**CVE-2023-25948** is an information leak in Honeywell Experion, published on 2023-07-13, in which configuration data is exposed when an error is generated in response to a specially crafted message. Honeywell and NVD say it affects the Experion Server and Stations, while CISA says the C300 controller. NVD scores it 7.5 and CISA 9.8.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-25948 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Honeywell Experion Server, Experion Station, Engineering Station, Direct Station | cpe:2.3:a:honeywell:experion_server:*:*:*:*:*:*:*:* | Experion Server and Station 501.1 to 501.6 HF8, 510.1 to 510.2 HF12, 511.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2; Engineering and Direct Station 510.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2 (CVE record; NVD CPE) |
| Honeywell Experion PKS, Experion LX and PlantCruise | — | before R520.2 per CISA ICSA-23-194-06; update to R520.2 |
What does this mean for affected devices?
Honeywell, the CNA, describes a "Server information leak of configuration data when an error is generated in response to a specially crafted message". It scores the flaw CVSS 3.1 7.5 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N), maps it to CWE-394, unexpected status code or return value, and lists Experion Server and Station 501.1 to 501.6 HF8, 510.1 to 510.2 HF12, 511.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2; Engineering and Direct Station 510.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2 (CVE record).
NVD's Primary score is the same 7.5 vector. NVD maps it to CWE-209, error message containing sensitive information, and its configuration lists Experion Server, Experion Station, Engineering Station and Direct Station, following the CVE record (NVD).
CISA's ICSA-23-194-06 of 2023-07-13 covers nine Experion CVEs reported by Armis in Experion PKS, Experion LX and PlantCruise before R520.2, and recommends R520.2 for all three, downloaded from Honeywell's support portal. It also asks users to limit access to authorised users and to keep backup files where only authorised users can reach them. Honeywell's product security page lists the advisory as Critical, covering nine CVEs in versions before R520.2. CISA describes this CVE differently: "C300 could leak configuration data when an error is generated in response to a specially crafted message", scored 9.8 with the CVSS 3.0 vector AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H and CWE-394.
Because the sources disagree on the component, check both the Experion servers and stations and the C300 controllers when matching assets. The R520.2 update covers all of them, so the fix is the same either way.
CVE-2023-25948 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.0057, percentile 48.0, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).
Our Honeywell Experion and ControlEdge guide lists all nine CVEs from this advisory. CVE-2023-23585 is a server-side heap overflow from the same advisory, and CVE-2023-25770 is a C300 error-path overflow.
Evidence
- Honeywell CNA: server information leak of configuration data on error for crafted message; 7.5 C:H; CWE-394; Experion Server/Station/Engineering/Direct Station ranges. — CVE.org record
- NVD Primary CVSS 3.1 7.5 C:H; CWE-209; CPE experion_server, experion_station, engineering_station, direct_station. — NVD
- ICSA-23-194-06: C300 could leak configuration data when an error is generated; CVSS 3.0 9.8; CWE-394; fix R520.2. — CISA ICSA-23-194-06 (CSAF)
- Honeywell notice table lists ICSA-23-194-06, versions prior to R520.2, 9 CVEs, Critical. — Honeywell product security

Related advisories
Sources
Frequently asked questions
Does CVE-2023-25948 affect the C300 or the Experion server?
The sources disagree. Honeywell's CVE record and NVD name the Experion Server, Experion Station, Engineering Station and Direct Station; CISA's ICSA-23-194-06 says the C300 could leak configuration data (per the CVE record, NVD and CISA).
How severe is CVE-2023-25948?
NVD and Honeywell score it 7.5 with high confidentiality impact only. CISA scores it 9.8 with a CVSS 3.0 vector that also rates integrity and availability high (per NVD and CISA ICSA-23-194-06).
How do I fix CVE-2023-25948?
CISA recommends updating Experion PKS, Experion LX or PlantCruise to R520.2, available from the Honeywell support portal under Product Documents and Downloads (per CISA ICSA-23-194-06).
Is CVE-2023-25948 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.0057, percentile 48.0, in the 2026-11-21 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?