CVE-2023-30897 is a local privilege escalation in Siemens SIMATIC WinCC V7: when WinCC is installed to a non-default folder, the installer does not set proper access rights on that folder, so an authenticated local user could place code there and escalate privileges. NVD and Siemens both score it CVSS 7.8. Siemens fixed it in WinCC V7.5.2.13 and advises using the default installation path.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
0.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-30897 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC WinCC V7 | cpe:2.3:a:siemens:wincc:*:*:*:*:*:*:*:* | All versions before V7.5.2.13 when installed to a non-default path; fixed in V7.5.2.13 or later (Siemens SSA-914026). NVD CPE: wincc versions before 7.5.2.13 |
What does this mean for affected devices?
NVD's description, from Siemens, reads: "Affected applications fail to set proper access rights for their installation folder if a non-default installation path was chosen during installation. This could allow an authenticated local attacker to inject arbitrary code and escalate privileges." It applies to SIMATIC WinCC before V7.5.2.13. NVD's Primary score is CVSS v3.1 7.8 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), the same vector Siemens submitted as CNA, with CWE-732 (incorrect permission assignment for a critical resource). NVD's CPE configuration lists the product as wincc with versions before 7.5.2.13 (NVD, CVE record).
What does Siemens say?
Siemens advisory SSA-914026 ("Local Code Execution Vulnerability in SIMATIC WinCC V7", V1.0, 2023-06-13) says WinCC V7 is affected "if a non-default installation path was chosen during installation". Its CVSS v3.1 score is 7.8 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C). The fix is to update to V7.5.2.13 or a later version. Siemens also lists three mitigations: harden the application server to prevent local access by untrusted personnel; after installing to a non-default folder, make sure that folder's access permissions equal those of the Program Files folder; and always use the default installation path when installing WinCC V7.
What does CISA say?
CISA advisory ICSA-23-166-07 (CSAF), "Siemens SIMATIC WinCC V7", republishes the 7.8 score, CWE-732, the V7.5.2.13 fix and the three mitigations.
How do I check a WinCC host?
- Find out where WinCC was installed on each server, client and engineering station. A host that used the default path is not exposed to this flaw, according to Siemens.
- On hosts with a custom path, update to V7.5.2.13 or later, and compare the folder's permissions with those of Program Files.
- Limit interactive logons on WinCC hosts to trusted operators and administrators.
The Siemens WinCC and PCS 7 guide lists this flaw under authentication and local hardening, and explains how Siemens writes WinCC V7 fix levels such as V7.5.2.13. CVE-2019-10918 is a network path to SYSTEM-level command execution on the same hosts, and CVE-2010-2772 is the oldest WinCC credential flaw. The KEV and EPSS prioritization guide explains how to rank a local flaw with a low EPSS score.
CVE-2023-30897 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.00224, a percentile of 7.6, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2023-06-13; NVD Primary CVSS v3.1 7.8 CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; Siemens Secondary 7.8 same vector; CWE-732; CPE cpe:2.3:a:siemens:wincc versions before 7.5.2.13. — NVD
- Siemens SSA-914026 CSAF V1.0, 2023-06-13 (read 2026-11-28): non-default installation path; CVSS v3.1 7.8 with E:P/RL:O/RC:C; fix V7.5.2.13 or later; mitigations harden server, match Program Files permissions, use default path. — Siemens ProductCERT SSA-914026
- CISA ICSA-23-166-07 CSAF (read 2026-11-28): CVSS v3.1 7.8, CWE-732, same fix and mitigations. — CISA ICSA-23-166-07
- CVE record (read 2026-11-28): state PUBLISHED, assigner siemens, CNA CVSS v3.1 7.8, CWE-732. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.00224, percentile 0.07646, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Is every WinCC V7 installation affected by CVE-2023-30897?
No. Siemens says the flaw applies if a non-default installation path was chosen during installation. Hosts installed to the default path do not have the weak folder permissions.
Which version fixes CVE-2023-30897?
Siemens SSA-914026 says to update SIMATIC WinCC to V7.5.2.13 or a later version.
What can be done without updating?
Siemens lists hardening the server against local access by untrusted personnel, setting the custom folder's permissions equal to those of Program Files, and using the default installation path for WinCC V7.
Is CVE-2023-30897 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.00224 (percentile 7.6) in the 2026-11-27 dataset.
Questions about this page?