CVE-2020-28221 is an improper input validation flaw (CWE-20) in Schneider Electric's EcoStruxure Operator Terminal Expert and Pro-face BLUE HMI software that could let an attacker run arbitrary code on a Harmony or Pro-face HMI panel when the Ethernet Download feature is enabled. NVD scores it 9.8; Schneider scores it 8.8. Version 3.1 Service Pack 1B fixes it.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
2.1%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-28221 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric EcoStruxure Operator Terminal Expert (formerly Vijeo XD) on Harmony HMIST6, HMIG3U and HMISTO HMIs | cpe:2.3:a:schneider-electric:ecostruxure_operator_terminal_expert:3.1:sp1a:*:*:*:*:*:* | 3.1 Service Pack 1A and prior per Schneider; NVD CPE lists 3.1 and 3.1 SP1A. Fixed in V3.1 Service Pack 1B |
| Pro-face BLUE on Pro-face ST6000, SP-5B41 (SP5000 series) and GP4100 HMIs | cpe:2.3:a:schneider-electric:pro-face_blue:3.1:sp1a:*:*:*:*:*:* | 3.1 Service Pack 1A and prior per Schneider; NVD CPE lists 3.1 and 3.1 SP1A. Fixed in V3.1 Service Pack 1B |
What does this mean for affected devices?
Schneider Electric's notice SEVD-2021-012-01, published on 12 January 2021, says a CWE-20 improper input validation vulnerability "could cause arbitrary code execution when the Ethernet Download feature is enable on the HMI". Operator Terminal Expert (formerly Vijeo XD) and Pro-face BLUE are the configuration tools for these panels, and the risk sits on the HMI that receives the project, not only on the engineering workstation.
How severe is CVE-2020-28221?
NVD's Primary score is CVSS v3.1 9.8, AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (NVD). Schneider, the CNA, publishes CVSS v3.0 8.8 with AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H in its notice: the only difference is that Schneider assumes user interaction is required. NVD also lists a CVSS v2 score of 9.3. The CVE.org record carries Schneider's description and product list but no CVSS block.
Which HMIs are affected and what is the fix?
Schneider lists Operator Terminal Expert 3.1 Service Pack 1A and prior running on Harmony HMIST6 series, HMIG3U in the HMIGTU series and HMISTO series panels, and Pro-face BLUE 3.1 Service Pack 1A and prior running on Pro-face ST6000 series, SP-5B41 in the SP5000 series and GP4100 series panels. V3.1 Service Pack 1B of each product fixes it; for Operator Terminal Expert it is also delivered through the Schneider Electric Software Update (SESU) client. Owners who cannot update should disable "Always Allow Ethernet Transfer" under Target, Advanced, Settings, Preferences in the project and keep the panels on a secure network.
The Schneider EcoStruxure HMI and SCADA software guide puts this flaw next to the other Operator Terminal Expert and Vijeo Designer issues; CVE-2020-7497 is a workstation-side path traversal in the same product, and CVE-2021-22704 is an FTP flaw on Harmony panels configured with Vijeo Designer. The OT security guide for small manufacturers covers zoning the HMI network away from office systems.
Is CVE-2020-28221 exploited?
It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.02139, the 82.7th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS). The KEV and EPSS prioritization guide explains how to weigh that against network exposure of the panels.


Evidence
- NVD (read 2026-11-28): published 2021-01-26, status Modified; NVD Primary CVSS v3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 9.3; CWE-20 (Schneider); CPE ecostruxure_operator_terminal_expert 3.1 and 3.1 sp1a, pro-face_blue 3.1 and 3.1 sp1a with Harmony and Pro-face panel hardware. — NVD
- Schneider SEVD-2021-012-01 (12 January 2021, read 2026-11-28): affected Operator Terminal Expert 3.1 SP1A and prior on HMIST6, HMIG3U, HMISTO; Pro-face BLUE 3.1 SP1A and prior on ST6000, SP-5B41, GP4100; CVSS v3.0 8.8 AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H; fix V3.1 SP1B (also via SESU); mitigation: disable Always Allow Ethernet Transfer. — Schneider Electric
- CVE.org record (read 2026-11-28): assigner Schneider Electric, CWE-20, no CVSS metric in the CNA container. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.02139, percentile 0.82717, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which version fixes CVE-2020-28221?
V3.1 Service Pack 1B of EcoStruxure Operator Terminal Expert and V3.1 Service Pack 1B of Pro-face BLUE, per Schneider's SEVD-2021-012-01. Operator Terminal Expert users can also get it through the Schneider Electric Software Update (SESU) client.
What can I do if I cannot update the HMI software?
Schneider's mitigation is to disable the "Always Allow Ethernet Transfer" option under Target, Advanced, Settings, Preferences in the project, and to run Harmony and Pro-face HMIs only in a secure network environment.
Why does NVD score 9.8 when Schneider scores 8.8?
Both vectors are network, low complexity, no privileges, with high impact on confidentiality, integrity and availability. Schneider's CVSS v3.0 vector requires user interaction (UI:R); NVD's CVSS v3.1 vector does not (UI:N), which raises the score to 9.8.
Is CVE-2020-28221 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.02139, the 82.7th percentile, in the 2026-11-27 dataset.
Questions about this page?