Security Advisory

CVE-2011-3321: WinCC flexible Runtime Loader Heap Overflow

Last updated:
  • CVE-2011-3321

CVE-2011-3321 is a heap-based buffer overflow in the Runtime Loader of Siemens SIMATIC WinCC flexible Runtime and WinCC (TIA Portal) V11 Runtime Advanced. When transfer mode is switched on, the loader listens on TCP port 2308, and a crafted packet can crash it or possibly run code. NVD scores it 9.3 (CVSS v2). Siemens released no patch; the mitigation is to keep transfer mode off except while loading a project.

Vulnerability summary

CVSS base score

9.3

Critical severity

EPSS score (FIRST)

7.1%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2011-3321 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Siemens SIMATIC WinCC flexible Runtime (WinCC flexible 2005 to 2008 SP2); SIMATIC WinCC (TIA Portal) V11 Runtime Advancedcpe:2.3:a:siemens:simatic_wincc_flexible_runtime:*:*:*:*:*:*:*:*Siemens SSA-460621: SIMATIC WinCC flexible 2005, 2005 SP1, 2007, 2008, 2008 SP1, 2008 SP2 and TIA Portal V11; NVD CPE: all simatic_wincc_flexible_runtime versions and simatic_wincc_runtime advanced. No patch: keep the Runtime Loader transfer mode disabled except during transfers

What does this mean for affected devices?

NVD's description reads: "Heap-based buffer overflow in the Siemens WinCC Runtime Advanced Loader, as used in SIMATIC WinCC flexible Runtime and SIMATIC WinCC (TIA Portal) Runtime Advanced, allows remote attackers to cause a denial of service (memory corruption) or possibly execute arbitrary code via a crafted packet to TCP port 2308." NVD's Primary score is CVSS v2 9.3 (AV:N/AC:M/Au:N/C:C/I:C/A:C) with CWE-119; there is no NVD v3 score. NVD published the record on 2011-09-16; CERT/CC assigned it with no CNA score (NVD, CVE record).

What does Siemens say?

Siemens advisory SSA-460621 (V1.2, external publication 2011-09-05) lists SIMATIC WinCC flexible 2005, 2005 SP1, 2007, 2008, 2008 SP1 and 2008 SP2 plus TIA Portal V11 as affected. It explains that the runtime loader listens on TCP port 2308 only "if the transfer mode is activated", and that it does not sanitize its input. Siemens scores the flaw lower than NVD: CVSS v2 base 7.9 and temporal 7.5 (AV:A/AC:M/Au:N/C:C/I:C/A:C/E:F/RL:U/RC:C), because the attacker needs access to the network where the loader runs and transfer mode must be on. Billy Rios and Terry McCorkle reported it.

What does CISA say?

CISA advisory ICSA-11-244-01 (CSAF), "Siemens WinCC Flexible Runtime Heap Overflow", scores it CVSS v2 9.3 with CWE-119. It records that Siemens would not patch the loader: the Runtime Loader feature "is disabled by default and is only used when updating firmware", and Siemens updated the product documentation to tell users to disable it except when it is actively in use. CISA also advises monitoring traffic to 2308/TCP.

How do I mitigate it?

  1. Leave the Runtime Loader transfer mode off on every panel and runtime PC; switch it on only for the time it takes to load a project or firmware.
  2. Block or watch TCP port 2308 at the cell boundary so only the engineering station can reach it.
  3. Keep HMI networks behind a firewall and away from the internet, as CISA's recommended practices say.

CVE-2011-4509 covers the HMI web server default password on the same WinCC flexible panels, and CVE-2019-10929 is a later Siemens SIMATIC flaw. The memory corruption guide explains how vendors remove this class of bug, and the OT/ICS security guide for small manufacturers covers segmenting HMIs.

CVE-2011-3321 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0707, a percentile of 95.0, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2011-09-16; NVD Primary CVSS v2 9.3 AV:N/AC:M/Au:N/C:C/I:C/A:C; no v3 metric; CWE-119; CPEs simatic_wincc_flexible_runtime (all versions) and simatic_wincc_runtime advanced. — NVD
  • CISA ICSA-11-244-01 CSAF (read 2026-11-28): CWE-119, CVSS v2 9.3; WinCC flexible Runtime and WinCC (TIA Portal) Runtime Advanced; no patch; loader disabled by default and only used when updating firmware; documentation updated; monitor 2308/TCP. — CISA ICSA-11-244-01
  • Siemens SSA-460621 V1.2 PDF (read 2026-11-28): affected WinCC flexible 2005 to 2008 SP2 and TIA Portal V11; transfer mode listens on TCP 2308; CVSS v2 base 7.9, temporal 7.5 AV:A/AC:M/Au:N/C:C/I:C/A:C/E:F/RL:U/RC:C; credit Billy Rios and Terry McCorkle. — Siemens ProductCERT SSA-460621
  • CVE record (read 2026-11-28): state PUBLISHED, assigner certcc; affected n/a; no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.07070, percentile 0.94976, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-11-244-01: Siemens WinCC Flexible Runtime Heap Overflow
  3. CISA ICSA-11-244-01 CSAF (machine-readable advisory)
  4. Siemens SSA-460621: WinCC flexible Runtime Loader memory corruption
  5. CVE record CVE-2011-3321 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Is there a Siemens patch for CVE-2011-3321?

No. CISA ICSA-11-244-01 records that Siemens did not patch the Runtime Loader. Instead it updated the WinCC flexible documentation to tell users to keep the loader disabled except while it is actively used for a transfer.

When is TCP port 2308 open on a WinCC flexible panel?

Only when the Runtime Loader transfer mode is activated. Siemens SSA-460621 says the loader then listens on TCP 2308; the feature is off by default and is used for loading projects and firmware.

Why do Siemens and NVD give different scores?

NVD scores it CVSS v2 9.3 with a network attack vector. Siemens scores it base 7.9 and temporal 7.5 with an adjacent-network vector, because the attacker must reach the network where the loader runs and transfer mode must be on.

Is CVE-2011-3321 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0707 (percentile 95.0) in the 2026-11-27 dataset.