Security Advisory

CVE-2020-7560: Control Expert Write-What-Where File Flaw

Last updated:
  • CVE-2020-7560

CVE-2020-7560 is a write-what-where condition (CWE-123) in Schneider Electric's EcoStruxure Control Expert and its predecessor Unity Pro, the engineering software for Modicon PLCs. Opening a malicious project file could crash the software or run code. NVD and Schneider both score it 8.6. The fix in Control Expert v15.0 SP1 is a file encryption feature you must turn on.

Vulnerability summary

CVSS base score

8.6

High severity

EPSS score (FIRST)

1.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-7560 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric EcoStruxure Control Expertcpe:2.3:a:schneider-electric:ecostruxure_control_expert:*:*:*:*:*:*:*:*Prior to v15.0 SP1 per Schneider SEVD-2020-343-01 V2.0 (NVD CPE: all versions); v15.0 SP1 adds the file encryption feature that fixes it
Schneider Electric Unity Pro (former name of Control Expert)cpe:2.3:a:schneider-electric:unity_pro:*:*:*:*:*:*:*:*All versions; no fix, migrate to Control Expert v15.0 SP1 or later
Schneider Electric EcoStruxure Process Expert and RemoteConnect (SCADAPack x70 RTU configuration)—All versions per SEVD-2020-343-01 V2.0; mitigations only in that notice (not in NVD's CPE list)

What does this mean for affected devices?

Schneider Electric's notice SEVD-2020-343-01, first published on 8 December 2020 and revised to version 2.0 on 13 July 2021, describes "a CWE-123 - Write-what-where Condition vulnerability" that "could cause a crash of the software or unexpected code execution when opening a malicious file in the engineering software". Control Expert designs, diagnoses and updates applications for Modicon M340, M580, M580 Safety, Momentum, Premium and Quantum PLCs.

How severe is CVE-2020-7560?

NVD's Primary score is CVSS v3.1 8.6, AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H: local, user interaction required, scope changed. Schneider gives the same 8.6 vector in CVSS v3.0. NVD's CVSS v2 score is 6.8 (NVD). The CVE.org record still reads "all versions" of Control Expert and Unity Pro, which is the original December 2020 wording. Jared Rittle of Cisco Talos reported it.

What fixes it?

Version 2.0 of the notice lists Control Expert prior to v15.0 SP1, Unity Pro (all versions), EcoStruxure Process Expert (all versions) and RemoteConnect (all versions), the tool for SCADAPack x70 RTUs. For Control Expert the fix is v15.0 SP1, delivered as a "file encryption" feature: it is proposed by default for new projects, and Schneider recommends applying it to all new projects and to existing projects that come from a trusted source, and sharing project files only when encrypted. For Process Expert and RemoteConnect the notice gives mitigations only: store project files in secure storage open to trusted users, use secure protocols to exchange them, encrypt them at rest, open only trusted files, check a hash of each file before use and harden the workstation.

The Schneider EcoStruxure HMI and SCADA software guide flags this as a fix that needs a second step. Related Control Expert project-file flaws are CVE-2022-26507 in the bundled Xmill library and CVE-2023-27975. The memory corruption fix guide covers write-what-where bugs.

Is CVE-2020-7560 exploited?

It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.01447, the 73.6th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): published 2020-12-11, status Modified; NVD Primary CVSS v3.1 8.6 AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H; NVD Primary CVSS v2 6.8; CWE-123 (Schneider); CPE ecostruxure_control_expert and unity_pro, all versions. — NVD
  • Schneider SEVD-2020-343-01 V2.0 (8 December 2020, revised 13 July 2021, read 2026-11-28): affected Control Expert prior to v15.0 SP1, Unity Pro all versions, Process Expert all versions, RemoteConnect all versions; CVSS v3.0 8.6 same vector; fix in v15.0 SP1 via file encryption feature, default for new projects; mitigations for Process Expert and RemoteConnect; credited to Jared Rittle (Cisco Talos). — Schneider Electric
  • CVE.org record (read 2026-11-28): assigner Schneider Electric, CWE-123, product Control Expert (all versions) and Unity Pro (all versions), no CVSS metric in the CNA container. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.01447, percentile 0.73606, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2020-343-01 V2.0: EcoStruxure Control Expert, Process Expert and RemoteConnect
  3. CVE.org record (JSON)
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Is installing Control Expert v15.0 SP1 enough?

No. Schneider delivers the fix as a file encryption feature in v15.0 SP1. It is proposed by default for new projects, but existing projects from trusted sources must be switched to it under Edit, Properties, Project & Controller Protection, and files should be shared only when encrypted.

Are Process Expert and RemoteConnect affected?

Yes. Version 2.0 of SEVD-2020-343-01 (July 2021) added EcoStruxure Process Expert and RemoteConnect, all versions, with mitigations only: secure storage, encrypted files, trusted sources, hash checks and a hardened workstation. NVD's CPE list names only Control Expert and Unity Pro.

Does the flaw run code on the PLC?

Schneider describes the impact as a crash of the engineering software or unexpected code execution when a malicious file is opened in it, on the Windows workstation. NVD and Schneider score a local attack with user interaction and changed scope (8.6).

Is CVE-2020-7560 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.01447, the 73.6th percentile, in the 2026-11-27 dataset.