Security Advisory

CVE-2020-28221: Operator Terminal Expert HMI Download Flaw

Last updated:
  • CVE-2020-28221

CVE-2020-28221 is an improper input validation flaw (CWE-20) in Schneider Electric's EcoStruxure Operator Terminal Expert and Pro-face BLUE HMI software that could let an attacker run arbitrary code on a Harmony or Pro-face HMI panel when the Ethernet Download feature is enabled. NVD scores it 9.8; Schneider scores it 8.8. Version 3.1 Service Pack 1B fixes it.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

2.1%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-28221 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric EcoStruxure Operator Terminal Expert (formerly Vijeo XD) on Harmony HMIST6, HMIG3U and HMISTO HMIscpe:2.3:a:schneider-electric:ecostruxure_operator_terminal_expert:3.1:sp1a:*:*:*:*:*:*3.1 Service Pack 1A and prior per Schneider; NVD CPE lists 3.1 and 3.1 SP1A. Fixed in V3.1 Service Pack 1B
Pro-face BLUE on Pro-face ST6000, SP-5B41 (SP5000 series) and GP4100 HMIscpe:2.3:a:schneider-electric:pro-face_blue:3.1:sp1a:*:*:*:*:*:*3.1 Service Pack 1A and prior per Schneider; NVD CPE lists 3.1 and 3.1 SP1A. Fixed in V3.1 Service Pack 1B

What does this mean for affected devices?

Schneider Electric's notice SEVD-2021-012-01, published on 12 January 2021, says a CWE-20 improper input validation vulnerability "could cause arbitrary code execution when the Ethernet Download feature is enable on the HMI". Operator Terminal Expert (formerly Vijeo XD) and Pro-face BLUE are the configuration tools for these panels, and the risk sits on the HMI that receives the project, not only on the engineering workstation.

How severe is CVE-2020-28221?

NVD's Primary score is CVSS v3.1 9.8, AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (NVD). Schneider, the CNA, publishes CVSS v3.0 8.8 with AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H in its notice: the only difference is that Schneider assumes user interaction is required. NVD also lists a CVSS v2 score of 9.3. The CVE.org record carries Schneider's description and product list but no CVSS block.

Which HMIs are affected and what is the fix?

Schneider lists Operator Terminal Expert 3.1 Service Pack 1A and prior running on Harmony HMIST6 series, HMIG3U in the HMIGTU series and HMISTO series panels, and Pro-face BLUE 3.1 Service Pack 1A and prior running on Pro-face ST6000 series, SP-5B41 in the SP5000 series and GP4100 series panels. V3.1 Service Pack 1B of each product fixes it; for Operator Terminal Expert it is also delivered through the Schneider Electric Software Update (SESU) client. Owners who cannot update should disable "Always Allow Ethernet Transfer" under Target, Advanced, Settings, Preferences in the project and keep the panels on a secure network.

The Schneider EcoStruxure HMI and SCADA software guide puts this flaw next to the other Operator Terminal Expert and Vijeo Designer issues; CVE-2020-7497 is a workstation-side path traversal in the same product, and CVE-2021-22704 is an FTP flaw on Harmony panels configured with Vijeo Designer. The OT security guide for small manufacturers covers zoning the HMI network away from office systems.

Is CVE-2020-28221 exploited?

It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.02139, the 82.7th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS). The KEV and EPSS prioritization guide explains how to weigh that against network exposure of the panels.

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): published 2021-01-26, status Modified; NVD Primary CVSS v3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 9.3; CWE-20 (Schneider); CPE ecostruxure_operator_terminal_expert 3.1 and 3.1 sp1a, pro-face_blue 3.1 and 3.1 sp1a with Harmony and Pro-face panel hardware. — NVD
  • Schneider SEVD-2021-012-01 (12 January 2021, read 2026-11-28): affected Operator Terminal Expert 3.1 SP1A and prior on HMIST6, HMIG3U, HMISTO; Pro-face BLUE 3.1 SP1A and prior on ST6000, SP-5B41, GP4100; CVSS v3.0 8.8 AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H; fix V3.1 SP1B (also via SESU); mitigation: disable Always Allow Ethernet Transfer. — Schneider Electric
  • CVE.org record (read 2026-11-28): assigner Schneider Electric, CWE-20, no CVSS metric in the CNA container. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.02139, percentile 0.82717, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2021-012-01: EcoStruxure Operator Terminal Expert and Pro-face BLUE
  3. CVE.org record (JSON)
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Which version fixes CVE-2020-28221?

V3.1 Service Pack 1B of EcoStruxure Operator Terminal Expert and V3.1 Service Pack 1B of Pro-face BLUE, per Schneider's SEVD-2021-012-01. Operator Terminal Expert users can also get it through the Schneider Electric Software Update (SESU) client.

What can I do if I cannot update the HMI software?

Schneider's mitigation is to disable the "Always Allow Ethernet Transfer" option under Target, Advanced, Settings, Preferences in the project, and to run Harmony and Pro-face HMIs only in a secure network environment.

Why does NVD score 9.8 when Schneider scores 8.8?

Both vectors are network, low complexity, no privileges, with high impact on confidentiality, integrity and availability. Schneider's CVSS v3.0 vector requires user interaction (UI:R); NVD's CVSS v3.1 vector does not (UI:N), which raises the score to 9.8.

Is CVE-2020-28221 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.02139, the 82.7th percentile, in the 2026-11-27 dataset.