CVE-2021-35535 is an insecure boot image flaw in Hitachi Energy Relion 670, 650 and SAM600-IO protection and control devices. For a short time during boot an older VxWorks runs, and an attacker on the front network port who can force reboots can exploit it. NVD and Hitachi Energy score it 8.1. Versions 2.2.1.7, 2.2.2.5, 2.2.3.4 and 2.2.4.3 fix it.
Vulnerability summary
CVSS base score
8.1
High severity
EPSS score (FIRST)
0.7%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-35535 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Hitachi Energy Relion 670 series | cpe:2.3:o:hitachienergy:relion_670_firmware:*:*:*:*:*:*:*:* | 2.2.0 all revisions (no fix, apply mitigation factors); 2.2.1 up to 2.2.1.6 (fix 2.2.1.7); 2.2.2 up to 2.2.2.4 (fix 2.2.2.5); 2.2.3 up to 2.2.3.3 (fix 2.2.3.4); 2.2.4 up to 2.2.4.2 (fix 2.2.4.3) (CISA ICSA-21-336-05, Hitachi Energy 8DBD000061, revision 2025-05-27) |
| Hitachi Energy Relion 650 series | cpe:2.3:o:hitachienergy:relion_650_firmware:*:*:*:*:*:*:*:* | 2.2.0 all revisions (no fix); 2.2.1 up to 2.2.1.6 (fix 2.2.1.7); 2.2.4 up to 2.2.4.2 (fix 2.2.4.3) (CISA ICSA-21-336-05) |
| Hitachi Energy SAM600-IO series | cpe:2.3:o:hitachienergy:relion_sam600-io_firmware:2.2.1:*:*:*:*:*:*:* | 2.2.1 up to 2.2.1.6; fix 2.2.1.7 (CISA ICSA-21-336-05) |
What does this mean for affected devices?
Hitachi Energy, the CNA, describes a "tiny time gap during the booting process where an older version of VxWorks is loaded prior to application firmware booting." An attacker who gets access to the front network port and can cause reboot sequences may exploit flaws in that older VxWorks. The two primary texts differ on impact: the CVE record calls the result a denial of service, while Hitachi Energy's advisory 8DBD000061, republished verbatim by CISA as ICSA-21-336-05 (CSAF), says the older VxWorks "is susceptible to Urgent/11 of which successful exploitation allows for remote code execution on the device before operating system is loaded." NVD's Primary score is CVSS v3.1 8.1 (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H), with a CVSS v2 6.8. Hitachi Energy and CISA reach the same 8.1 with a local vector and changed scope (AV:L/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H). All list CWE-1188. The record was published on 2021-11-18 (NVD, CVE record).
Which versions are fixed?
The advisory was revised on 2021-12-07 and again on 2025-05-27 with updated affected versions and actions. As of that revision: Relion 670 and 650 2.2.4 up to 2.2.4.2 are fixed in 2.2.4.3; Relion 670 2.2.3 up to 2.2.3.3 in 2.2.3.4; Relion 670 2.2.2 up to 2.2.2.4 in 2.2.2.5; Relion 670, 650 and SAM600-IO 2.2.1 up to 2.2.1.6 in 2.2.1.7. For Relion 670 and 650 2.2.0, all revisions, the only listed action is the general mitigation factors. The CVE record's text still says "2.2.3 versions prior to 2.2.3.3", while the CSAF and NVD's CPE include 2.2.3.3 in the affected range; 2.2.3.4 is the fixed build. U.S. Department of Energy CyTRICS researcher Riley Barello Myers reported the flaw.
Mitigation
The attack needs the front network port, which is meant for local engineering access, and the ability to make the device reboot. Hitachi Energy's general mitigation factors: physically protect process control systems from unauthorized personnel, keep them off the Internet, and separate them from other networks with a firewall that exposes a minimal number of ports. Restrict who can reach the front port of each IED. The ABB AC500, RTU500 and Relion guide covers the Relion 670 and 650 advisories, CVE-2022-3864 is a later Relion 670/650 flaw fixed in 2.2.x builds, and the secure boot guide covers verifying every boot stage.
CVE-2021-35535 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00667, the 52.8th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2021-11-18; NVD Primary CVSS v3.1 8.1 AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H and CVSS v2 6.8; Hitachi Energy Secondary 8.1 AV:L/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H; CWE-1188; CPE relion_670_firmware 2.2.0, 2.2.1, 2.2.2, 2.2.3 to including 2.2.3.3, 2.2.4; relion_650_firmware 2.2.0, 2.2.1, 2.2.4; relion_sam600-io_firmware 2.2.1. — NVD
- CISA ICSA-21-336-05 CSAF, verbatim republication of Hitachi Energy PSIRT 8DBD000061 (initial 2021-11-04, revisions 2021-12-07 and 2025-05-27), read 2026-11-23: affected ranges per series; fixes 2.2.4.3, 2.2.3.4, 2.2.2.5, 2.2.1.7; 2.2.0 all revisions: apply general mitigation factors; older VxWorks susceptible to URGENT/11, RCE before OS loads; CWE-1188, CVSS 8.1 AV:L/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H; acknowledgment DOE CyTRICS. — CISA ICSA-21-336-05
- CVE record (checked 2026-11-23): state PUBLISHED; CNA Hitachi Energy; description says denial of service; affected Relion 670 2.2.2 all, 2.2.3 prior to 2.2.3.3, Relion 670/650 2.2.0 and 2.2.4 all, Relion 670/650/SAM600-IO 2.2.1 all; credit DOE CyTRICS researcher Riley Barello Myers. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.00667, percentile 0.52835, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Relion firmware fixes CVE-2021-35535?
Hitachi Energy's advisory as republished by CISA (revision of 2025-05-27) names 2.2.1.7, 2.2.2.5, 2.2.3.4 and 2.2.4.3, each for its own 2.2.x line. Relion 670 and 650 2.2.0 has no listed fix; only the general mitigation factors apply.
Is this a denial of service or remote code execution?
The sources differ. The CVE record says denial of service. Hitachi Energy's advisory, republished by CISA, says the older VxWorks loaded during boot is susceptible to URGENT/11, which allows remote code execution before the operating system loads.
What access does an attacker need?
Access to the front network port of the device and the ability to cause reboot sequences, according to Hitachi Energy. Physically protecting the IEDs and limiting who can connect to the front port reduces the exposure.
Is CVE-2021-35535 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.00667 (52.8th percentile) in the 2026-11-22 dataset.