CVE-2022-41778 is a deserialization flaw in Delta Electronics InfraSuite Device Master 00.00.01a and earlier. Data sent to the Device-DataCollect service port is deserialized without checks, so a malicious serialized object can run code on the server. NVD scores it 8.8 and CISA 9.8, and Delta's fix is a reinstall of version 1.0.3.
Vulnerability summary
CVSS base score
8.8
High severity
EPSS score (FIRST)
1.1%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2022-41778 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Delta Electronics InfraSuite Device Master | cpe:2.3:a:deltaww:infrasuite_device_master:*:*:*:*:*:*:*:* | 00.00.01a and prior (CVE record, NVD up to and including 00.00.01a); fixed by uninstalling and reinstalling 1.0.3 (CISA ICSA-22-298-07); later advisories name 1.0.5 and 1.0.10 for further flaws |
What does this mean for affected devices?
NVD carries the CISA description: InfraSuite Device Master versions 00.00.01a and prior "deserialize user-supplied data provided through the Device-DataCollect service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization." CISA maps it to CWE-502 (NVD, CVE record).
Why do NVD and CISA score it differently?
CISA, the CNA, scores CVSS v3.1 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), treating the attacker as unauthenticated. NVD's Primary score is 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) because it assumes the attacker needs low privileges. The description itself names no login step, and CISA's advisory says these flaws could let "an unauthenticated attacker" execute code with local administrator privileges, so plan around the 9.8 case. NVD's CPE covers versions up to and including 00.00.01a.
What does CISA's advisory cover?
CISA's ICSA-22-298-07 of 2022-10-25, updated on 2023-01-18, lists 10 flaws reported by kimiya of Trend Micro's Zero Day Initiative: deserialization in the Device-DataCollect and Device-Gateway service ports (this CVE and CVE-2022-38142), a deserialization reached when the product connects to an attacker-controlled server (CVE-2022-41779), path traversal, and missing authentication on backup, user group and configuration functions. Delta's fix is to uninstall old versions and reinstall version 1.0.3. The current CSAF file lists both 00.00.01a and earlier and 1.0.3 and earlier as affected, which does not match its own remediation; since later advisories found more flaws before 1.0.5 (CVE-2023-1133) and in 1.0.7 (CVE-2023-47207), install the newest release Delta offers. The Delta Electronics guide lists the InfraSuite advisories with their fixed versions.
CVE-2022-41778 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01118, the 66.9th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2023-01-13; NVD Primary CVSS v3.1 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; ICS-CERT Secondary 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CWE-502 (ICS-CERT); CPE deltaww infrasuite_device_master up to and including 00.00.01a. — NVD
- CISA ICSA-22-298-07 CSAF (released 2022-10-25, updated 2023-01-18), read 2026-11-23: products 'Version 00.00.01a and prior' and 'Version 1.0.3 and prior'; 10 CVEs including CVE-2022-41778 (CWE-502, 9.8, Device-DataCollect), CVE-2022-38142 (Device-Gateway), CVE-2022-41779 (8.8, attacker-controlled server); remediation uninstall old versions and reinstall 1.0.3; risk evaluation: unauthenticated attacker could execute code with local administrator privileges; reported by kimiya, Trend Micro ZDI. — CISA ICSA-22-298-07
- CVE record (checked 2026-11-23): state PUBLISHED, CNA ICS-CERT (icscert), published 2023-01-12, CNA CVSS v3.1 9.8, CWE-502, affected 0 to 00.00.01a. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.01118, percentile 0.66942, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Is CVE-2022-41778 rated 8.8 or 9.8?
Both. NVD's Primary CVSS v3.1 score is 8.8 because it assumes low privileges are needed; CISA, the CNA, scores 9.8 with no privileges required. CISA's advisory describes the attacker as unauthenticated.
How do I fix CVE-2022-41778?
Uninstall InfraSuite Device Master and reinstall version 1.0.3 or later (CISA ICSA-22-298-07). Later CISA advisories name 1.0.5 and 1.0.10 for further flaws, so install the newest release.
Which service is affected?
The Device-DataCollect service port. The same advisory lists a matching deserialization flaw in the Device-Gateway service port, CVE-2022-38142.
Is CVE-2022-41778 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.01118 (66.9th percentile) in the 2026-11-22 dataset.
Questions about this page?