CVE-2022-41667 is a path traversal flaw (CWE-22) in Schneider Electric EcoStruxure Operator Terminal Expert and Pro-face BLUE, the HMI configuration tools for Harmony and Pro-face panels. A user with local privileges could use it to load a malicious DLL and run code on the workstation. NVD scores it 7.8 and Schneider 7.0. V3.3 Service Pack 1 fixes it.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
0.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2022-41667 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric EcoStruxure Operator Terminal Expert | cpe:2.3:a:schneider-electric:ecostruxure_operator_terminal_expert:*:*:*:*:*:*:*:* | V3.3 Hotfix 1 or prior (NVD: before 3.3, 3.3 and 3.3 HF1); fixed in V3.3 Service Pack 1 |
| Pro-face BLUE | cpe:2.3:a:schneider-electric:pro-face_blue:*:*:*:*:*:*:*:* | V3.3 Hotfix 1 or prior; fixed in V3.3 Service Pack 1 |
What does this mean for affected devices?
Schneider's notice SEVD-2022-284-01, published on 11 October 2022, describes "a CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability" "that allows adversaries with local user privileges to load a malicious DLL which could lead to execution of malicious code." It sits next to CVE-2022-41666, a missing signature check with the same outcome, and four more flaws: an incorrect project conversion that loads a project from an attacker-controlled network share, a signature check and a path traversal in the SGIUtility component, and an SQL injection during project migration. Noam Moshe and Amir Preminger of Claroty reported all six.
How severe is CVE-2022-41667?
NVD's Primary score is CVSS v3.1 7.8, AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H (NVD). Schneider scores it 7.0 with high attack complexity, AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H, and that 7.0 is the score in the CVE.org record. The CWE-22 label is Schneider's; NVD adds none. The attacker needs a local user account on the engineering workstation.
Which versions are affected and what is the fix?
Affected are Operator Terminal Expert V3.3 Hotfix 1 or prior and Pro-face BLUE V3.3 Hotfix 1 or prior; NVD's configuration matches versions before 3.3, 3.3 itself and 3.3 Hotfix 1. V3.3 Service Pack 1 of each product fixes it, from Schneider's or Pro-face's download pages or through Schneider Electric Software Update (SESU). Schneider asks owners who delay the update to use the software only on a trusted, hardened workstation in a secure network environment.
The Schneider EcoStruxure HMI and SCADA software guide puts this flaw in its Operator Terminal Expert table. The earlier path traversal in the same product, CVE-2020-7497, runs an application at start-up instead. The OT security guide for small manufacturers explains how to keep engineering workstations on a short list of trusted users.
Is CVE-2022-41667 exploited?
It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0030, the 15th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): published 2022-11-04, status Modified; NVD Primary CVSS v3.1 7.8 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; Schneider Secondary CVSS v3.1 7.0 AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H; CWE-22 (Schneider, no NVD Primary CWE); CPE ecostruxure_operator_terminal_expert before 3.3, 3.3, 3.3 hf1; pro-face_blue before 3.3, 3.3, 3.3 hf1. — NVD
- Schneider SEVD-2022-284-01 (11 October 2022, PDF and Schneider CSAF read 2026-11-28): CVE-2022-41667 CWE-22 CVSS v3.1 7.0; sibling CVEs 41666 (CWE-347), 41668 (project conversion from network share), 41669/41670 (SGIUtility), 41671 (SQL injection in project migration); affected V3.3 Hotfix 1 or prior of both products; fix V3.3 Service Pack 1, also via SESU; credit Noam Moshe and Amir Preminger (Claroty). — Schneider Electric
- CVE.org record (read 2026-11-28): assigner Schneider Electric, CWE-22, CVSS v3.1 7.0 AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H; affected Operator Terminal Expert and Pro-face BLUE V3.3 up to and including Hotfix 1. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.00296, percentile 0.14680, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which version fixes CVE-2022-41667?
V3.3 Service Pack 1 of EcoStruxure Operator Terminal Expert and of Pro-face BLUE. Schneider's SEVD-2022-284-01 lists V3.3 Hotfix 1 and earlier as affected, and the fix also arrives through SESU.
How is it different from CVE-2022-41666?
Both let a local user load a malicious DLL. CVE-2022-41666 is a missing cryptographic signature check (CWE-347); CVE-2022-41667 is a path traversal (CWE-22). They share the same scores and the same fix.
Are the HMI panels themselves affected?
Schneider's notice describes the impact on the Windows workstation where Operator Terminal Expert, Pro-face BLUE or their runtime is installed. It does not list panel firmware as affected.
Is CVE-2022-41667 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0030, the 15th percentile, in the 2026-11-27 dataset.
Questions about this page?