Delta Electronics' published vulnerabilities fall into two groups: server software that listens on the network, chiefly the DIAEnergie energy management application and InfraSuite Device Master, and engineering tools that open project files, chiefly DOPSoft, DIAScreen, CNCSoft, ISPSoft and WPLSoft. The server flaws are unauthenticated SQL injection, deserialization and authentication bypass scored up to 9.8; the tool flaws are memory corruption triggered by a crafted file. Newer advisories add PLC firmware: the DVP12SE accepts Modbus TCP commands without authentication and had no fix when published. As of 2026-11-23, one Delta CVE is in CISA's KEV catalog: CVE-2021-38406 in the end-of-life DOPSoft 2.
Key takeaways
- The split matters for prioritization.
- Only three port numbers appear in the sources: UDP 10100, TCP 928 and TCP 502.
- DIAEnergie has the longest advisory history of any Delta product, and the pattern repeats: SQL injection in web handlers, authentication or authorization bypass, and file upload or path traversal.
- InfraSuite Device Master is a .NET server whose services accept serialized objects from the network.
Where do Delta DIAEnergie, PLCs and HMI tools sit in OT networks?
CISA lists the sectors per advisory: critical manufacturing for the DIAEnergie, DOPSoft 2, ISPSoft and DVP12SE advisories, energy for both DIAScreen advisories, three of the five InfraSuite Device Master advisories and the 2023 DOPSoft advisory ICSA-23-334-01, and both sectors for CNCSoft-G2. Every advisory lists worldwide deployment and a headquarters in Taiwan. The products named in Delta and CISA advisories fall into four groups:
| Group | Products named in advisories | Typical place in the network |
|---|---|---|
| Plant servers | DIAEnergie; InfraSuite Device Master | Windows hosts at the supervisory level that collect data from field devices and serve web pages and APIs to users |
| HMI and CNC editors | DOPSoft and DOPSoft 2 (end-of-life), DIAScreen in DIAStudio, CNCSoft, CNCSoft-B and CNCSoft-G2 | Engineering workstations that build screens for Delta HMI panels and CNC controllers |
| PLC engineering tools | ISPSoft, WPLSoft | Engineering workstations and laptops that open and download PLC projects |
| Controllers | DVP12SE, DVP15MC11T, AS320T | Control level, on the cell or machine network, reached over Modbus TCP and web services |
The split matters for prioritization. A flaw in DIAEnergie or InfraSuite Device Master can be reached by anyone who can open a connection to the server, so its exposure depends on where the server sits in the Purdue model and what reaches it from the business network. A flaw in DOPSoft or ISPSoft needs a user to open a malicious file; CISA's 2024 CNCSoft-G2 and DIAScreen advisories say those vulnerabilities are not exploitable remotely. The risk there is the path by which project files arrive on an engineering laptop, which is how CVE-2021-38406 ended up in KEV.
How are Delta servers, HMIs and PLCs managed?
The management paths that advisories name are also the attack paths:
| Path | Products | What the sources say |
|---|---|---|
| Web application (.ashx and .aspx handlers) | DIAEnergie | Most DIAEnergie CVEs are SQL injection in named handlers such as Handler_CFG.ashx and AM_RegReport.aspx; CISA's ICSA-21-238-03 says the web application runs on HTTP by default |
| CEBC.exe service | DIAEnergie | Tenable's TRA-2024-13 says CEBC.exe listens on TCP port 928 and processes remote messages without authentication |
| Device-status, Device-Gateway and Device-DataCollect services | InfraSuite Device Master | CISA's ICSA-23-080-02 says Device-status listens on UDP port 10100 by default; the other two are named without ports |
| Modbus TCP | DVP12SE, DVP15MC11T | CISA's ICSA-26-181-07 names TCP/502 for the DVP12SE; Delta's DVP15MC11T advisory names Modbus/TCP |
| Web service | AS320T | Delta-PCSA-2026-00006 names the GET/PUT request handler of the web service |
| Project files | DOPSoft, DIAScreen, CNCSoft, ISPSoft, WPLSoft | Crafted project files (DPA files for DIAScreen, DVP files for WPLSoft, CBDGL files for ISPSoft) trigger memory corruption |
Only three port numbers appear in the sources: UDP 10100, TCP 928 and TCP 502. Confirm the rest from the installation or a capture. The BOD 23-02 guide on internet-exposed management interfaces explains how to check exposure from outside instead of trusting the firewall rules.
