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H. The Zero Day Initiative's ZDI-23-905 of 10 July 2023 agrees with CISA: "Authentication is required to exploit this vulnerability", and it places the flaw in the modifyusergroup endpoint. ZDI credits Piotr Bazydlo of Trend Micro's Zero Day Initiative. In practice, any account on the server, including one obtained through another flaw, can become an administrator. NVD's CPE data covers versions before 1.0.7.

Which other flaws are in the same advisory?

ICSA-23-180-01 covers three InfraSuite Device Master flaws: this one, a patch bypass that lets an attacker retrieve file contents (CVE-2023-34316), and the deserialization flaw CVE-2023-34347. CISA's risk summary says they "could allow an attacker to escalate privileges or remotely execute arbitrary code."

How do you fix it?

CISA's remediation is "Delta Electronics InfraSuite Device Master: Update to v1.0.7". Version 1.0.7 was in turn affected by CVE-2023-47207, for which CISA's ICSA-23-331-01 recommends 1.0.10 or later, and ICSA-24-303-03 sets 1.0.13 as the fix for a further flaw. Install 1.0.13 or later, review the user groups and privilege settings for changes you did not make, and keep the server off the internet and behind a firewall. Older builds also carry the deserialization flaws CVE-2022-41779 and CVE-2022-41778.

The Delta Electronics guide compares the InfraSuite Device Master advisories and their fix versions, and the guide to OT/ICS security for small manufacturers covers the account and network separation that limits privilege escalation.

CVE-2023-30765 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.01271, the 69.9th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): published 2023-07-10; status Modified; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CISA ICS (CNA) Secondary 8.8 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; CWE-269 (CISA ICS); CPE deltaww infrasuite_device_master versionEndExcluding 1.0.7. — NVD
  • ICSA-23-180-01 (2023-06-29): InfraSuite Device Master < 1.0.7; CVE-2023-30765 CWE-269, CVSS v3 8.8; remediation update to v1.0.7; reported by Piotr Bazydlo (Trend Micro ZDI). — CISA CSAF
  • ZDI-23-905 (ZDI-CAN-20911), published 2023-07-10: InfraSuite Device Master modifyusergroup improper access control privilege escalation, authentication required, CVSS 8.8 AV:N/AC:L/PR:L/UI:N, reported 2023-05-03, credit Piotr Bazydlo. — Zero Day Initiative
  • Later CISA InfraSuite advisories (CSAF): ICSA-23-331-01 (affects <= 1.0.7) recommends v1.0.10 or later; ICSA-24-303-03 fixed by 1.0.13 released October 2024. — CISA CSAF
  • CVE record (checked 2026-11-28): PUBLISHED, CNA icscert, published 2023-07-10; affected before v1.0.7; solution update to v1.0.7. — CVE Program
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.01271, percentile 0.69892, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-23-180-01: Delta Electronics InfraSuite Device Master (CSAF)
  3. Zero Day Initiative ZDI-23-905: InfraSuite Device Master modifyusergroup improper access control
  4. CISA ICSA-24-303-03: Delta Electronics InfraSuite Device Master (CSAF)
  5. CVE Program record CVE-2023-30765 (CNA: CISA ICS)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which InfraSuite Device Master version fixes CVE-2023-30765?

Version 1.0.7 (CISA ICSA-23-180-01). Later CISA advisories require 1.0.10 and then 1.0.13, so install 1.0.13 or later.

Does an attacker need an account?

CISA and ZDI say yes: a low-privileged authenticated user can change privilege settings. NVD's vector assumes no privileges, which is why its score is 9.8 rather than 8.8.

What should I check after updating?

Review InfraSuite Device Master user groups and privilege settings for changes you did not make, and remove accounts that are not needed.

Is CVE-2023-30765 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27). FIRST EPSS gives it 0.01271, the 69.9th percentile, in the 2026-11-27 dataset.