CVE-2025-41450 is an authentication bypass in Danfoss AK-SM 8xxA refrigeration system managers before 4.2: an attacker without credentials can generate a web report that exposes internal IP addresses, usernames and store names. NVD scores it 7.5 (Danfoss 8.2) and CISA KEV lists it as exploited since 2026-11-25. Danfoss fixed it in release 4.2.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.5%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
Yes
Listed as known exploited
Published
Vulnerability ID: CVE-2025-41450 · Source: NVD (Primary CVSS v3.1)
Affected components
| Component | CPE | Version range |
|---|---|---|
| Danfoss AK-SM 8xxA Series system managers (AK-SM 800A) | cpe:2.3:o:danfoss:ak-sm_800a_firmware:*:*:*:*:*:*:*:* | Before 4.2 (Danfoss DSA-2025-03-01, NVD CPE); fixed in R4.2. CISA names R4.3.1 for the related CVE-2025-41451/-41452 |
What does this mean for affected devices?
The CVE record, published on 2025-05-08 by Danfoss as CNA, describes an "Improper Authentication vulnerability in Danfoss AKSM8xxA Series" affecting "AK-SM 8xxA Series prior to version 4.2". NVD's Primary CVSS v3.1 score is 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N), an unauthenticated network attack with high confidentiality impact. Danfoss scores it 8.2 (AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:L/A:H) with CWE-305, authentication bypass by primary weakness (NVD, CVE record). The AK-SM 800A family are Danfoss system managers that run refrigeration and HVAC control in food retail stores.
What does the flaw expose?
Danfoss advisory DSA-2025-03-01 of 24 March 2025, credited to Claroty Team82, says that because of an authentication flaw "an attacker would be capable of generating a web report that discloses sensitive information such as internal IP addresses, usernames, store names and other sensitive information". CISA's ICSA-25-140-03 (CSAF) adds that the bypass is caused by datetime-based password generation and maps it to CWE-287. The same CISA advisory, updated on 2025-08-26, also covers two post-authentication flaws, CVE-2025-41451 (command injection) and CVE-2025-41452, fixed in release 4.3.1, so an attacker who gets past the login can go further on units below 4.3.1.
How do you fix it?
Danfoss says to "install the latest patch with number 4.2" from its AK-SM 800A software page and lists no mitigation; CISA says users can follow the AK-SM 800A software upgrade process and names release 4.3.1 for the two later CVEs, so upgrade to 4.3.1 or later. CISA's recommended practices for this advisory are to keep control system devices off the internet, put them behind firewalls and use a VPN for remote access (BOD 23-02 guide). Older AK-SM 800A software has further exploited flaws: the path traversal CVE-2023-25914 and command execution CVE-2023-25915, fixed in 3.3. The class fix is in how to fix authentication bypass in embedded firmware.
Is CVE-2025-41450 exploited?
Yes, per CISA. When ICSA-25-140-03 was published, CISA said no known public exploitation had been reported. CISA added the CVE to the KEV catalog on 2026-11-25 with a due date of 2026-12-09 and a required action to apply the vendor's mitigations in line with BOD 26-04 or stop using the product if none are available; known ransomware campaign use is "Unknown" (catalog version 2026.11.25, as of 2026-11-26). FIRST EPSS gives 0.00513, the 37.03rd percentile, in the 2026-11-25 dataset (FIRST EPSS); KEV outranks the low EPSS here, see KEV and EPSS vulnerability prioritization.
Evidence
- NVD: status Modified, published 2025-05-08; Improper Authentication in Danfoss AK-SM 8xxA Series prior to 4.2; NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N; Danfoss Secondary 8.2; CWE-305 (Danfoss); CPE ak-sm_800a_firmware < 4.2; read 2026-11-26. — NVD
- CVE record: PUBLISHED, CNA Danfoss; AK-SM 8xxA Series affected below 4.2; CVSS 3.1 8.2. — CVE.org
- Danfoss DSA-2025-03-01 (published 24 March 2025, updated 1 September 2025): authentication flaw lets an attacker generate a web report disclosing internal IP addresses, usernames, store names; affected AK-SM 8xxA before 4.2; install patch 4.2; mitigations N/A; credit Tomer Goldschmidt (Claroty Team82). — Danfoss security advisory
- CISA ICSA-25-140-03 (CSAF, initial 2025-05-20, Update A 2025-08-26 added CVE-2025-41451 and CVE-2025-41452, revision 2026-11-18): bypass caused by datetime-based password generation, CWE-287, 8.2; R4.2 fixes CVE-2025-41450, R4.3.1 fixes CVE-2025-41451 (CWE-77) and CVE-2025-41452; recommended practices minimize network exposure, firewalls, VPN; no known public exploitation reported to CISA at publication. — CISA ICS advisory (CSAF)
- KEV catalog 2026.11.25: dateAdded 2026-11-25, dueDate 2026-12-09, forensicTriage No, knownRansomwareCampaignUse Unknown, CWE-305; required action per vendor instructions and BOD 26-04 or discontinue use; read 2026-11-26. — CISA KEV
- EPSS 0.00513, percentile 0.37031, dataset 2026-11-25, read 2026-11-26. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Danfoss devices are affected by CVE-2025-41450?
AK-SM 8xxA Series system managers, the AK-SM 800A family, with software before 4.2 (per Danfoss DSA-2025-03-01 and CISA ICSA-25-140-03).
What can an attacker get through CVE-2025-41450?
Danfoss says the flaw lets an attacker generate a web report that discloses internal IP addresses, usernames, store names and other sensitive information. CISA notes that two further flaws behind the login, CVE-2025-41451 and CVE-2025-41452, are fixed only in 4.3.1 (per Danfoss and CISA).
How do I fix CVE-2025-41450?
Install Danfoss release 4.2 or later; CISA names 4.3.1 for the two related CVEs, so 4.3.1 or later covers all three. Keep the system manager off the internet and reach it over a VPN (per Danfoss and CISA ICSA-25-140-03).
Is CVE-2025-41450 exploited?
CISA added it to the KEV catalog on 2026-11-25 with a due date of 2026-12-09; ransomware use is listed as Unknown. FIRST EPSS gives 0.00513 (37.03rd percentile) in the 2026-11-25 dataset (as of 2026-11-26, per CISA KEV and FIRST EPSS).