CVE-2021-27384 is an out-of-bounds memory access in SmartVNC on Siemens SIMATIC HMI Comfort and KTP Mobile Panels, WinCC Runtime Advanced V15 and V16, and the HMI panels in SINAMICS medium-voltage drives. The flaw sits in the SmartVNC device layout handler and can potentially result in code execution. NVD and Siemens score it CVSS 9.8. Siemens fixed it in V15.1 Update 6 and V16 Update 4.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
2.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-27384 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC HMI Comfort Panels 4" to 22", Comfort Outdoor Panels 7" and 15" (incl. SIPLUS), KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900, KTP900F | cpe:2.3:o:siemens:simatic_hmi_comfort_panels_4\"_firmware:*:*:*:*:*:*:*:* | V15 panels before V15.1 Update 6; V16 panels before V16 Update 4. Fix: update WinCC (TIA Portal) to V15.1 Update 6 or V16 Update 4 or later, then update the panel (Siemens SSA-538778) |
| Siemens SIMATIC WinCC Runtime Advanced V15 and V16 | cpe:2.3:a:siemens:simatic_wincc_runtime_advanced:*:*:*:*:*:*:*:* | V15 before V15.1 Update 6; V16 before V16 Update 4; fixed in V15.1 Update 6 and V16 Update 4 or later |
| Siemens SINAMICS GH150, GL150 (option X30), GM150 (option X30), SH150, SL150, SM120, SM150, SM150i | cpe:2.3:o:siemens:sinamics_gh150_firmware:*:*:*:*:*:*:*:* | All versions, through the built-in SIMATIC HMI panel image (images before V16 Update 4, or before V15 SP1 Update 6 for SL150, SM150 and SM150i). Mitigation: update the HMI panel image, or disable Sm@rtServer (CISA ICSA-21-131-04) |
What does this mean for affected devices?
NVD's description, from Siemens, says: "SmartVNC has an out-of-bounds memory access vulnerability in the device layout handler, represented by a binary data stream on client side, which can potentially result in code execution." It lists SIMATIC HMI Comfort Panels 4" to 22", Comfort Outdoor Panels 7" and 15" and KTP Mobile Panels (KTP400F, KTP700, KTP700F, KTP900, KTP900F) before V15.1 Update 6 or V16 Update 4, WinCC Runtime Advanced V15 and V16 before the same updates, and eight SINAMICS medium-voltage drive families. NVD's Primary scores are CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and CVSS v2 7.5. NVD has not assigned its own CWE; Siemens gives CWE-788 (access of memory location after end of buffer) (NVD, CVE record).
What does Siemens say?
Siemens advisory SSA-538778 ("SmartVNC Vulnerabilities in SIMATIC HMI/WinCC Products", first published 2021-05-11, current version 3 of 2021-10-12) scores the flaw CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C). The panel fix is two steps: update WinCC (TIA Portal) to V15.1 Update 6 or V16 Update 4 or later, then update the panel to the same version. WinCC Runtime Advanced is fixed in V15.1 Update 6 and V16 Update 4 or later. Siemens' mitigation for every listed product is to restrict access to port 5900/tcp to trusted IP addresses only.
What about SINAMICS drives?
SINAMICS GH150, GL150 and GM150 (with option X30), SH150, SL150, SM120, SM150 and SM150i carry a SIMATIC HMI Comfort Panel. CISA advisory ICSA-21-131-04 (CSAF), which republishes Siemens SSA-286838, says only HMI image versions before V16 Update 4 (before V15 SP1 Update 6 for SL150, SM150 and SM150i) are affected, and that owners should update the HMI panel image in the drive. Its other mitigations are to restrict port 5900/tcp and to disable Sm@rtServer in the panel; CISA notes that Sm@rtServer is disabled by default but can be enabled on request by the system integrator.
What does CISA say about the panels?
CISA advisory ICSA-21-131-12 (CSAF), "Siemens SIMATIC SmartVNC HMI WinCC Products (Update B)", gives CVSS v3.1 9.8 and CWE-788 with the same panel and Runtime Advanced fixes.
What should an owner do?
- Update WinCC (TIA Portal) and then each panel, or the Runtime Advanced PC, to V15.1 Update 6 or V16 Update 4 or later.
- Where SmartVNC or Sm@rtServer is not used, leave it switched off; where it is, allow 5900/tcp only from named engineering hosts.
- For SINAMICS drives, ask the system integrator which HMI image the drive panel runs before planning the update.
The Siemens WinCC and PCS 7 guide covers the Runtime Advanced and HMI panel line. CVE-2020-15786 is a Sm@rt Server brute-force flaw on the same panels, and CVE-2011-3321 is an older memory corruption flaw in the WinCC flexible and Runtime Advanced loader. The memory corruption guide explains how this class of bug is removed from device firmware.
CVE-2021-27384 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.02608, a percentile of 86.1, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2021-05-12; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H and CVSS v2 7.5; no NVD CWE, Siemens CWE-788; CPEs for Comfort, Comfort Outdoor and KTP Mobile panel firmware and WinCC Runtime Advanced before 15.1 Update 6 / 16 Update 4, and SINAMICS firmware all versions. — NVD
- Siemens SSA-538778 CSAF version 3, 2021-10-12 (read 2026-11-28): CVSS v3.1 9.8 with E:P/RL:O/RC:C; fix: update WinCC (TIA Portal) to V15.1 Update 6 or V16 Update 4 or later, then the panel; Runtime Advanced V15.1 Update 6 / V16 Update 4; restrict 5900/tcp. — Siemens ProductCERT SSA-538778
- CISA ICSA-21-131-12 CSAF (read 2026-11-28): CVSS v3.1 9.8, CWE-788, same fixes. — CISA ICSA-21-131-12
- CISA ICSA-21-131-04 CSAF (read 2026-11-28, Siemens SSA-286838): SINAMICS medium-voltage drives; only HMI images before V16 Update 4 (V15 SP1 Update 6 for SL150, SM150, SM150i) affected; update panel image, restrict 5900/tcp, disable Sm@rtServer (disabled by default). — CISA ICSA-21-131-04
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.02608, percentile 0.86143, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
- NVD
- Siemens SSA-538778: SmartVNC Vulnerabilities in SIMATIC HMI/WinCC Products
- CISA ICSA-21-131-12: Siemens SIMATIC SmartVNC HMI WinCC Products
- CISA ICSA-21-131-12 CSAF (machine-readable advisory)
- CISA ICSA-21-131-04: Siemens SINAMICS Medium Voltage Products Remote Access
- CVE record CVE-2021-27384 (CVE Services JSON)
- CISA KEV
- FIRST EPSS
Frequently asked questions
How is a panel updated for CVE-2021-27384?
Siemens SSA-538778 describes two steps: update WinCC (TIA Portal) to V15.1 Update 6 or V16 Update 4 or later, then update the panel to the same version. WinCC Runtime Advanced is updated directly to V15.1 Update 6 or V16 Update 4.
Which port should be restricted?
Siemens' mitigation is to restrict access to port 5900/tcp to trusted IP addresses only.
Are SINAMICS drives affected?
Yes, through their built-in SIMATIC HMI panel. CISA ICSA-21-131-04 says only HMI images before V16 Update 4 (before V15 SP1 Update 6 for SL150, SM150 and SM150i) are affected, and Sm@rtServer is disabled by default unless the integrator enabled it.
Is CVE-2021-27384 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.02608 (percentile 86.1) in the 2026-11-27 dataset.
Questions about this page?