Which DIAEnergie vulnerabilities matter?
DIAEnergie has the longest advisory history of any Delta product, and the pattern repeats: SQL injection in web handlers, authentication or authorization bypass, and file upload or path traversal.
| CVE | Flaw, per the advisory | Affected and fixed | Scores |
|---|---|---|---|
| CVE-2021-32967 | Add a new administrative user without authentication (CWE-288) | 1.7.5 and prior; CISA: upgrade to 1.9 or later | CISA 9.8, NVD 9.8 |
| CVE-2021-32955 | Unrestricted file upload leading to remote code execution (CWE-434) | 1.7.5 and prior; 1.9 or later | CISA 9.8, NVD 9.8 |
| CVE-2021-32983 | Unauthenticated blind SQL injection in /DataHandler/Handler_CFG.ashx, parameter keyword | 1.7.5 and prior; 1.9 or later | CISA 9.8, NVD 9.8 |
| CVE-2022-1374 | Blind SQL injection in DIAE_unHandler.ashx, one of 26 such flaws in the 2022 advisory | Before 1.8.02.004 per the CVE record; CISA: 1.9 or later | CISA 9.8, NVD 9.8 |
| CVE-2022-41775 | SQL injection in Handler_CFG.ashx by a low-privileged authenticated user | Before 1.9.02.001 | CISA 8.8, NVD 8.8 |
| CVE-2023-0822 | Improper authorization that lets an unauthorized user reach privileged functions | Before 1.9.03.001 | CISA 8.8, NVD 8.8 |
| CVE-2024-4548 | Unauthenticated SQL injection in the 'RecalculateHDMWYC' message to CEBC.exe on TCP 928 | 1.10.1.8610 and prior; Tenable: v1.10.01.004 | Tenable 9.8; no NVD score |
| CVE-2024-43699 | Unauthenticated SQL injection in AM_RegReport.aspx that can read records | Up to v1.10.01.008; CISA: v1.10.01.009 | CISA 9.8 (v3.1) and 9.3 (v4), NVD 9.8 |
| CVE-2024-42417 | Authenticated SQL injection in Handler_CFG.ashx that can delay the product | Up to v1.10.01.008; v1.10.01.009 | CISA 8.8 (v3.1) and 8.7 (v4), NVD 8.8 |
| CVE-2026-78308 | Improper authentication allowing authentication bypass (CWE-287) | Before v1.11.00.022 | Delta 9.8; no NVD score |
The 2021 set comes from CISA's ICSA-21-238-03, first published on 26 August 2021 and last updated on 22 March 2022 (Update C). Its risk summary is blunt: an attacker could retrieve passwords in cleartext, execute code remotely or log in with administrative privileges. The 2022 set, ICSA-22-081-01 (22 March 2022, Update C on 28 April 2022), adds 26 blind SQL injections, a path traversal, and an incorrect default permission that CISA says combines with a DLL hijacking flaw to escalate privileges; CISA says each SQL injection lets an attacker "retrieve and modify database contents, and execute system commands". ICSA-22-298-06 (10 November 2022, updated 16 February 2023) moves to authenticated SQL injection and stored cross-site scripting, and CISA notes that Delta did not publicly release v1.9.01.002, v1.9.02.001 and v1.9.03.001; users had to ask Delta for them.
Tenable's TRA-2024-13 of 6 May 2024 is the clearest view of the network side. It says CEBC.exe listens on TCP port 928 and accepts remote messages; CVE-2024-4547 and CVE-2024-4548 are SQL injection in two message types, and CVE-2024-4549 is a denial of service in which an 'ICS Restart!' message makes CEBC.exe restart the system. Tenable gives the fix as DIAEnergie v1.10.01.004 or later, obtained through sales representatives. NVD has no Primary score for CVE-2024-4548 or CVE-2024-4549 as of 2026-11-23.
