Security Advisory

CVE-2020-15786: SIMATIC HMI Sm@rt Server Brute Force

Last updated:
  • CVE-2020-15786

CVE-2020-15786 is a missing brute-force protection in the Sm@rt Server of Siemens SIMATIC HMI panels: Basic Panels 2nd Generation, Comfort Panels, Mobile Panels and Unified Comfort Panels insufficiently block repeated login attempts, so a remote attacker could guess user passwords and take over Sm@rt Server access. NVD scores it CVSS 9.8, Siemens 6.5. Siemens fixed it in V16 Update 3, and in V16 Update 5 for Unified Comfort Panels.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-15786 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Siemens SIMATIC HMI Basic Panels 2nd Generation, Comfort Panels and Mobile Panels (incl. SIPLUS variants)cpe:2.3:o:siemens:simatic_hmi_comfort_panels_firmware:*:*:*:*:*:*:*:*CVE description: Basic Panels 2nd Generation before V16; Comfort Panels and Mobile Panels V16 and earlier. Fixed in V16 Update 3 (Siemens SSA-542525). NVD CPE for the Basic Panels 2nd Generation firmware stops at version 14
Siemens SIMATIC HMI Unified Comfort Panelscpe:2.3:o:siemens:simatic_hmi_united_comfort_panels_firmware:*:*:*:*:*:*:*:*V16 and earlier; fixed in V16 Update 5 (NVD's CPE spells the product "united_comfort_panels")

What does this mean for affected devices?

NVD's description, from Siemens, reads: "Affected devices insufficiently block excessive authentication attempts. This could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack." It lists SIMATIC HMI Basic Panels 2nd Generation before V16, and Comfort Panels, Mobile Panels and Unified Comfort Panels up to and including V16. CWE-307 (improper restriction of excessive authentication attempts) is used by NVD, Siemens and CISA alike (NVD, CVE record).

Why do NVD and Siemens score it so differently?

NVD's Primary score is CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), with CVSS v2 5.0; NVD also shows a Secondary 9.8 with the same vector from CISA's ADP container in the CVE record. Siemens scores it 6.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L/E:P/RL:O/RC:C), rating the impact as low integrity and low availability with no confidentiality impact where NVD's vector rates high confidentiality, integrity and availability impact. This page uses NVD's Primary 9.8 as the headline score.

What does Siemens say?

Siemens advisory SSA-542525 ("Authentication Vulnerabilities in SIMATIC HMI Products", first published 2020-09-08, current version 4 of 2021-06-08) gives the fixes: update Basic Panels 2nd Generation, Comfort Panels and Mobile Panels to V16 Update 3, and Unified Comfort Panels to V16 Update 5. It recommends defense in depth per Siemens' operational guidelines. The advisory also covers CVE-2020-15787, a password truncation in Unified Comfort Panels using SmartClient that Siemens says cannot be resolved because RFC 6143 limits VNC passwords to 8 characters; Siemens recommends complex passwords.

What does CISA say?

CISA advisory ICSA-20-252-06 (CSAF), "Siemens SIMATIC HMI Products (Update A)", republishes Siemens' 6.5 score, CWE-307 and the same four panel families and updates.

What should a panel owner do?

  1. Update WinCC (TIA Portal) and the panel images to V16 Update 3, or V16 Update 5 on Unified Comfort Panels.
  2. Set complex Sm@rt Server passwords at commissioning, as Siemens recommends for the related CVE-2020-15787, and switch Sm@rt Server off on panels that do not use it.
  3. Keep panels in the machine cell, with no route to Sm@rt Server ports from the office network or the internet.

The Siemens WinCC and PCS 7 guide covers the HMI panel line alongside WinCC. CVE-2021-27384 is a SmartVNC flaw on the same Comfort and Mobile Panels, and CVE-2011-4509 is the older default password on the HMI web server. The OT/ICS security guide for small manufacturers covers passwords and segmentation for panels.

CVE-2020-15786 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.01477, a percentile of 74.2, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2020-09-09; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H and CVSS v2 5.0 AV:N/AC:L/Au:N/C:P/I:N/A:N; Secondary 9.8 from CISA-ADP; CWE-307; CPEs Basic Panels 2nd Generation firmware up to 14, Comfort, Mobile and united_comfort_panels firmware all versions. — NVD
  • Siemens SSA-542525 CSAF version 4, 2021-06-08 (read 2026-11-28): CVSS v3.1 6.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L/E:P/RL:O/RC:C; fixes V16 Update 3 (Basic 2nd Gen, Comfort, Mobile) and V16 Update 5 (Unified Comfort); CVE-2020-15787 truncation cannot be resolved due to RFC 6143. — Siemens ProductCERT SSA-542525
  • CISA ICSA-20-252-06 CSAF (read 2026-11-28): CVSS v3.1 6.5, CWE-307, four HMI panel families. — CISA ICSA-20-252-06
  • CVE record (read 2026-11-28): state PUBLISHED, assigner siemens, CWE-307; CISA-ADP container adds CVSS v3.1. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.01477, percentile 0.74160, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens SSA-542525: Authentication Vulnerabilities in SIMATIC HMI Products
  3. CISA ICSA-20-252-06: Siemens SIMATIC HMI Products
  4. CISA ICSA-20-252-06 CSAF (machine-readable advisory)
  5. CVE record CVE-2020-15786 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2020-15786?

Siemens SSA-542525 lists V16 Update 3 for SIMATIC HMI Basic Panels 2nd Generation, Comfort Panels and Mobile Panels, and V16 Update 5 for Unified Comfort Panels.

Why does NVD rate it 9.8 when Siemens rates it 6.5?

NVD's vector scores high confidentiality, integrity and availability impact. Siemens and CISA score low integrity and availability impact and no confidentiality impact, which gives 6.5.

Is the 8-character password limit fixed too?

No. The same advisory covers CVE-2020-15787, password truncation on Unified Comfort Panels using SmartClient. Siemens says it cannot be resolved because RFC 6143 limits passwords to 8 characters, and recommends complex passwords.

Is CVE-2020-15786 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.01477 (percentile 74.2) in the 2026-11-27 dataset.