Security Advisory

CVE-2020-28214: Modicon M221 Predictable Password Salt

Last updated:
  • CVE-2020-28214

CVE-2020-28214 is a password-storage weakness in Schneider Electric Modicon M221 nano PLCs, later extended to the M100 and M200: passwords are hashed with a predictable salt (CWE-760), so an attacker who obtains a hash can reverse it with a precomputed rainbow table. NVD scores it 5.5, Schneider 3.3. No firmware fix exists; Schneider lists mitigations.

Vulnerability summary

CVSS base score

5.5

Medium severity

EPSS score (FIRST)

0.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-28214 · Source: NVD

Affected components

ComponentCPEVersion range
Modicon M221 (all references)cpe:2.3:o:schneider-electric:modicon_m221_firmware:*:*:*:*:*:*:*:*All versions; no fix as of 2026-11-20, mitigations only (Schneider SEVD-2020-315-05, CISA ICSA-20-343-04)
Modicon M200 (all references)—All versions; added to SEVD-2020-315-05 in version 3.0.0 (2021-01-12); not in NVD's CPE list
Modicon M100 (all references)—All versions; added to SEVD-2020-315-05 in version 3.0.0 (2021-01-12); not in NVD's CPE list

What does this mean for affected devices?

NVD carries the Schneider Electric description: "A CWE-760: Use of a One-Way Hash with a Predictable Salt vulnerability exists in Modicon M221 (all references, all versions), that could allow an attacker to pre-compute the hash value using dictionary attack technique such as rainbow tables, effectively disabling the protection that an unpredictable salt would provide." The record was published on 2020-12-11 (NVD, CVE record).

How severe is CVE-2020-28214, and why are there three scores?

NVD's Primary score is CVSS v3.1 5.5 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N): a local attacker with low privileges and a high confidentiality impact. Schneider Electric, the CNA, scores it 3.3 (CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N) in its bulletin SEVD-2020-315-05, and CISA's ICSA-20-343-04 CSAF repeats 3.3. A third score sits in the CVE record: the CISA ADP container added CVSS v3.1 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and an SSVC entry of 2026-05-28 with exploitation "none", automatable "yes" and technical impact "total". NVD shows that 9.8 as a Secondary metric. The vendor and NVD agree that the flaw is local; the 9.8 treats it as a network-reachable takeover. All sources use CWE-760.

What does a predictable salt mean on a Modicon M221?

A salt is meant to make every stored password hash unique, so that an attacker cannot reverse it with a precomputed table. If the salt can be predicted, one rainbow table built in advance works against every controller. The same Schneider bulletin lists four related flaws in the link between EcoStruxure Machine Expert - Basic and the controller: CVE-2020-7565 and CVE-2020-7566 let an attacker who captured that traffic break the encryption keys, and CVE-2020-7567 then lets them find the password hash. CVE-2020-28214 is what makes such a hash cheap to reverse. Schneider's overview says that without the mitigations, unauthorized users could "replay authentication sequences, which could result in an attacker taking control over the PLC." The flaws were reported by Claroty, Trustwave and the NESC Lab of Zhejiang University.

Which controllers are affected?

Product (Schneider wording) Affected Fixed
Modicon M221, all references all versions no fix
Modicon M200, all references all versions no fix
Modicon M100, all references all versions no fix

SEVD-2020-315-05 version 2.0.0 (2020-12-08) added CVE-2020-28214, and version 3.0.0 (2021-01-12) added the M100 and M200. CISA's advisory of 2020-12-08 and NVD's CPE (modicon_m221_firmware, any version) still name only the M221, so a CPE match alone misses the M100 and M200.

How do you mitigate CVE-2020-28214?

There is no firmware fix as of 2026-11-20. Schneider tells users to set up network segmentation and a firewall that blocks all unauthorized access to port 502/TCP, and, within the M100/M200/M221 application, to disable all unused protocols (especially the Programming protocol), set a password to protect the project, set a password for read access and set a different password for write access. Keep the engineering laptop that runs Machine Expert - Basic on the cell network only. Our Modicon and UMAS security guide covers Schneider controller hardening, and the weak cryptography fix guide explains salted, slow password hashing for firmware teams. Related Modicon flaws: CVE-2017-6034 (Modbus command replay), CVE-2022-45789 (session replay authentication bypass) and CVE-2018-7842 (UMAS session ID brute force).

Is CVE-2020-28214 exploited?

It is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). CISA's ICS advisory states that no known public exploits specifically target these vulnerabilities. FIRST EPSS gives it 0.00748, the 55.7th percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-20): status Modified; published 2020-12-11; NVD Primary CVSS v3.1 5.5 CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N, v2 2.1; CISA ADP Secondary 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CWE-760 (Schneider); CPE modicon_m221_firmware, all versions; references SEVD-2020-315-05 and ICSA-20-343-04. — NVD
  • Schneider Electric SEVD-2020-315-05 version 3.0.0 (published 2020-11-10, updated 2021-01-12; CSAF file in the bulletin package), read 2026-11-20: CVE-2020-28214 CWE-760, CVSS v3.0 3.3 CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N; Modicon M100, M200 and M221 all references, all versions; revision 2.0.0 (2020-12-08) added CVE-2020-28214, revision 3.0.0 added M100/M200; mitigations: firewall 502/TCP, disable unused protocols especially Programming protocol, project password, read password, different write password; credits Claroty, Trustwave, NESC Lab of Zhejiang University. — Schneider Electric SEVD-2020-315-05
  • CISA ICSA-20-343-04 CSAF (2020-12-08), read 2026-11-20: Modicon M221 all versions; CVE-2020-28214 CWE-760 CVSS v3.0 3.3; no known public exploits specifically target these vulnerabilities; credits Claroty and Trustwave. — CISA CSAF ICSA-20-343-04
  • CVE record (checked 2026-11-20): state PUBLISHED, CNA Schneider, published 2020-12-11; CNA CWE-760, no CNA CVSS metric; CISA ADP CVSS v3.1 9.8 and SSVC (2026-05-28) exploitation none, automatable yes, technical impact total. — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-20. — CISA KEV
  • EPSS 0.00748, percentile 0.55687, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2020-315-05: Modicon M100/M200/M221 Programmable Logic Controller (bulletin package with PDF and CSAF)
  3. CISA CSAF: ICSA-20-343-04 Schneider Electric Modicon M221 Programmable Logic Controller (machine-readable advisory)
  4. CVE.org record CVE-2020-28214 (CNA: Schneider Electric)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Is there a firmware update that fixes CVE-2020-28214?

No. Schneider Electric SEVD-2020-315-05 lists all versions of the Modicon M100, M200 and M221 as affected and gives mitigations only, with no fixed firmware as of 2026-11-20.

Which Modicon controllers does CVE-2020-28214 affect?

All references and versions of the Modicon M221, M200 and M100. The M100 and M200 were added in version 3.0.0 of SEVD-2020-315-05 on 2021-01-12; CISA ICSA-20-343-04 and NVD's CPE list only the M221.

Why does NVD score it 5.5 when Schneider scores it 3.3?

Both treat it as a local attack with low privileges. NVD rates the confidentiality impact high (5.5); Schneider and CISA's ICS advisory rate it low (3.3). The CISA ADP entry in the CVE record adds a network-based 9.8, which NVD shows as a Secondary metric.

How do I reduce the risk on an M221 that cannot be updated?

Follow the Schneider mitigations: block all unauthorized access to port 502/TCP with a firewall, disable unused protocols (especially the Programming protocol), protect the project with a password and set separate read and write passwords on the controller (per SEVD-2020-315-05).