The newest advisory is Delta-PCSA-2026-00014 of 18 September 2026. It lists six CVEs in versions before v1.11.00.022: improper authentication (CVE-2026-78308, 9.8), two SQL injections (8.8 each), a path traversal (9.1), an authorization bypass through a user-controlled key (4.3) and an improper access control flaw (6.5), all CVSS v3.1 scores from Delta. The fix is v1.11.00.022 from Delta technical support. Delta credits Alex Williams of Pellera Technologies, with coordination by VulnCheck. As of 2026-11-23, NVD lists CVE-2026-78308 as Deferred with only Delta's score.
What do the InfraSuite Device Master advisories show?
InfraSuite Device Master is a .NET server whose services accept serialized objects from the network. Five CISA advisories between 2022 and 2024 follow each other, and each one lists the previous advisory's fixed version, or versions shortly after it, as affected:
| CISA advisory | Affected | Fix | CVEs cited here |
|---|---|---|---|
| ICSA-22-298-07 (25 October 2022, updated 18 January 2023) | 00.00.01a and prior | Uninstall and reinstall 1.0.3 | CVE-2022-41778: deserialization through the Device-DataCollect service port (CISA 9.8, NVD 8.8); CVE-2022-41779: deserialization of packets when the product connects to an attacker-controlled server (CISA 8.8, NVD 9.8) |
| ICSA-23-080-02 (29 March 2023) | Before 1.0.5 | Uninstall and reinstall 1.0.5 | CVE-2023-1133: Device-status service on UDP 10100 deserializes unverified packets (CISA 9.8, NVD 9.8); CVE-2023-1140: unauthenticated remote code execution as administrator (CISA 9.8, NVD 9.8) |
| ICSA-23-180-01 (29 June 2023) | Before 1.0.7 | 1.0.7 | CVE-2023-30765: privilege management configuration can be altered (CISA 8.8, NVD 9.8) |
| ICSA-23-331-01 (28 November 2023, updated 6 May 2025) | 1.0.7 | 1.0.10 or later | CVE-2023-47207: unauthenticated code execution with local administrator privileges (CISA 9.8, NVD 9.8) |
| ICSA-24-303-03 (29 October 2024) | Before 1.0.12 | 1.0.13, released October 2024 | CVE-2024-10456: deserialization of arbitrary .NET objects in the Device-Gateway before authentication (CISA 9.8 v3.1 and 9.3 v4; no NVD score) |
The 2023 advisories also list a token-generation authentication bypass, command injection, Lua script execution and a flaw that runs code through a single UDP packet. CISA and NVD disagree on three scores in this table, in both directions, so record which scorer you use. The CVE record for CVE-2024-10456 lists versions up to and including 1.0.12 as affected while CISA says "prior to 1.0.12"; treat 1.0.13 as the first fixed release, as CISA does. The path traversal guide covers the .ZIP and file-path issues that appear alongside the deserialization flaws.
Which DOPSoft, DIAScreen and CNCSoft flaws are published?
These are file-parsing bugs: an attacker builds a project or screen file that overflows a buffer when an engineer opens it, and the code runs as that user.
