Security Advisory

CVE-2023-25914: Danfoss AK-SM 800A Path Traversal

Last updated:
  • CVE-2023-25914

CVE-2023-25914 is a path traversal in the XML interface of the Danfoss AK-SM 800A refrigeration system manager: a logged-in attacker can read system files on the controller, which can lead to full compromise. NVD scores it 8.8 and CISA KEV lists it as exploited since 2026-11-25. Danfoss fixed it in software 3.3; install the current release.

Vulnerability summary

CVSS base score

8.8

High severity

EPSS score (FIRST)

1.1%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

Yes

Listed as known exploited

Published

Vulnerability ID: CVE-2023-25914 · Source: NVD (Primary CVSS v3.1)

Affected components

ComponentCPEVersion range
Danfoss AK-SM 800A system manager (all series)cpe:2.3:o:danfoss:ak-sm_800a_firmware:*:*:*:*:*:*:*:*Software before 3.3 (Danfoss DSA-2023-08-01); fixed in 3.3. NVD's CPE reads 'up to and including 3.3'

What does this mean for affected devices?

The CVE record, published on 2023-08-21 by the Dutch Institute for Vulnerability Disclosure (DIVD) as CNA, says that "due to improper restriction, authenticated attackers could retrieve and read system files of the underlying server through the XML interface" of the Danfoss AK-SM 800A, and that the information read "can lead to a full system compromise". NVD's Primary CVSS v3.1 score is 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), the same as DIVD's, with CWE-22 path traversal (NVD, CVE record). The AK-SM 800A is a Danfoss system manager that supervises refrigeration and HVAC controllers in food retail stores, so it sits on the store network and is often reached remotely for service.

Which AK-SM 800A software is affected?

Danfoss advisory DSA-2023-08-01 of 21 August 2023 covers "AK-SM 800A all Series with SW version below/before 3.3" and three CVEs: this path traversal, the command execution flaw CVE-2023-25915 and an information leak, CVE-2023-25913. Danfoss scores this one 7.5. NVD's CPE configuration says "up to and including 3.3", which also takes in the fixed release; follow the vendor text, which names 3.3 as the fix.

How do you fix it?

Danfoss says to "install the latest patch with number 3.3" from its AK-SM 800A software page and lists no other mitigation. A later Danfoss advisory adds release 4.2 for the authentication bypass CVE-2025-41450, so an upgrade today should go to the current release, not stop at 3.3. DIVD's case DIVD-2023-00025 records that it scanned the internet for exposed units from 17 August 2023 and notified owners; keep the system manager's web interface off the internet and reachable only over a VPN or a jump host, as in the BOD 23-02 guide on internet-exposed management interfaces. The class fix is in how to fix path traversal in embedded firmware.

Is CVE-2023-25914 exploited?

Yes, per CISA. It was added to the KEV catalog on 2026-11-25 with a due date of 2026-11-28, forensic triage required, and a required action to apply the vendor's mitigations in line with BOD 26-04 or stop using the product if none are available; known ransomware campaign use is "Unknown" (catalog version 2026.11.25, as of 2026-11-26). FIRST EPSS gives 0.01078, the 64.58th percentile, in the 2026-11-25 dataset (FIRST EPSS). For ordering this against other work, see KEV and EPSS vulnerability prioritization.

How to fix this class of issueThis advisory's weakness class is Path traversal. Our practical guide covers how to detect, fix, verify and disclose it: How to fix path traversal in embedded firmware.

Evidence

  • NVD: status Modified; authenticated attackers could retrieve and read system files of the underlying server through the XML interface; NVD Primary CVSS v3.1 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; DIVD Secondary 8.8; CWE-22; CPE ak-sm_800a_firmware up to and including 3.3; read 2026-11-26. — NVD
  • CVE record: PUBLISHED, CNA DIVD, published 2023-08-21; affected AK-SM800A < 3.3. — CVE.org
  • Danfoss DSA-2023-08-01 (published 21 Aug 2023): CVE-2023-25913 (7.5), CVE-2023-25914 (7.5, path traversal via the XML interface, CWE-22), CVE-2023-25915 (9.8, remote command execution, CWE-20); affected: AK-SM 800A all series with SW version below 3.3; remediation: install patch 3.3 / latest software; mitigations N/A; credits HackDefense, Synacktiv, DIVD. — Danfoss security advisory
  • DIVD-2023-00025: reported 18 Jan 2023 by HackDefense researchers, limited disclosure 17 Aug 2023, DIVD scanned the internet and from 27 Sep 2023 notified owners of vulnerable instances; Danfoss advises updating to version 3.3; case closed 20 Dec 2023. — DIVD CSIRT
  • KEV catalog 2026.11.25: CVE-2023-25914 dateAdded 2026-11-25, dueDate 2026-11-28, forensicTriage Yes, knownRansomwareCampaignUse Unknown; required action: apply mitigations per vendor instructions in line with BOD 26-04 and CISA's forensics triage requirements, or discontinue use if mitigations are unavailable; read 2026-11-26. — CISA KEV
  • EPSS 0.01078, percentile 0.64585, dataset 2026-11-25, read 2026-11-26. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Danfoss DSA-2023-08-01: AK-SM 800A vulnerabilities
  3. DIVD case DIVD-2023-00025
  4. CVE.org record CVE-2023-25914 (CNA: DIVD)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which Danfoss products are affected by CVE-2023-25914?

Danfoss lists the AK-SM 800A system manager, all series, with software below 3.3. The flaw is in its XML interface and needs a logged-in user (per Danfoss DSA-2023-08-01 and the CVE record).

How do I fix CVE-2023-25914?

Install Danfoss software 3.3 or later from the AK-SM 800A download page; Danfoss lists no workaround. Because later Danfoss advisories fixed more flaws in releases 4.2 and 4.3.1, go to the current release, and keep the web interface off the internet (per Danfoss).

Is CVE-2023-25914 exploited in the wild?

CISA added it to the KEV catalog on 2026-11-25 with a due date of 2026-11-28 and forensic triage required; ransomware use is listed as Unknown. FIRST EPSS gives 0.01078 (64.58th percentile) in the 2026-11-25 dataset (as of 2026-11-26, per CISA KEV and FIRST EPSS).

Why do the scores for CVE-2023-25914 differ?

NVD's Primary score and DIVD's CNA score are both CVSS v3.1 8.8 because the attacker needs a login. Danfoss's own advisory lists 7.5. This page uses the NVD Primary score (per NVD and Danfoss).