CVE-2023-25915 is a remote command execution flaw in the Danfoss AK-SM 800A refrigeration system manager: improper input validation lets an authenticated attacker run arbitrary commands on the controller. NVD scores it 8.8 (DIVD 9.9) and CISA KEV lists it as exploited since 2026-11-25. Danfoss fixed it in software 3.3; install the current release.
Vulnerability summary
CVSS base score
8.8
High severity
EPSS score (FIRST)
1.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
Yes
Listed as known exploited
Published
Vulnerability ID: CVE-2023-25915 · Source: NVD (Primary CVSS v3.1)
Affected components
| Component | CPE | Version range |
|---|---|---|
| Danfoss AK-SM 800A system manager (all series) | cpe:2.3:o:danfoss:ak-sm_800a_firmware:*:*:*:*:*:*:*:* | Software before 3.3 (Danfoss DSA-2023-08-01); fixed in 3.3. NVD's CPE reads 'up to and including 3.3' |
What does this mean for affected devices?
The CVE record, published on 2023-08-21 by DIVD as CNA, says that "due to improper input validation, an authenticated remote attacker could execute arbitrary commands on the target system", the Danfoss AK-SM 800A. NVD's Primary CVSS v3.1 score is 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) with CWE "NVD-CWE-noinfo"; DIVD scores it 9.9 with a changed scope and CWE-20 (NVD, CVE record). The AK-SM 800A is the Danfoss system manager that runs refrigeration and HVAC control in supermarkets, so command execution on it reaches the store's cooling plant.
Which AK-SM 800A software is affected?
Danfoss advisory DSA-2023-08-01 covers "AK-SM 800A all Series with SW version below/before 3.3" and three CVEs: this remote command execution, the XML-interface path traversal CVE-2023-25914 and an information leak, CVE-2023-25913. Danfoss scores this one 9.8 and describes "a remote attacker" without mentioning a login, while the CVE record and NVD say the attacker must be authenticated. NVD's CPE configuration reads "up to and including 3.3"; Danfoss names 3.3 as the fixed release.
How do you fix it?
Danfoss says to "install the latest patch with number 3.3" from its AK-SM 800A software page and lists no other mitigation. Later Danfoss advisories fixed further AK-SM 8xxA flaws in releases 4.2 (CVE-2025-41450) and 4.3.1, so upgrade to the current release. DIVD's case DIVD-2023-00025 notes that it scanned for and notified owners of exposed units from September 2023. Keep the controller's web and XML interfaces reachable only from the service network or a VPN (BOD 23-02 guide), and change any shared service passwords, since the attack needs a login. The class fix is in how to fix input handling weaknesses in embedded firmware.
Is CVE-2023-25915 exploited?
Yes, per CISA. It was added to the KEV catalog on 2026-11-25 with a due date of 2026-11-28, forensic triage required, and a required action to apply the vendor's mitigations in line with BOD 26-04 or stop using the product if none are available; known ransomware campaign use is "Unknown" (catalog version 2026.11.25, as of 2026-11-26). FIRST EPSS gives 0.01431, the 73.24th percentile, in the 2026-11-25 dataset (FIRST EPSS). See KEV and EPSS vulnerability prioritization for ordering it against other work.
Evidence
- NVD: status Modified; due to improper input validation an authenticated remote attacker could execute arbitrary commands; NVD Primary CVSS v3.1 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H, CWE NVD-CWE-noinfo; DIVD Secondary 9.9 S:C, CWE-20; CPE ak-sm_800a_firmware up to and including 3.3; read 2026-11-26. — NVD
- CVE record: PUBLISHED, CNA DIVD, published 2023-08-21; affected AK-SM800A < 3.3; workaround: upgrade to the latest patch, version 3.3. — CVE.org
- Danfoss DSA-2023-08-01 (published 21 Aug 2023): CVE-2023-25913 (7.5), CVE-2023-25914 (7.5, path traversal via the XML interface, CWE-22), CVE-2023-25915 (9.8, remote command execution, CWE-20); affected: AK-SM 800A all series with SW version below 3.3; remediation: install patch 3.3 / latest software; mitigations N/A; credits HackDefense, Synacktiv, DIVD. — Danfoss security advisory
- DIVD-2023-00025: reported 18 Jan 2023 by HackDefense researchers, limited disclosure 17 Aug 2023, DIVD scanned the internet and from 27 Sep 2023 notified owners of vulnerable instances; Danfoss advises updating to version 3.3; case closed 20 Dec 2023. — DIVD CSIRT
- KEV catalog 2026.11.25: CVE-2023-25915 dateAdded 2026-11-25, dueDate 2026-11-28, forensicTriage Yes, knownRansomwareCampaignUse Unknown; required action: apply mitigations per vendor instructions in line with BOD 26-04 and CISA's forensics triage requirements, or discontinue use if mitigations are unavailable; read 2026-11-26. — CISA KEV
- EPSS 0.01431, percentile 0.73235, dataset 2026-11-25, read 2026-11-26. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Danfoss products are affected by CVE-2023-25915?
Danfoss lists the AK-SM 800A system manager, all series, with software below 3.3 (per Danfoss DSA-2023-08-01 and the CVE record).
Does an attacker need a login for CVE-2023-25915?
The CVE record and NVD say the attacker must be authenticated (CVSS PR:L). Danfoss's advisory only says "a remote attacker" and scores it 9.8. Treat exposed units with default or shared passwords as reachable (per NVD and Danfoss).
How do I fix CVE-2023-25915?
Install Danfoss software 3.3 or later; Danfoss lists no workaround. Later releases 4.2 and 4.3.1 fix further AK-SM 8xxA flaws, so go to the current release and keep the interface off the internet (per Danfoss).
Is CVE-2023-25915 exploited in the wild?
CISA added it to the KEV catalog on 2026-11-25 with a due date of 2026-11-28 and forensic triage required; ransomware use is listed as Unknown. FIRST EPSS gives 0.01431 (73.24th percentile) in the 2026-11-25 dataset (as of 2026-11-26, per CISA KEV and FIRST EPSS).