| CVE | Product and flaw | Affected and fixed | Scores |
|---|---|---|---|
| CVE-2021-38406 | DOPSoft 2, out-of-bounds write parsing project files | 2.00.07 and prior; no fix, end-of-life | CISA 7.8, NVD 7.8; in KEV |
| CVE-2021-38404 | DOPSoft 2, heap-based buffer overflow parsing project files | 2.00.07 and prior; no fix | CISA 7.8, NVD 7.8 |
| CVE-2023-0123 | DOPSoft, stack-based buffer overflow from a malformed file | 4.00.16.22 and prior; CISA: use DIAScreen 1.3.0 | CISA 7.8, NVD 7.8 |
| CVE-2023-5944 | DOPSoft, stack-based buffer overflow from a crafted file | All versions; DOPSoft end-of-life, use DIAScreen v1.3.1 or newer | CISA 7.8, NVD 7.8 |
| CVE-2023-0249 | DIAScreen, out-of-bounds write | 1.2.1.23 and prior; 1.3.0 | CISA 7.8, NVD 7.8 |
| CVE-2024-7502 | DIAScreen, stack-based overflow from a crafted DPA file | Before 1.4.2; 1.4.2 | CISA 7.8 (v3.1) and 8.5 (v4), NVD 7.8 |
| CVE-2025-59297 | DIAScreen, out-of-bounds write from a malicious file | Before v1.6.1; v1.6.1 or later | Delta 6.8 (v4), NVD 7.8 |
| CVE-2024-39880 | CNCSoft-G2, stack-based buffer overflow | 2.0.0.5 per the CVE record; CISA: v2.1.0.20 or later | CISA 7.8 (v3.1) and 8.4 (v4), NVD 8.8 |
| CVE-2025-47728 | CNCSoft-G2, out-of-bounds write from a malicious file | V2.1.0.20 and prior; v2.1.0.27 or later | Delta 7.3 (v4), NVD 7.3 |
| CVE-2026-3094 | CNCSoft-G2, out-of-bounds write from a malicious file | V2.1.0.34 and prior; v2.1.0.39 or later | Delta 7.8; no NVD score |
DOPSoft 2 is the KEV entry. CISA's ICSA-21-252-02 of 9 September 2021 says it "will not receive an update" because it is end-of-life and recommends moving HMI devices to the DOP-100 family and the software to DIAScreen in DIAStudio v1.1.2 or later. CISA added CVE-2021-38406 to KEV on 25 August 2022 with the required action "The impacted product is end-of-life and should be disconnected if still in use." DOPSoft (version 4) followed DOPSoft 2 into end-of-life, per ICSA-23-334-01.
CNCSoft-G2 shows how quickly these fixes are overtaken. CISA's ICSA-24-191-01 was updated on 18 February 2025 to add CVE-2025-22880 and raise the fix to v2.1.0.20; Delta-PCSA-2025-00007 then listed v2.1.0.20 and prior as affected by CVE-2025-47728 (fix v2.1.0.27), and Delta-PCSA-2026-00004 lists V2.1.0.34 and prior for CVE-2026-3094 (fix v2.1.0.39). The memory corruption guide explains why these parser bugs are so common and what fixes them for good.
What about ISPSoft and WPLSoft?
ISPSoft and WPLSoft open PLC project files, and both have file-parsing CVEs:
- CVE-2020-27280, ISPSoft v3.12 and prior: a use-after-free when processing project files. CISA's ICSA-21-021-01 of 21 January 2021 recommends v3.12.01, obtained from Delta customer service. CISA and NVD score it 7.8.
- CVE-2025-22882, ISPSoft v3.20 and prior: a stack-based buffer overflow when parsing a CBDGL file. Delta-PCSA-2025-00004 lists it with four other stack overflow and out-of-bounds write CVEs and fixes all five in v3.21. Delta scores it 7.8 with a local, user-interaction vector and NVD 9.8 with a network vector and no user interaction (both CVSS v3.1).
- CVE-2023-5130, WPLSoft: a buffer overflow when a user opens a crafted DVP file. The CVE record names version 2.42.11. Exodus Intelligence's advisory of 18 January 2024 says the product is end-of-life and no patches are available. Exodus scores it 8.2 and NVD 8.8.
On an engineering laptop that also holds remote-access tools, a file-parsing bug becomes a path to every PLC that laptop can program, so these tools belong in the asset list with the PLCs.
Which Delta PLC firmware vulnerabilities are published?
