Security Advisory

CVE-2021-27459: Rosemount X-STREAM Unvalidated File Upload

Last updated:
  • CVE-2021-27459

CVE-2021-27459 is an unrestricted file upload flaw (CWE-434) in the web server of Emerson Rosemount X-STREAM enhanced gas analyzers (XEGP, XEGK, XEXF and XEFD). The analyzer accepts unvalidated files, which an attacker could use to execute code on it. NVD scores it 9.8 and CISA 7.1. Emerson released new firmware through its technical support.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.8%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2021-27459 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Emerson Rosemount X-STREAM enhanced XEGP gas analyzercpe:2.3:o:emerson:x-stream_enhanced_xegp_firmware:*:*:*:*:*:*:*:*All revisions before Emerson's 2021 firmware release (CISA ICSA-21-138-01 lists all versions and names no fixed version number); fix: new firmware from Emerson technical support
Emerson Rosemount X-STREAM enhanced XEGK gas analyzercpe:2.3:o:emerson:x-stream_enhanced_xegk_firmware:*:*:*:*:*:*:*:*All revisions before Emerson's 2021 firmware release (CISA ICSA-21-138-01 lists all versions and names no fixed version number); fix: new firmware from Emerson technical support
Emerson Rosemount X-STREAM enhanced XEXF gas analyzercpe:2.3:o:emerson:x-stream_enhanced_xexf_firmware:*:*:*:*:*:*:*:*All revisions before Emerson's 2021 firmware release (CISA ICSA-21-138-01 lists all versions and names no fixed version number); fix: new firmware from Emerson technical support
Emerson Rosemount X-STREAM enhanced XEFD gas analyzercpe:2.3:o:emerson:x-stream_enhanced_xefd_firmware:*:*:*:*:*:*:*:*All revisions before Emerson's 2021 firmware release (CISA ICSA-21-138-01 lists all versions and names no fixed version number); fix: new firmware from Emerson technical support

What does this mean for affected devices?

The CVE record from CISA says: "The webserver of the affected products allows unvalidated files to be uploaded, which an attacker could utilize to execute arbitrary code." NVD's Primary score is CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). CISA, which handled the disclosure, scored it lower in its advisory: CVSS v3.0 7.1 (AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:H/A:N), assuming the attacker already has a low-privilege login. Both use CWE-434, unrestricted upload of file with dangerous type. NVD published the record on 2021-05-20; its configuration lists X-STREAM enhanced XEGP, XEGK, XEFD and XEXF firmware without a version boundary (NVD, CVE record).

What is affected?

CISA's ICSA-21-138-01, released on 2021-05-18, covers all versions of the Rosemount X-STREAM enhanced gas analyzer models XEGP, XEGK, XEXF and XEFD; Emerson reported the issues to CISA. The same advisory lists five more CVEs in the analyzers' web interface: weak encoding of stored passwords (CVE-2021-27457), path traversal (CVE-2021-27461), persistent cookies holding sensitive data (CVE-2021-27463), cross-site scripting (CVE-2021-27465) and clickjacking (CVE-2021-27467). CISA reported no known public exploits.

How do you fix CVE-2021-27459?

Emerson recommends updating the analyzer firmware: a new release addresses all six issues, and owners get it by contacting Emerson's Hasselroth technical support team (the address is in the CISA advisory). CISA does not give a version number. Emerson also asks owners to:

  • keep the analyzers on a well-protected network, segmented from the internet;
  • set web browsers used to reach the analyzer so they do not store login names and passwords;
  • follow the guidance on Emerson's security notifications page.

Other Emerson process instrument flaws on this site are CVE-2023-46687 in Rosemount gas chromatographs and CVE-2014-9191 in Emerson HART DTMs; the Emerson DeltaV, Ovation and ROC guide collects the Emerson advisories, and the patch management guide covers scheduling firmware updates on field devices. Another upload flaw in OT software is CVE-2021-32955 in Delta DIAEnergie.

Is CVE-2021-27459 exploited?

CVE-2021-27459 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01752, the 78.34th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2021-05-20; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 7.5; CWE-434 from ICS-CERT; CPEs emerson x-stream_enhanced_xegp/xegk/xefd/xexf_firmware (no version), running on the matching hardware. — NVD
  • CISA ICSA-21-138-01 CSAF (released 2021-05-18, read 2026-11-27): X-STREAM enhanced XEGP, XEGK, XEXF, XEFD, all versions; CVE-2021-27459 CWE-434 CVSS v3.0 7.1 AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:H/A:N; siblings CVE-2021-27457 (CWE-326), 27461 (CWE-22), 27463 (CWE-539), 27465 (CWE-79), 27467 (CWE-1021); Emerson recommends updating firmware, new release available via [email protected]; segment from the internet; configure browsers not to store credentials; Emerson reported to CISA; no known public exploits. — CISA ICSA-21-138-01
  • CVE record (checked 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2021-05-20; the record carries no CNA CVSS metric; affected product Emerson Rosemount X-STREAM Gas Analyzer; reference is the CISA advisory. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.01752, percentile 0.78344, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-21-138-01: Emerson Rosemount X-STREAM (CSAF)
  3. CISA ICSA-21-138-01 advisory page
  4. CVE.org record CVE-2021-27459
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which X-STREAM models does CVE-2021-27459 affect?

The Rosemount X-STREAM enhanced XEGP, XEGK, XEXF and XEFD gas analyzers, all versions before Emerson's firmware update (CISA ICSA-21-138-01).

How do I get the fixed firmware?

CISA's advisory says the new firmware is obtained by contacting Emerson technical support in Hasselroth; no version number is published. The same release fixes the other five CVEs in the advisory.

Why do NVD and CISA scores differ for CVE-2021-27459?

NVD's 9.8 assumes no login is needed and full impact. CISA's 7.1 assumes a low-privilege user and limited confidentiality impact with no availability impact. Treat it as critical if the web interface is reachable from untrusted networks.

Is CVE-2021-27459 in the CISA KEV catalog?