Security Advisory

CVE-2021-35533: Hitachi Energy RTU500 BCI IEC 104 reboot

Last updated:
  • CVE-2021-35533

CVE-2021-35533 is an input validation flaw in the IEC 60870-5-104 parser of the Bidirectional Communication Interface on Hitachi Energy RTU500 remote terminal units. With BCI IEC 104 enabled, a crafted message reboots the CMU. CMU firmware 12.0, 12.2 and 12.4 is affected; 12.6.5.0 and later fix it. NVD, Hitachi Energy and CISA score it 7.5.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

0.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2021-35533 · Source: NVD

Affected components

ComponentCPEVersion range
Hitachi Energy RTU500 series CMU firmware (BCI IEC 60870-5-104 enabled)cpe:2.3:o:hitachienergy:rtu500_firmware:12.4:*:*:*:*:*:*:*CMU firmware 12.0.*, 12.2.* and 12.4.* (all versions); fixed in 12.6.5.0 or later, e.g. 12.7.* or 13.2.* (CVE record, CISA ICSA-21-336-04); NVD CPE lists 12.0, 12.2 and 12.4

What does this mean for affected devices?

Hitachi Energy, the CNA, describes an "Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function" of the RTU500 series that makes the receiving RTU500 CMU reboot on a specially crafted message. The BCI IEC 60870-5-104 function is disabled (not configured) by default, so only RTUs that use it are exposed. NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), with a CVSS v2 7.1; Hitachi Energy and CISA's ICSA-21-336-04 of 2021-12-02 (CSAF) give the same 7.5. All list CWE-20. The record was published on 2021-11-26 (NVD, CVE record).

Which firmware is affected?

The CVE record and CISA list RTU500 series CMU firmware 12.0., 12.2. and 12.4.*, all versions. NVD's CPE names only the three branch numbers 12.0, 12.2 and 12.4, so a scanner that matches exact versions such as 12.4.3.0 may miss it; check the CMU firmware branch instead. CISA states that no known public exploits specifically target this vulnerability and lists the energy sector, deployed worldwide.

Fix and mitigation

Update to RTU500 series CMU firmware 12.6.5.0 or later, for example 12.7.x or 13.2.x. If the BCI IEC 60870-5-104 function is not used, disable it in the configuration; that is the default state. CISA's general measures apply as well: physically protect process control systems, do not connect them directly to the Internet, and separate them from other networks with a firewall that exposes a minimal number of ports. Hitachi Energy's own advisory is 8DBD000063. The ABB AC500, RTU500 and Relion guide covers the RTU500 advisories and later firmware lines, CVE-2021-27196 is a Hitachi ABB IEC 61850 reboot flaw, CVE-2021-35535 covers the Relion 670/650 boot image, and the IEC 60870-5-104 protocol security guide covers protecting IEC 104 links.

CVE-2021-35533 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.0095, the 62.1st percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2021-11-26; NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H and CVSS v2 7.1; Hitachi Energy Secondary 7.5; CWE-20; CPE rtu500_firmware 12.0, 12.2, 12.4 running on rtu500. — NVD
  • CISA ICSA-21-336-04 CSAF (released 2021-12-02), read 2026-11-23: RTU500 series CMU firmware 12.0, 12.2, 12.4 all versions; CWE-20, CVSS v3 7.5; disable BCI IEC 60870-5-104 if not used (disabled by default); update to 12.6.5.0 or later (12.7.* or 13.2.*); Hitachi Energy advisory 8DBD000063; no known public exploits; energy sector, worldwide. — CISA ICSA-21-336-04
  • CVE record (checked 2026-11-23): state PUBLISHED; CNA Hitachi Energy; affected CMU firmware 12.0.*, 12.2.*, 12.4.*; solution: disable BCI IEC 104 if unused, update to 12.6.5.0 or later; reference Hitachi Energy 8DBD000063. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.0095, percentile 0.62147, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-21-336-04: Hitachi Energy RTU500 series BCI
  3. CISA ICSA-21-336-04 CSAF (machine-readable advisory)
  4. CVE.org record CVE-2021-35533 (Hitachi Energy CNA)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which RTU500 firmware fixes CVE-2021-35533?

CMU firmware 12.6.5.0 or later, for example 12.7.x or 13.2.x, according to Hitachi Energy's CVE record and CISA ICSA-21-336-04. Firmware 12.0, 12.2 and 12.4 is affected in all versions.

Is every RTU500 on 12.x exposed?

Only CMUs on which the BCI IEC 60870-5-104 function is enabled and configured. Hitachi Energy says the function is disabled by default, and disabling it where it is not used removes the exposure.

Why might a scanner miss this CVE?

NVD's CPE lists only the branch numbers 12.0, 12.2 and 12.4, while installed firmware carries full versions. Compare the CMU firmware branch with the advisory instead of relying on exact CPE matching.

Is CVE-2021-35533 in the CISA KEV catalog?

No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.0095 (62.1st percentile) in the 2026-11-22 dataset.