PLC firmware CVEs appear only in Delta's own advisories from 2025 on, plus one CISA advisory:
| CVE | Product and flaw | Affected and fixed | Scores |
|---|---|---|---|
| CVE-2026-12819 | DVP12SE, Modbus TCP service without authentication or access control (CWE-306) | All versions; no fix at publication | Delta and CISA 9.8 (v3.1), 9.3 (v4); no NVD score |
| CVE-2026-12818 | DVP12SE, no limit on resource allocation when TCP/502 is flooded (CWE-770) | All versions; no fix at publication | Delta and CISA 9.8 (v3.1), 9.3 (v4); no NVD score |
| CVE-2026-1949 | AS320T, incorrect buffer size calculation on the stack in the web service's GET/PUT request handler (CWE-131) | v1.14 and prior; v1.16 or later | Delta 9.8; no NVD score |
| CVE-2026-1952 | AS320T, denial of service through an undocumented subfunction (CWE-912) | v1.14 and prior; v1.16 or later | Delta 9.8, NVD 7.5 |
| CVE-2025-59301 | DVP15MC11T, improper validation of Modbus/TCP packets leading to denial of service | Before v1.16.0; v1.16.0 or later | Delta 4.0, NVD 7.5 |
CISA's ICSA-26-181-07 of 30 June 2026 says exploitation of the DVP12SE flaws "could allow an attacker to remotely issue commands, modify operational values, interfere with control logic, and alter device behavior without authentication or privilege enforcement." That is Modbus as designed: the Modbus protocol guide explains why a Modbus TCP server has no authentication of its own. Delta's mitigations for the DVP12SE are the PLC's IP Filter restricted to trusted HMI and SCADA addresses, PLC password protection set in the programming software, and network isolation behind a firewall with VPN for remote access.
Delta-PCSA-2026-00006 for the AS320T splits the fix: CVE-2026-1949, CVE-2026-1950 and CVE-2026-1952 affect v1.14 and prior and are fixed in v1.16, while the stack overflow on directory names, CVE-2026-1951, affects v1.10 and prior and is fixed in v1.12. Note how far apart the scores are: Delta rates CVE-2025-59301 at 4.0 and CVE-2026-1952 at 9.8, while NVD rates both 7.5.
Are Delta Electronics vulnerabilities exploited in the wild?
As of 2026-11-23, CISA's KEV catalog (version 2026.11.20, 1,790 entries) has one Delta entry, CVE-2021-38406 in DOPSoft 2. CISA's Delta advisories from ICSA-23-331-01 (November 2023) on say no known public exploitation specifically targeting the vulnerabilities has been reported to CISA, including the DVP12SE advisory of June 2026.
FIRST EPSS scores (data dated 2026-11-22, retrieved 2026-11-23) put the network-facing server flaws near the top:
| CVE | Product | EPSS | Percentile |
|---|---|---|---|
| CVE-2021-38406 | DOPSoft 2 (KEV) | 0.76428 | 99.5th |
| CVE-2023-1133 | InfraSuite Device Master | 0.50050 | 98.9th |
| CVE-2021-32955 | DIAEnergie | 0.37319 | 98.6th |
| CVE-2024-4548 | DIAEnergie | 0.29425 | 98.2nd |
| CVE-2024-10456 | InfraSuite Device Master | 0.17589 | 97.2nd |
| CVE-2023-47207 | InfraSuite Device Master | 0.16573 | 97.1st |
Every other CVE in this guide scores below 0.08. The PLC CVEs all score below 0.01, but that reflects their age and exposure, not their impact. The KEV and EPSS prioritization guide explains how to combine the two.
How should Delta systems be hardened?
Delta's general recommendations, printed in each PCSA advisory cited here, are: do not click untrusted links or open unsolicited attachments; avoid exposing control systems to the Internet; place systems behind a firewall and isolate them from the business network; and use a secure method such as a VPN when remote access is required. CISA adds the same isolation advice in its advisories. In practice:
Update DIAEnergie to v1.11.00.022 or laterthrough Delta technical support, and keep its web interface and TCP 928 off the business network. The fixes are not all in the public download center. Update InfraSuite Device Master to 1.0.13 or laterand block UDP 10100 and the Device-Gateway and Device-DataCollect services from anything that does not need them. Retire DOPSoft 2, DOPSoft and WPLSoftCISA's KEV action for DOPSoft 2 is to disconnect it. Move HMI projects to DIAScreen v1.6.1 or later. Keep the engineering tools current: ISPSoft v3.21, CNCSoft-G2 v2.1.0.39 and DIAScreen v1.6.1 or later, and only open project files from trusted sources. Restrict Modbus TCP to the PLCsFor the DVP12SE, enable the IP Filter and a PLC password until Delta ships firmware; update the DVP15MC11T to v1.16.0 and the AS320T to v1.16. Change passwords after upgradingDIAEnergie and InfraSuite Device Master: CISA's 2021 DIAEnergie advisory and ICSA-23-080-02 list flaws that expose passwords or plaintext administrator credentials, so assume old credentials are known. The hard-coded credentials guide covers how to handle stored and default credentials.
