Security Advisory

CVE-2021-36763: CODESYS WebVisu File Read on WAGO PLCs

Last updated:
  • CVE-2021-36763

CVE-2021-36763 is a file access flaw in the CODESYS V3 web server before V3.5.17.10. Web requests without a login can read every file in the controller's visu folder, including private files that may hold user IDs and password hashes of visualisation users. WAGO PFC100, PFC200, CC100 and Touch Panel 600 are affected until FW22. NVD scores it 7.5.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2021-36763 · Source: NVD

Affected components

ComponentCPEVersion range
WAGO PFC100 750-8100, 750-8101, 750-8102—up to and including 03.09.05 (21); fixed in 03.10.08 (22) (CERT@VDE VDE-2022-035; no WAGO device CPE in NVD)
WAGO PFC200 750-8202 to 750-8216—up to and including 03.09.05 (21); fixed in 03.10.08 (22) (CERT@VDE VDE-2022-035; no WAGO device CPE in NVD)
WAGO Compact Controller CC100 751-9301—up to and including 03.09.07 (21); fixed in 03.10.09 (22) (CERT@VDE VDE-2022-035; no WAGO device CPE in NVD)
WAGO Touch Panel 600 (762-4x0x, 762-5x0x, 762-6x0x)—up to and including 03.07.14 (19); fixed in 03.10.09 (22) (CERT@VDE VDE-2022-035; no WAGO device CPE in NVD)
WAGO Edge Controller EC300 752-8303/8000-0002—up to and including 03.07.14 (19) (CERT@VDE VDE-2022-035 names no separate fixed version)
CODESYS V3 runtimes with CmpWebServer (Control RTE, Control Win, HMI, Runtime System Toolkit, Embedded and Remote Target Visu Toolkit)cpe:2.3:a:codesys:control_runtime_system_toolkit:*:*:*:*:*:*:*:*before V3.5.17.10; fixed in V3.5.17.10 (CODESYS Advisory 2021-11, NVD before 3.5.17.10)
CODESYS Control for PFC100 SL, PFC200 SL and WAGO Touch Panels 600 SLcpe:2.3:a:codesys:control:*:*:*:*:*:wago_touch_panels_600_sl:*:*before V4.2.0.0; fixed in V4.2.0.0 (CODESYS Advisory 2021-11, NVD)

What does this mean for affected devices?

NVD's description reads: "In CODESYS V3 web server before 3.5.17.10, files or directories are accessible to External Parties." NVD scores it CVSS v3.1 7.5 Primary (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N, v2 5.0) with CWE-552; the record dates from 2021-08-03 (NVD, CVE record). WAGO's CERT@VDE advisory gives the same 7.5.

What can an attacker read?

CODESYS Advisory 2021-11 (published 30 August 2021) explains the scope. The web server that serves WebVisu screens lets "specific web server requests" read "all files stored in the 'visu' subfolder/placeholder of the PLC's file system". Next to the public files the visualisation needs, "there may exist also private files, which may contain user IDs and password hashes of visualization users". CODESYS stresses that "the runtime user management itself is not affected". So the leak is limited to visualisation accounts, but a recovered password often works elsewhere on the same plant. The fix is V3.5.17.10 for the V3 runtimes and V4.2.0.0 for the SL packages, among them CODESYS Control for PFC100 SL, PFC200 SL and WAGO Touch Panels 600 SL. Witali Rempel of Eaton Industries reported it.

Which WAGO devices are affected?

WAGO's VDE-2022-035, released on 2022-08-17 (CSAF), lists the same firmware limits as for the web server heap overflow CVE-2021-33485: PFC100 and PFC200 up to 03.09.05 (21), CC100 up to 03.09.07 (21), and the Touch Panel 600 and Edge Controller EC300 up to 03.07.14 (19). WAGO tells PFC100 and PFC200 users to install 03.10.08 (22) or later, and TP600 and CC100 users 03.10.09 (22) or later. NVD's CPE list names only CODESYS products.

What should operators do?

Update to FW22 or later. CODESYS names no workaround, so until then keep the controller web server off networks that do not need it. After the update, change the passwords of all WebVisu users, since their hashes may already have been copied, and do not reuse them for the runtime or the WAGO web-based management. Weak runtime password hashing on the same controllers is CVE-2020-12069, and credentials sent without TLS are CVE-2019-9013. See the WAGO PFC controller guide, the CODESYS runtime guide and the path traversal fix guide.

CVE-2021-36763 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01215, the 69.3rd percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2021-08-03; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N, v2 5.0; CWE-552; CPE CODESYS V3 runtimes before 3.5.17.10 and SL products incl. wago_touch_panels_600_sl; no WAGO device CPE. — NVD
  • CODESYS Advisory 2021-11 (published 30 August 2021): CWE-552; web server requests can read all files in the visu subfolder, private files may contain user IDs and password hashes of visualization users; runtime user management not affected; CVSS v3.0 7.5; fixed in V3.5.17.10 and V4.2.0.0 for SL products; reported by Witali Rempel, Eaton Industries GmbH. — CODESYS Advisory 2021-11
  • CERT@VDE VDE-2022-035 (released 2022-08-17), HTML and CSAF read 2026-11-23: CVE-2021-36763 CVSS 7.5 CWE-552; known affected CC100 <=03.09.07(21), EC300 <=03.07.14(19), PFC100/PFC200 <=03.09.05(21), TP600 <=03.07.14(19); update PFC100/PFC200 to 03.10.08(22), TP600/CC100 to 03.10.09(22). — CERT@VDE VDE-2022-035
  • CVE record (checked 2026-11-23): state PUBLISHED, assigner MITRE, published 2021-08-03. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.01215, percentile 0.69333, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CERT@VDE VDE-2022-035: WAGO multiple product series affected by multiple CODESYS vulnerabilities
  3. CERT@VDE VDE-2022-035 CSAF (machine-readable advisory)
  4. CODESYS Advisory 2021-11: Security update for CODESYS V3 web server file access
  5. CVE.org record CVE-2021-36763
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which WAGO firmware fixes CVE-2021-36763?

03.10.08 (22) or later for PFC100 and PFC200, and 03.10.09 (22) or later for Touch Panel 600 and CC100 (CERT@VDE VDE-2022-035).

Are the runtime user passwords exposed?

No. CODESYS says the runtime user management is not affected; the exposed files are those in the visu folder, which may contain user IDs and password hashes of visualisation users.

What should I do after updating?

Change the passwords of all WebVisu users, because their hashes may already have been read, and make sure they differ from runtime and web-based management passwords.

Is CVE-2021-36763 in the CISA KEV catalog?

No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.01215 (69.3rd percentile) in the 2026-11-22 dataset.