Security Advisory

CVE-2020-7565: Modicon M221 Weak Encryption Key

Last updated:
  • CVE-2020-7565

CVE-2020-7565 is a weakness in how Schneider Electric Modicon M221 nano PLCs (and the M100 and M200) protect traffic from the EcoStruxure Machine Expert - Basic programming software: inadequate encryption strength (CWE-326) lets an attacker who captured that traffic break the encryption key. NVD scores it 7.3, Schneider 7.1. No firmware fix exists; Schneider lists mitigations.

Vulnerability summary

CVSS base score

7.3

High severity

EPSS score (FIRST)

0.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-7565 · Source: NVD

Affected components

ComponentCPEVersion range
Modicon M221 (all references)cpe:2.3:o:schneider-electric:modicon_m221_firmware:-:*:*:*:*:*:*:*All versions; no fix as of 2026-11-21, mitigations only (Schneider SEVD-2020-315-05, CISA ICSA-20-343-04)
Modicon M200 (all references)—All versions; added to SEVD-2020-315-05 in version 3.0.0 (2021-01-12); not in NVD's CPE list
Modicon M100 (all references)—All versions; added to SEVD-2020-315-05 in version 3.0.0 (2021-01-12); not in NVD's CPE list

What does this mean for affected devices?

NVD carries the Schneider Electric description: "A CWE-326: Inadequate Encryption Strength vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption key when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller." NVD's Primary score is CVSS v3.1 7.3 (CVSS:3.1/AV:A/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N), and the weakness is the Schneider CNA's CWE-326 (inadequate encryption strength). The record was published on 2020-11-19 (NVD, CVE record).

How severe is CVE-2020-7565, and why do the scores differ?

Schneider Electric scores CVE-2020-7565 at CVSS v3.0 7.1 (CVSS:3.0/AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H) in SEVD-2020-315-05, and CISA's ICSA-20-343-04 repeats 7.1. The CISA ADP container in the CVE record carries the same vector as CVSS v3.1 7.1, which NVD shows as a Secondary metric. All agree that the attacker sits on the adjacent network and that user interaction is required. NVD rates attack complexity low and availability impact none; Schneider rates complexity high and availability high. CISA's advisory says that no known public exploits specifically target these flaws and that a high skill level is needed to exploit them.

What does breaking the key give an attacker?

CVE-2020-7565 is the first step in a chain: the encryption that protects programming traffic between Machine Expert - Basic and the controller is too weak, so captured traffic can be decrypted. The twin flaw CVE-2020-7566 reaches the same result through a small space of random values. Schneider's overview of SEVD-2020-315-05 says that without the mitigations, unauthorized users could "replay authentication sequences, which could result in an attacker taking control over the PLC." The same notice lists CVE-2020-7566, CVE-2020-7567 (password hash recoverable once the keys are broken), CVE-2020-7568 (information disclosure) and CVE-2020-28214 (predictable password salt). Schneider credits Claroty (Yehuda Anikster, Rei Henigman) and the NESC Lab of Zhejiang University.

Which controllers are affected?

Product (Schneider wording) Affected Fixed
Modicon M221, all references all versions no fix
Modicon M200, all references all versions no fix
Modicon M100, all references all versions no fix

SEVD-2020-315-05 was first released on 2020-11-10; version 3.0.0 of 2021-01-12 added the M100 and M200. CISA's advisory of 2020-12-08 and NVD's CPE (modicon_m221_firmware, version -) still name only the M221, so a CPE match alone misses the M100 and M200.

How do you mitigate CVE-2020-7565?

There is no firmware fix as of 2026-11-21. Schneider tells users to set up network segmentation and a firewall that blocks all unauthorized access to port 502/TCP, and, within the M100/M200/M221 application, to disable all unused protocols, especially the Programming protocol, so that remote programming access is not possible. It also tells users to set a password to protect the project, a password for read access and a different password for write access. Since the attack needs captured programming traffic, run Machine Expert - Basic only on the network intended for the controller. Our Modicon and UMAS security guide covers Schneider controller hardening, and the weak cryptography fix guide explains this class of flaw. A related Modicon flaw on the same port is CVE-2017-6034 (Modbus command replay).

CVE-2020-7565 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00294, the 22.5th percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-21): status Modified; published 2020-11-19; NVD Primary CVSS v3.1 7.3 CVSS:3.1/AV:A/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N, v2 4.3; CISA-ADP Secondary 7.1 CVSS:3.1/AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H; CWE CWE-326 (Schneider); CPE modicon_m221_firmware version "-"; references ICSA-20-343-04 and SEVD-2020-315-05. — NVD
  • Schneider Electric SEVD-2020-315-05 version 3.0.0 (published 2020-11-10, updated 2021-01-12), CSAF read 2026-11-21: CVE-2020-7565 CWE-326, CVSS v3.0 7.1 CVSS:3.0/AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H; Modicon M100, M200 and M221 all references, all versions; mitigations only: firewall 502/TCP, disable unused protocols especially Programming protocol, project password, read password, different write password; overview: unauthorized users could replay authentication sequences and take control over the PLC; credits Claroty (Yehuda Anikster, Rei Henigman) and the NESC Lab of Zhejiang University. — Schneider Electric SEVD-2020-315-05
  • CISA ICSA-20-343-04 CSAF (released 2020-12-08), read 2026-11-21: CVE-2020-7565 CWE-326, CVSS v3 7.1, Modicon M221; exploitability: no known public exploits specifically target these vulnerabilities, high skill level needed. — CISA CSAF ICSA-20-343-04
  • CVE record (checked 2026-11-21): state PUBLISHED, CNA Schneider Electric, published 2020-11-19; CNA CWE-326, no CNA CVSS metric; CISA-ADP CVSS v3.1 7.1 and SSVC (exploitation none, automatable no, technical impact total). — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21. — CISA KEV
  • EPSS 0.00294, 22.5th percentile, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2020-315-05: Modicon M100/M200/M221 Programmable Logic Controller (PDF)
  3. Schneider Electric SEVD-2020-315-05 (CSAF)
  4. CISA CSAF: ICSA-20-343-04 Schneider Electric Modicon M221 Programmable Logic Controller (machine-readable advisory)
  5. CVE.org record CVE-2020-7565 (CNA: Schneider Electric)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Is there a firmware update for CVE-2020-7565?

No. Schneider lists all references and all versions of the Modicon M100, M200 and M221 as affected and gives mitigations only (per SEVD-2020-315-05, version 3.0.0).

What should I configure on the M221?

Disable all unused protocols, especially the Programming protocol, set a password to protect the project, and set separate passwords for read and write access on the controller. Block all unauthorized access to port 502/TCP with a firewall (per Schneider SEVD-2020-315-05).

Can it be exploited from the internet?

Schneider, CISA and NVD all score the attack vector as adjacent network, and the attacker needs to capture traffic between Machine Expert - Basic and the controller. CISA notes that no known public exploits specifically target these flaws.

How is CVE-2020-7565 different from CVE-2020-7566?

Both let an attacker who captured Machine Expert - Basic traffic break the encryption. Schneider classes CVE-2020-7565 as inadequate encryption strength (CWE-326) and CVE-2020-7566 as a small space of random values (CWE-334); both have the same scores, products and mitigations in SEVD-2020-315-05.