How do you check which Delta versions you run?
Version numbers come from the software itself, not from the network. Read the About dialog or the installed-programs list on each server and engineering workstation for DIAEnergie, InfraSuite Device Master, DIAScreen, CNCSoft-G2 and ISPSoft, and read PLC firmware versions through the programming software. Watch for formatting differences between sources: Tenable writes the affected DIAEnergie build as v1.10.1.8610 and the fix as v1.10.01.004, while CISA writes v1.10.01.008 and v1.10.01.009, so compare the full build number with the advisory you are applying. NVD has no Primary score for CVE-2024-4548, CVE-2024-10456, CVE-2026-1949, CVE-2026-3094, CVE-2026-12818, CVE-2026-12819 or CVE-2026-78308 as of 2026-11-23, so a scanner that relies on NVD CPE data alone can miss them.
Where does passive monitoring fit in a Delta review?
A passive capture shows who talks to servers, PLCs and HMIs without logging in to anything. SoftWSP's OT Snapshot reads Zeek and ICSNPP logs from a mirror-port recording and builds a host-by-port inventory at connection level, including hosts using TCP 502, TCP 928, UDP 10100 and web ports, and lists remote-access sessions that cross from outside the private address range. It does not read Delta software or firmware versions from traffic, so those come from the asset list. For that list, Device & Firmware Security identifies components and versions and matches them against NVD, CISA KEV, FIRST EPSS and CISA ICS advisories. An engineer reviews every AI-drafted, cited report before it is sent.
Flow records show who connected to which port and when, not which Modbus function was used. Map what you find to MITRE ATT&CK for ICS techniques such as exploitation of remote services, user execution and modification of parameters.
Worked example: what does a review of a packaging plant find?
Synthetic example, not a real site. A packaging plant runs DIAEnergie for energy metering, DVP12SE PLCs on its lines and DIAScreen and ISPSoft on two engineering laptops.
| Observation | Why it matters | Action |
|---|---|---|
| DIAEnergie v1.10.01.009 reachable from the office VLAN on HTTP and TCP 928 | CVE-2026-78308 and the 2026 SQL injections; TCP 928 is the CEBC.exe port | Request v1.11.00.022 from Delta; restrict both ports to the operator subnet |
| Three DVP12SE PLCs answering Modbus TCP to any host on the plant network | CVE-2026-12819 and CVE-2026-12818; no firmware fix | Enable the IP Filter for the HMI and SCADA addresses; set a PLC password |
| One laptop with DOPSoft 2 still installed for an old panel | CVE-2021-38406 is in KEV with "disconnect" as the action | Migrate the panel project to DIAScreen; remove DOPSoft 2 |
| ISPSoft 3.19 on both laptops | CVE-2025-22882 and four related CVEs | Update to v3.21 |
| InfraSuite Device Master 1.0.10 on a facilities server | CVE-2024-10456 affects versions before 1.0.12 | Update to 1.0.13; block UDP 10100 from the plant network |
What are the common pitfalls?
- Treating DIAEnergie fixes as downloadable: several releases were available only from Delta support or sales, per CISA and Tenable.
- Updating InfraSuite Device Master once and stopping: five CISA advisories in two years each superseded the previous fix.
- Leaving DOPSoft 2 on a laptop for one legacy panel; it is end-of-life and in KEV.
- Trusting one score: CISA gives CVE-2022-41778 9.8 where NVD gives 8.8, and Delta gives CVE-2025-22882 7.8 where NVD gives 9.8.
