CVE-2019-18253 is a path traversal in ABB Relion 670 series protection relays: specially crafted paths in a request let an unauthenticated attacker read or delete files outside the intended directory. NVD and CISA score it 10.0. ABB fixed it in 1p1r27, 1.2.3.18, 2.0.0.11 and 2.1.0.2; disabling unused IEC 61850 removes the flaw.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
2.0%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-18253 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| ABB Relion 670 series | cpe:2.3:o:hitachienergy:relion_670_firmware:*:*:*:*:*:*:*:* | 1p1r26 and earlier (fix 1p1r27); 1.2.3.17 and earlier (fix 1.2.3.18); 2.0.0.10 and earlier, RES670 2.0.0.4 and earlier (fix 2.0.0.11, RES670 2.0.0.5); 2.1.0.1 and earlier (fix 2.1.0.2) (CISA ICSA-19-330-01; NVD CPE ends before 1p1r26, 1.2.3.17, 2.0.0.10 and 2.1.0.1) |
What does this mean for affected devices?
NVD carries CISA's description: "An attacker could use specially crafted paths in a specific request to read or delete files from Relion 670 Series (versions 1p1r26, 1.2.3.17, 2.0.0.10, RES670 2.0.0.4, 2.1.0.1, and prior) outside the intended directory." NVD's Primary score is CVSS v3.1 10.0 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H), and CISA's ICSA-19-330-01 gives CVSS v3.0 10.0 with the same vector. Both list CWE-22. The CNA is CISA ICS (icscert), and the record was published on 2019-11-27 (NVD, CVE record).
Which Relion 670 firmware fixes it?
CISA's advisory, released on 2019-11-26 and titled ABB Relion 670 Series (CSAF), lists these fixes, which ABB recommends "if IEC 61850 is used":
- 1p1r26 and earlier: update to 1p1r27.
- 1.2.3.17 and earlier: update to 1.2.3.18.
- 2.0.0.10 and earlier (RES670 2.0.0.4 and earlier): update to 2.0.0.11 (RES670 2.0.0.5).
- 2.1.0.1 and earlier: update to 2.1.0.2.
NVD's CPE ranges end before 1p1r26, 1.2.3.17, 2.0.0.10 and 2.1.0.1, so a CPE-only scan misses the last affected build of each line, and it has no separate RES670 entry. The Relion 670 line is now handled by Hitachi Energy, which is why NVD files it under hitachienergy.
What if you cannot update the relay?
CISA quotes ABB: "The only known workaround for this vulnerability is to disable IEC 61850 protocol when not in use." Where IEC 61850 is needed, ABB recommends dividing the system into security zones and limiting MMS, which uses TCP port 102, to the relevant upper networks. CISA lists the sectors as Critical Manufacturing and Energy, deployed worldwide, and noted no known public exploits.
The ABB AC500, RTU500 and Relion guide lists the Relion 670 history, including the reboot flaw CVE-2019-18247 published the same day and the IEC 61850 reboot CVE-2021-27196. The IEC 61850 security guide covers MMS exposure, and the path traversal fix guide covers the class.
CVE-2019-18253 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.0198, the 81.1st percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2019-11-27; NVD Primary CVSS v3.1 10.0 AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H; CWE-22 (icscert and NVD); CPE hitachienergy relion_670_firmware before 1p1r26, 1.2 to before 1.2.3.17, 2.0 to before 2.0.0.10, 2.1 to before 2.1.0.1. — NVD
- CISA ICSA-19-330-01 CSAF (released 2019-11-26), read 2026-11-23: ABB Relion 670 Series; CWE-22; CVSS v3.0 10.0; affected 1p1r26, 1.2.3.17, 2.0.0.10 (RES670 2.0.0.4), 2.1.0.1 and prior; fixes 1p1r27, 1.2.3.18, 2.0.0.11 (RES670 2.0.0.5), 2.1.0.2; only workaround disable IEC 61850; MMS uses port 102/TCP; ABB advisory 1MRG024910. — CISA ICSA-19-330-01
- CVE record (checked 2026-11-23): see body; state PUBLISHED. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.0198, percentile 0.81066, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Relion 670 versions fix CVE-2019-18253?
1p1r27, 1.2.3.18, 2.0.0.11 (RES670 2.0.0.5) and 2.1.0.2, per CISA ICSA-19-330-01.
Is there a workaround?
Yes. ABB says the only known workaround is to disable the IEC 61850 protocol when it is not used. Otherwise, limit MMS on TCP port 102 to the relevant upper networks with zones and firewall rules.
Will a CPE-based scanner flag every affected relay?
No. As of 2026-11-23 NVD's CPE ranges end before 1p1r26, 1.2.3.17, 2.0.0.10 and 2.1.0.1, while CISA lists those builds as affected.
Is CVE-2019-18253 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.0198 (81.1st percentile) in the 2026-11-22 dataset.
Questions about this page?