Security Advisory

CVE-2022-26507: Control Expert Xmill Heap Overflow

Last updated:
  • CVE-2022-26507

CVE-2022-26507 is a heap-based buffer overflow in the AT&T Labs Xmill 0.7 XML decompressor that Schneider Electric bundled with EcoStruxure Control Expert, Process Expert and SCADAPack RemoteConnect for x70. A crafted file can lead to code execution on the engineering workstation. NVD and CISA score it 9.8; Control Expert V15.1 HF001 fixes it.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

2.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-26507 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric EcoStruxure Control Expert (including former Unity Pro)cpe:2.3:a:schneider-electric:ecostruxure_control_expert:*:*:*:*:*:*:*:*All versions prior to V15.1 HF001 (NVD CPE: before 15.1, and 15.1 without hotfix); fixed in V15.1 HF001
Schneider Electric EcoStruxure Process Expert (including former HDCS)cpe:2.3:a:schneider-electric:ecostruxure_process_expert:*:*:*:*:*:*:*:*All versions prior to V2021; fixed in V2021
Schneider Electric SCADAPack RemoteConnect for x70 (SCADAPack 470, 474, 570, 574, 575 RTUs)cpe:2.3:a:schneider-electric:remoteconnect:-:*:*:*:*:*:*:*All versions prior to R2.7.3; fixed in R2.7.3
AT&T Labs Xmill (XML compressor, XMill/XDemill)cpe:2.3:a:att:xmill:0.7:*:*:*:*:*:*:*0.7; no longer supported by AT&T Labs

What does this mean for affected devices?

The CVE record, assigned by MITRE, says "a heap-based buffer overflow exists in XML Decompression DecodeTreeBlock in AT&T Labs Xmill 0.7. A crafted input file can lead to remote code execution", and notes that it is distinct from the earlier Xmill CVEs CVE-2021-21810 to CVE-2021-21830 and that it "only affects products that are no longer supported by the maintainer" (CVE.org record). NVD classifies it as CWE-787, out-of-bounds write; CISA's CSAF labels it CWE-125.

How severe is it and who scores it?

NVD's Primary score is CVSS v3.1 9.8, AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with CVSS v2 7.5 (NVD). CISA's ICSA-22-223-03, released on 11 August 2022, gives the same 9.8 vector. Schneider's own description is narrower: an attacker needs access to the engineering workstation and must trick a valid user into running a script or loading a malicious project file, after which code can run with elevated privileges on that workstation.

Which products are affected and what is the fix?

Schneider's SEVD-2021-222-02 version 4.0 (12 July 2022) and the CISA advisory list three products, each with a fix:

  • EcoStruxure Control Expert, all versions including former Unity Pro prior to V15.1 HF001: install V15.1 HF001.
  • EcoStruxure Process Expert, all versions including former HDCS prior to V2021: install V2021.
  • SCADAPack RemoteConnect for x70, the tool for the SCADAPack 470, 474, 570, 574 and 575 RTUs, prior to R2.7.3: install R2.7.3.

Schneider's revision history records that releases it had first named, in March 2022, did not fully address the issues; CVE-2022-26507 was added with the V15.1 HF001 and V2021 fixes in April 2022. Until updated, store project files in secure storage open to trusted users only, exchange them over secure channels, open only trusted project files, check a hash of each file before use, harden the workstation and move off Unity Pro.

The Schneider EcoStruxure HMI and SCADA software guide lists this flaw with the other Control Expert project-file issues, including the write-what-where CVE-2020-7560 and CVE-2023-6409. The memory corruption fix guide covers the root cause.

Is CVE-2022-26507 exploited?

It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.02558, the 85.8th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): published 2022-04-14, status Modified; NVD Primary CVSS v3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 7.5; CWE-787 (NVD); CPE att:xmill 0.7, ecostruxure_control_expert before 15.1 and 15.1, ecostruxure_process_expert before 2021, remoteconnect with SCADAPack 470/474/570/574/575. — NVD
  • CISA ICSA-22-223-03 CSAF (read 2026-11-28): released 2022-08-11; CVE-2022-26507 CWE-125 CVSS v3.0 9.8; affected Control Expert prior to V15.1 HF001, Process Expert prior to V2021, SCADAPack RemoteConnect for x70 prior to R2.7.3; fixes and project-file mitigations; credited to Uri Katz; AT&T Labs no longer supports the software. — CISA ICSA-22-223-03
  • Schneider SEVD-2021-222-02 V4.0 (12 July 2022, read 2026-11-28): attacker needs workstation access and to trick a user into running a script or loading a malicious project file; elevated-privilege code execution; V2.1 notes earlier releases did not fully address the issues; V3.0 (12 April 2022) added CVE-2022-26507 and the V15.1 HF001 and V2021 fixes; V4.0 added RemoteConnect R2.7.3; CVE-2022-26507 credited to Uri Katz of Claroty Research. — Schneider Electric
  • CVE.org record (read 2026-11-28): assigner MITRE; description of Xmill 0.7 DecodeTreeBlock heap overflow; not the same as CVE-2021-21810..21830; only affects products no longer supported by the maintainer. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.02558, percentile 0.85828, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-22-223-03: Schneider Electric EcoStruxure, Process Expert, SCADAPack RemoteConnect for x70 (CSAF)
  3. Schneider Electric SEVD-2021-222-02 V4.0: AT&T Labs XMill and XDemill in Control Expert, Process Expert and RemoteConnect
  4. CVE.org record (JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which versions fix CVE-2022-26507?

EcoStruxure Control Expert V15.1 HF001, EcoStruxure Process Expert V2021 and SCADAPack RemoteConnect for x70 R2.7.3, per CISA ICSA-22-223-03 and Schneider SEVD-2021-222-02. Schneider notes that RemoteConnect no longer needs a separate update when Control Expert is updated.

Is the SCADAPack RTU itself vulnerable?

The flaw is in the Xmill library inside the engineering software, so the code runs on the Windows workstation. NVD lists the SCADAPack 470, 474, 570, 574 and 575 only as the hardware that RemoteConnect configures.

Why does CISA say CWE-125 and NVD CWE-787?

The CVE description calls it a heap-based buffer overflow; NVD maps it to CWE-787, out-of-bounds write, while CISA's CSAF entry uses CWE-125, out-of-bounds read. Both agree on the 9.8 score.

Is CVE-2022-26507 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.02558, the 85.8th percentile, in the 2026-11-27 dataset.