- Waiting for a DVP12SE firmware fix before acting, when the IP Filter and password are available now.
- Forgetting that project files are an attack path: an HMI or PLC project from a contractor is input to a parser with a long CVE history.
This guide draws on Delta Electronics product cybersecurity advisories Delta-PCSA-2025-00004, 2025-00007, 2025-00018, 2025-00020, 2026-00004, 2026-00006, 2026-00011 and 2026-00014; CISA ICS advisories ICSA-21-021-01, ICSA-21-238-03, ICSA-21-252-02, ICSA-22-081-01, ICSA-22-298-06, ICSA-22-298-07, ICSA-23-031-01, ICSA-23-033-01, ICSA-23-080-02, ICSA-23-180-01, ICSA-23-331-01, ICSA-23-334-01, ICSA-24-191-01, ICSA-24-219-01, ICSA-24-277-03, ICSA-24-303-03 and ICSA-26-181-07 and their CSAF records; Tenable TRA-2024-13; Exodus Intelligence's WPLSoft advisory; CVE.org and NVD records; the CISA KEV catalog; and FIRST EPSS data. KEV and EPSS facts are as of 2026-11-23. It is general information, not a substitute for the vendor advisory or a check of your exact software and firmware versions.
Put this guide to work
Frequently asked questions
Is any Delta Electronics vulnerability in the CISA KEV catalog?
Yes, one. As of 2026-11-23, CISA's Known Exploited Vulnerabilities catalog (version 2026.11.20, 1,790 entries) lists CVE-2021-38406, an out-of-bounds write in the DOPSoft 2 HMI editor triggered by a crafted project file. CISA added it on 25 August 2022 with a due date of 15 September 2022 and the required action that the end-of-life product should be disconnected if still in use. Ransomware use is marked Unknown. No DIAEnergie, InfraSuite Device Master, PLC or other Delta CVE is in the catalog. CVE-2021-38406 also has the highest FIRST EPSS score among the Delta CVEs in this guide, 0.76428 (99.5th percentile).
Which DIAEnergie version fixes the published vulnerabilities?
The newest fix is DIAEnergie v1.11.00.022. Delta's advisory Delta-PCSA-2026-00014 of 18 September 2026 lists six CVEs in versions before v1.11.00.022, led by CVE-2026-78308, an improper authentication flaw Delta scores 9.8 (CVSS v3.1), and tells users to contact Delta technical support to obtain the update. Earlier fix levels were v1.10.01.004 for the CEBC.exe flaws Tenable reported in 2024, v1.10.01.009 for the SQL injections in CISA's ICSA-24-277-03, and v1.9.01.002, v1.9.02.001 and v1.9.03.001 for the 2022 and 2023 issues, which CISA says Delta did not release publicly. Each new advisory supersedes the last, so plan for the latest build.
Does the DVP12SE PLC have a firmware fix for its Modbus TCP flaws?
Not when Delta and CISA published. Delta-PCSA-2026-00011 and CISA's ICSA-26-181-07, both of 30 June 2026, list all DVP12SE versions as affected by CVE-2026-12818 (no limit on resources when the Modbus port is flooded) and CVE-2026-12819 (Modbus TCP commands accepted without authentication). CISA says Delta is working on a fix. The workarounds are to enable the PLC's IP Filter so that only trusted HMI panels or SCADA hosts can connect, to set PLC password protection in the programming software, and to keep the PLC on an isolated, firewalled control network reached remotely only over a VPN.
What should replace DOPSoft and DOPSoft 2?
DIAScreen. CISA's ICSA-21-252-02 says DOPSoft 2 is end-of-life and will not be fixed, and that Delta recommends moving HMI devices to the DOP-100 family and the software to DIAScreen in DIAStudio v1.1.2 or later. CISA's ICSA-23-334-01 says Delta declared DOPSoft end-of-life too and recommends DIAScreen v1.3.1 or newer. DIAScreen has its own file-parsing CVEs, so keep it current: Delta-PCSA-2025-00018 names v1.6.1 as the fix for CVE-2025-59297 and three related CVEs.
Which network ports do Delta advisories name?
