CVE-2020-7567 is a flaw in Schneider Electric Modicon M221 nano PLCs (and the M100 and M200): the password hash travels without its own encryption (CWE-311) in traffic from the EcoStruxure Machine Expert - Basic programming software, so an attacker who captured that traffic and broke its keys can find it. NVD scores it 5.7, Schneider 7.1. No firmware fix exists; Schneider lists mitigations.
Vulnerability summary
CVSS base score
5.7
Medium severity
EPSS score (FIRST)
0.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-7567 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Modicon M221 (all references) | cpe:2.3:o:schneider-electric:modicon_m221_firmware:-:*:*:*:*:*:*:* | All versions; no fix as of 2026-11-21, mitigations only (Schneider SEVD-2020-315-05, CISA ICSA-20-343-04) |
| Modicon M200 (all references) | — | All versions; added to SEVD-2020-315-05 in version 3.0.0 (2021-01-12); not in NVD's CPE list |
| Modicon M100 (all references) | — | All versions; added to SEVD-2020-315-05 in version 3.0.0 (2021-01-12); not in NVD's CPE list |
What does this mean for affected devices?
NVD carries the Schneider Electric description: "A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to find the password hash when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller and broke the encryption keys." NVD's Primary score is CVSS v3.1 5.7 (CVSS:3.1/AV:A/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N), and the weakness is the Schneider CNA's CWE-311 (missing encryption of sensitive data). The record was published on 2020-11-19 (NVD, CVE record).
How severe is CVE-2020-7567, and why do the scores differ?
Schneider Electric scores CVE-2020-7567 at CVSS v3.0 7.1 (CVSS:3.0/AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H) in SEVD-2020-315-05, and CISA's ICSA-20-343-04 repeats 7.1. The CISA ADP container in the CVE record carries the same vector as CVSS v3.1 7.1, which NVD shows as a Secondary metric. NVD scores only the confidentiality loss (the password hash) and rates attack complexity low; Schneider rates complexity high and adds high integrity and availability impact, which reflects what an attacker can do with the password afterwards. Both put the attacker on the adjacent network and require user interaction. CISA says no known public exploits specifically target these flaws and that a high skill level is needed to exploit them.
Where does CVE-2020-7567 sit in the M221 attack chain?
CVE-2020-7567 is the step after the encryption is broken. The weak key in CVE-2020-7565 and the small random-value space in CVE-2020-7566 let an attacker who captured programming traffic between EcoStruxure Machine Expert - Basic and the controller decrypt it; CVE-2020-7567 then exposes the password hash inside that traffic. The same notice lists CVE-2020-28214 (a predictable password salt, which makes pre-computed hash tables practical) and CVE-2020-7568 (non-sensitive information disclosure). Schneider's overview says that without the mitigations, unauthorized users could "replay authentication sequences, which could result in an attacker taking control over the PLC." Schneider credits Claroty (Yehuda Anikster, Rei Henigman) and the NESC Lab of Zhejiang University.
Which controllers are affected?
| Product (Schneider wording) | Affected | Fixed |
|---|---|---|
| Modicon M221, all references | all versions | no fix |
| Modicon M200, all references | all versions | no fix |
| Modicon M100, all references | all versions | no fix |
SEVD-2020-315-05 was first released on 2020-11-10; version 3.0.0 of 2021-01-12 added the M100 and M200. CISA's advisory of 2020-12-08 and NVD's CPE (modicon_m221_firmware, version -) still name only the M221, so a CPE match alone misses the M100 and M200 in an asset list.
How do you mitigate CVE-2020-7567?
There is no firmware fix as of 2026-11-21. Schneider tells users to set up network segmentation and a firewall that blocks all unauthorized access to port 502/TCP, and, within the M100/M200/M221 application, to disable all unused protocols, especially the Programming protocol, so that remote programming access is not possible. It also tells users to set a password to protect the project, a password for read access and a different password for write access on the controller. Because the hash is only exposed in captured programming traffic, keep Machine Expert - Basic on the network intended for the controller and treat any capture point on that segment as sensitive. Our Modicon and UMAS security guide covers Schneider controller hardening, and the weak cryptography fix guide explains this class of flaw.
CVE-2020-7567 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00204, the 10.6th percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-21): status Modified; published 2020-11-19; NVD Primary CVSS v3.1 5.7 CVSS:3.1/AV:A/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N, v2 2.9; CISA-ADP Secondary 7.1 CVSS:3.1/AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H; CWE CWE-311 (Schneider); CPE modicon_m221_firmware version "-"; references ICSA-20-343-04 and SEVD-2020-315-05. — NVD
- Schneider Electric SEVD-2020-315-05 version 3.0.0 (published 2020-11-10, updated 2021-01-12), CSAF read 2026-11-21: CVE-2020-7567 CWE-311, CVSS v3.0 7.1 CVSS:3.0/AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H; attacker can find the password hash after capturing Machine Expert - Basic traffic to Modicon M100/M200/M221 and breaking the encryption keys; all versions affected; mitigations only: firewall 502/TCP, disable unused protocols especially Programming protocol, project password, read password, different write password; credits Claroty (Yehuda Anikster, Rei Henigman) and NESC Lab of Zhejiang University. — Schneider Electric SEVD-2020-315-05
- CISA ICSA-20-343-04 CSAF (released 2020-12-08), read 2026-11-21: CVE-2020-7567 CWE-311, CVSS v3 7.1, Modicon M221 all versions; no known public exploits specifically target these vulnerabilities, high skill level needed. — CISA CSAF ICSA-20-343-04
- CVE record (checked 2026-11-21): state PUBLISHED, CNA Schneider Electric, published 2020-11-19; CNA CWE-311, no CNA CVSS metric; CISA-ADP CVSS v3.1 7.1 and SSVC (exploitation none, automatable no, technical impact total). — CVE.org
- Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21. — CISA KEV
- EPSS 0.00204, 10.6th percentile, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories
Sources
- NVD
- Schneider Electric SEVD-2020-315-05: Modicon M100/M200/M221 Programmable Logic Controller (PDF)
- Schneider Electric SEVD-2020-315-05 (CSAF)
- CISA CSAF: ICSA-20-343-04 Schneider Electric Modicon M221 Programmable Logic Controller (machine-readable advisory)
- CVE.org record CVE-2020-7567 (CNA: Schneider Electric)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Is there a firmware update for CVE-2020-7567?
No. Schneider lists all references and all versions of the Modicon M100, M200 and M221 as affected and gives mitigations only (per SEVD-2020-315-05, version 3.0.0).
Why does NVD score CVE-2020-7567 lower than Schneider?
NVD's 5.7 counts only the loss of confidentiality (the password hash) with low attack complexity. Schneider's and CISA's 7.1 rate complexity high but add high integrity and availability impact. Both vectors need an adjacent-network attacker and user interaction.
Can an attacker use CVE-2020-7567 on its own?
No. The hash is exposed only after the attacker has captured Machine Expert - Basic traffic and broken its encryption keys, which is what CVE-2020-7565 and CVE-2020-7566 describe. A predictable salt (CVE-2020-28214) then makes the hash easier to reverse.
What should I configure on the M221?
Disable all unused protocols, especially the Programming protocol, set a project password and separate read and write passwords on the controller, and block unauthorized access to port 502/TCP with a firewall (per Schneider SEVD-2020-315-05).
Questions about this page?