CVE-2021-27196 is an input validation flaw in the IEC 61850 interfaces of Hitachi ABB Power Grids substation devices, including Relion 670 and 650 relays, REB500, RTU500 and FOX615. An attacker on the IEC 61850 network can force a reboot that takes the device offline for about 60 seconds. NVD scores it 7.5. Fixed firmware differs per product line.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
1.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-27196 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Relion 670 series | cpe:2.3:o:hitachienergy:relion_670_firmware:*:*:*:*:*:*:*:* | 1.1 (mitigations or upgrade); 1.2.3 before 1.2.3.20; 2.0 before 2.0.0.13; 2.1 (no fixed revision in Update A); 2.2.2 before 2.2.2.3; 2.2.3 before 2.2.3.2 (CISA ICSA-21-096-01 Update A) |
| Relion 670/650 and 670/650/SAM600-IO series 2.2.x | cpe:2.3:o:hitachienergy:relion_650_firmware:*:*:*:*:*:*:*:* | 2.2.0 before 2.2.0.13; 2.2.1 before 2.2.1.6 (CISA ICSA-21-096-01 Update A; SAM600-IO CPE relion_sam600-io_firmware) |
| Relion 650 series 1.x | cpe:2.3:o:hitachienergy:relion_650_firmware:*:*:*:*:*:*:*:* | 1.1 (no fixed revision in Update A); 1.2 (mitigations or upgrade to 1.3); 1.3 before 1.3.0.7 (CISA ICSA-21-096-01 Update A) |
| REB500 busbar protection | cpe:2.3:o:hitachienergy:reb500_firmware:*:*:*:*:*:*:*:* | 7.3, 7.4, 7.5 (migrate to 7.60.19); 7.6 before 7.60.19; 8.2 before 8.2.0.5; 8.3 before 8.3.1.0 (CISA; NVD marks 8.3 up to and including 8.3.1.0) |
| RTU500 series CMU firmware | cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:* | 7.x to 12.x; fix 12.6.1.0, target releases 12.4.10.0, 12.2.11.0 and 12.0.14.0 for the older 12.x branches; release 11 and older: migrate to release 12 (CISA ICSA-21-096-01 Update A; NVD lists only 7.0 to 12.0) |
| FOX615 (TEGO1) | cpe:2.3:o:hitachienergy:fox615_tego1_firmware:*:*:*:*:*:*:*:* | R1D02 and earlier; fixed in R2A16 and later (CISA ICSA-21-096-01 Update A) |
| MSM, GMS600, PWC600 | cpe:2.3:o:hitachienergy:pwc600_firmware:*:*:*:*:*:*:*:* | MSM before 2.1.0; GMS600 1.3.0 and earlier (fix 1.3.1); PWC600 1.0 before 1.0.1.4 and 1.1 before 1.1.0.1 (CISA ICSA-21-096-01 Update A) |
What does this mean for affected devices?
NVD carries the CVE description: an attacker "with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), the same as the score in the MITRE CNA record and in CISA's advisory; NVD and CISA list CWE-20. The record was published on 2021-06-14 (NVD, CVE record).
Which products and fixes does CISA list?
CISA's ICSA-21-096-01, first published on 2021-04-06 and updated on 2021-04-20 (Update A, CSAF), republishes Hitachi ABB Power Grids' fixes. The vendor is now Hitachi Energy.
- Relion 670: 1.2.3.20, 2.0.0.13, 2.2.2.3 and 2.2.3.2 for those lines; 670 1.1 should apply the mitigations or upgrade; 670 2.1 had no fixed revision in Update A.
- Relion 670/650: 2.2.0.13; Relion 670/650/SAM600-IO: 2.2.1.6.
- Relion 650: 1.3.0.7; 650 1.2 should apply the mitigations or move to 1.3; 650 1.1 had no fixed revision in Update A.
- REB500: 7.60.19, 8.2.0.5 and 8.3.1.0; REB500 7.3 to 7.5 should migrate to 7.60.19 or later.
- RTU500 CMU: 12.6.1.0, with 12.4.10.0, 12.2.11.0 and 12.0.14.0 named as target releases for the older 12.x branches; release 11 and older should migrate to release 12.
- FOX615 (TEGO1) R2A16 and later, MSM 2.1.0 and later, GMS600 1.3.1, PWC600 1.0.1.4 and 1.1.0.1.
NVD's CPE differs in places. It marks REB500 8.3 up to and including 8.3.1.0, the build CISA names as the fix, and it lists RTU500 only as versions 7.0 to 12.0, so a CPE match will not flag an RTU500 on, for example, 12.4.x.
What if a device cannot be updated?
The vendor's strongest mitigation is not connecting the affected products to any station network through the LAN port "should make above attack physically impossible", with switching commands given through hardwired binary inputs instead. Otherwise CISA repeats the vendor's firewall and zoning practices and the per-product cybersecurity deployment guidelines. CISA notes that the primary functionality of the device is not available during the reboot phase.
The ABB AC500, RTU500 and Relion guide explains why these products sit under both ABB and Hitachi Energy. Related flaws include CVE-2023-4518, a GOOSE reboot in Relion 670/650, and CVE-2019-18253, a Relion 670 path traversal over the same IEC 61850 interface. The IEC 61850 security guide covers MMS and GOOSE exposure, and the input handling fix guide covers the class.
CVE-2021-27196 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01575, the 76.1st percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2021-06-14; NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, MITRE Secondary 7.5; CWE-20 (NVD); CPE Relion 670/650/SAM600-IO ranges, REB500 8.3 up to and including 8.3.1.0, RTU500 7.0 to 12.0 exact versions, FOX615 TEGO1 before r2a16, MSM before 2.1.0, GMS600 up to 1.3.0, PWC600 ranges. — NVD
- CISA ICSA-21-096-01 Update A CSAF (initial 2021-04-06, current 2021-04-20), read 2026-11-23: CWE-20, CVSS v3 7.5; reboot, device inoperable about 60 seconds; per-product fixes as listed on the page; RTU500 12.6.1.0 plus 12.4.10.0, 12.2.11.0, 12.0.14.0 as target releases; mitigation: no station network connection through the LAN port; no known public exploits; primary functionality unavailable during reboot. — CISA ICSA-21-096-01
- CVE record (checked 2026-11-23): see body; state PUBLISHED. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.01575, percentile 0.76082, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
How long is the device down after the attack?
About 60 seconds, according to the CVE description and CISA ICSA-21-096-01. CISA notes the primary functionality is not available during the reboot phase.
Which RTU500 firmware fixes CVE-2021-27196?
CISA ICSA-21-096-01 Update A names RTU500 CMU firmware 12.6.1.0, with 12.4.10.0, 12.2.11.0 and 12.0.14.0 as target releases for the older 12.x branches. Release 11 and older should migrate to release 12.
What does the attacker need to know?
Access to the IEC 61850 network, knowledge of how to reproduce the attack and the IP addresses of the IEC 61850 access points of the target devices. Only products with IEC 61850 interfaces are affected.
Is CVE-2021-27196 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.01575 (76.1st percentile) in the 2026-11-22 dataset.