Three, from three sources. CISA's ICSA-23-080-02 says the InfraSuite Device Master Device-status service listens on UDP port 10100 by default (CVE-2023-1133). Tenable's TRA-2024-13 says DIAEnergie's CEBC.exe listens on TCP port 928 (CVE-2024-4548 and CVE-2024-4549). CISA's ICSA-26-181-07 names the DVP12SE Modbus port as TCP/502 (CVE-2026-12818). The advisories name the InfraSuite Device-Gateway and Device-DataCollect services and the AS320T web service without port numbers, so confirm those from the installation or a capture.
Sources
- Delta Electronics: Product Cybersecurity Advisory
- Delta-PCSA-2026-00014: DIAEnergie Multiple Vulnerabilities (CVE-2026-78308 to 78313)
- Delta-PCSA-2026-00011: DVP12SE Multiple Vulnerabilities
- Delta-PCSA-2026-00006: AS320T Multiple Vulnerabilities
- Delta-PCSA-2026-00004: CNCSoft-G2 File Parsing Out-Of-Bounds Write
- Delta-PCSA-2025-00020: DVP15MC11T Modbus/TCP DoS Vulnerability
- Delta-PCSA-2025-00018: DIAScreen File Parsing Out-Of-Bounds Write Vulnerabilities
- Delta-PCSA-2025-00007: CNCSoft-G2 File Parsing Memory Corruption
- Delta-PCSA-2025-00004: ISPSoft Multiple Vulnerabilities
- CISA CSAF: ICSA-26-181-07 Delta Electronics DVP12SE PLC
- CISA CSAF: ICSA-24-303-03 Delta Electronics InfraSuite Device Master
- CISA CSAF: ICSA-24-277-03 Delta Electronics DIAEnergie
- CISA CSAF: ICSA-24-219-01 Delta Electronics DIAScreen
- CISA CSAF: ICSA-24-191-01 Delta Electronics CNCSoft-G2 (Update A)
- CISA CSAF: ICSA-23-334-01 Delta Electronics DOPSoft
- CISA CSAF: ICSA-23-331-01 Delta Electronics InfraSuite Device Master
- CISA CSAF: ICSA-23-180-01 Delta Electronics InfraSuite Device Master
- CISA CSAF: ICSA-23-080-02 Delta Electronics InfraSuite Device Master
- CISA CSAF: ICSA-23-033-01 Delta Electronics DIAScreen
- CISA CSAF: ICSA-23-031-01 Delta Electronics DOPSoft
- CISA CSAF: ICSA-22-298-07 Delta Electronics InfraSuite Device Master
- CISA CSAF: ICSA-22-298-06 Delta Electronics DIAEnergie
- CISA CSAF: ICSA-22-081-01 Delta Electronics DIAEnergie (Update C)
- CISA CSAF: ICSA-21-252-02 Delta Electronics DOPSoft 2
- CISA CSAF: ICSA-21-238-03 Delta Electronics DIAEnergie (Update C)
- CISA CSAF: ICSA-21-021-01 Delta Electronics ISPSoft
- Tenable TRA-2024-13: Delta Electronics DIAEnergie CEBC.exe Multiple Vulnerabilities
- Exodus Intelligence: Delta Electronics WPLSoft buffer overflow (CVE-2023-5130)
- NVD: CVE-2021-38406 (DOPSoft 2 out-of-bounds write)
- NVD: CVE-2023-1133 (InfraSuite Device Master Device-status deserialization)
- NVD: CVE-2021-32955 (DIAEnergie unrestricted file upload)
- NVD: CVE-2024-43699 (DIAEnergie unauthenticated SQL injection)
- NVD: CVE-2025-22882 (ISPSoft stack-based buffer overflow)
- CVE.org: CVE-2026-78308 (DIAEnergie improper authentication)
- CISA Known Exploited Vulnerabilities catalog
- FIRST: Exploit Prediction Scoring System (EPSS)
About this guide
SoftWSP OT/ICS Desk
Covers the OT/ICS security cluster: 91 guides.

In this cluster
Questions about this page?