Security Advisory

CVE-2019-6567: SCALANCE X Recoverable Passwords

Last updated:
  • CVE-2019-6567

CVE-2019-6567 means Siemens SCALANCE X-200, X-200IRT, X-300 and X-414-3E switches store user passwords in a recoverable format, so anyone who gets a configuration backup or C-PLUG module can reconstruct them. NVD scores it 5.5; Siemens scores it 7.1. Fixed in X-200 V5.2.4, X-200IRT V5.5.0 and X-300 V4.1.3; the X-414-3E has no fix.

Vulnerability summary

CVSS base score

5.5

Medium severity

EPSS score (FIRST)

0.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2019-6567 · Source: NVD

Affected components

ComponentCPEVersion range
SCALANCE X-200 switch family (incl. SIPLUS NET variants)cpe:2.3:o:siemens:scalance_x-200_firmware:*:*:*:*:*:*:*:*All versions before V5.2.4; fixed in V5.2.4 (Siemens SSA-646841)
SCALANCE X-200IRT switch family (incl. SIPLUS NET variants)cpe:2.3:o:siemens:scalance_x-200irt_firmware:*:*:*:*:*:*:*:*All versions before V5.5.0; fixed in V5.5.0 (Siemens SSA-646841). NVD's CPE has no version limit
SCALANCE X-300 switch family (incl. X408 and SIPLUS NET variants)cpe:2.3:o:siemens:scalance_x-300_firmware:*:*:*:*:*:*:*:*All versions before V4.1.3; fixed in V4.1.3 (Siemens SSA-646841). NVD's CPE has no version limit
SCALANCE X-414-3Ecpe:2.3:o:siemens:scalance_x-414-3e_firmware:*:*:*:*:*:*:*:*All versions; no fix as of 2026-11-22, Siemens recommends migrating to SCALANCE XM-400 (Siemens SSA-646841)

What does this mean for affected devices?

NVD carries the Siemens description: SCALANCE X-200, X-200IRT, X-300 and X-414-3E switches "store passwords in a recoverable format. An attacker may extract and recover device passwords from the device configuration. Successful exploitation requires access to a device configuration backup and impacts confidentiality of the stored passwords." NVD's Primary score is CVSS v3.1 5.5 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N) with CWE-522 (insufficiently protected credentials); the Siemens CNA classes it CWE-257 (storing passwords in a recoverable format). The record was published on 2019-06-12 (NVD, CVE record).

How severe is it, and why do the scores differ?

Siemens ProductCERT scores CVE-2019-6567 at CVSS v3.1 7.1 (CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N/E:P/RL:O/RC:C) in SSA-646841. NVD assumes low privileges and an unchanged scope, which gives 5.5; Siemens assumes no privileges and a changed scope (S:C). Both agree the impact is confidentiality only and that the attacker works locally on a configuration backup. CISA's ICSA-19-162-04 CSAF (Update B, 2021-02-09) uses the Siemens 7.1 vector.

CVE-2019-6567 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00301, the 23.2nd percentile, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).

Where does an attacker get a configuration backup?

SSA-646841 names the paths in its mitigations: archived configuration files, the mechanisms that retrieve the configuration from the switch over the network, and the C-PLUG configuration module that stores the configuration on a removable card. Anyone who copies one of these can reconstruct the user passwords and then log in to the switch with them. Siemens credits Christopher Wade of Pen Test Partners with coordinated disclosure.

Which products and versions are affected?

Product (Siemens wording) Affected Fixed
SCALANCE X-200 switch family (incl. SIPLUS NET variants) before V5.2.4 V5.2.4
SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) before V5.5.0 V5.5.0
SCALANCE X-300 switch family (incl. X408 and SIPLUS NET variants) before V4.1.3 V4.1.3
SCALANCE X-414-3E all versions no fix; migrate to SCALANCE XM-400

The table follows SSA-646841 V1.2 of 2021-02-09. NVD's CPE limits only the X-200 entry (before 5.2.4); its X-200IRT, X-300 and X-414-3E entries have no upper version, so they do not show the V5.5.0 and V4.1.3 fixes.

How do you fix or mitigate it?

Update X-200 to V5.2.4, X-200IRT to V5.5.0 and X-300/X408 to V4.1.3 or later. For all four products Siemens lists the same mitigations: restrict access to configuration backups and archived configuration files, restrict or disable network access to the mechanisms that retrieve the device configuration, and restrict access to the C-PLUG module if one is in use. For the X-414-3E, Siemens recommends migrating to the SCALANCE XM-400 line. After updating, change the passwords, since any backup taken earlier still contains the old ones in recoverable form. Our SCALANCE and RUGGEDCOM guide covers backup handling, and the hard-coded credentials fix guide explains the credential storage class. Related flaws in the same switches are CVE-2020-28391 and CVE-2020-28395 (hard-coded private keys), CVE-2023-44318 (hard-coded backup key in newer SCALANCE lines) and CVE-2019-13933 (web management authentication bypass).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-22): status Modified; published 2019-06-12; NVD Primary CVSS v3.1 5.5 CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N, v2 2.1; CWE-522 (NVD), CWE-257 (Siemens); CPE: SCALANCE X-200 firmware before 5.2.4, X-200IRT, X-300 and X-414-3E firmware without version limit; reference SSA-646841. — NVD
  • Siemens SSA-646841 V1.2 (published 2019-06-11, updated 2021-02-09), read 2026-11-22: CVSS v3.1 7.1 CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N/E:P/RL:O/RC:C, CWE-257; X-200 fixed V5.2.4, X-200IRT V5.5.0, X-300 (incl. X408, SIPLUS NET) V4.1.3, X-414-3E all versions with no fix; mitigations: restrict access to config backups, restrict or disable network access to configuration retrieval mechanisms, restrict access to C-PLUG, migrate X-414-3E to XM-400; credits Christopher Wade (Pen Test Partners). — Siemens ProductCERT SSA-646841
  • CISA ICSA-19-162-04 CSAF (Update B, 2021-02-09), read 2026-11-22: Siemens SCALANCE X; CVE-2019-6567 CWE-257, CVSS v3.1 7.1; fixes and mitigations match SSA-646841. — CISA CSAF ICSA-19-162-04
  • CVE record (checked 2026-11-22): state PUBLISHED, CNA Siemens, published 2019-06-12; CWE-257; four affected products. — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-22. — CISA KEV
  • EPSS 0.00301, percentile 0.23188, dataset 2026-11-21, read 2026-11-22. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT SSA-646841: Recoverable Password from Configuration Storage in SCALANCE X Switches
  3. CISA CSAF: ICSA-19-162-04 Siemens SCALANCE X (Update B, machine-readable advisory)
  4. CVE.org record CVE-2019-6567 (CNA: Siemens)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2019-6567?

SCALANCE X-200 V5.2.4, X-200IRT V5.5.0 and X-300 (incl. X408 and SIPLUS NET variants) V4.1.3, per Siemens SSA-646841 V1.2. The SCALANCE X-414-3E has no fix as of 2026-11-22; Siemens recommends migrating to the XM-400 line.

What does an attacker need to exploit CVE-2019-6567?

A copy of the device configuration: an archived backup file, a configuration pulled from the switch over the network, or the C-PLUG module. From that copy the passwords can be reconstructed and used to log in (per Siemens SSA-646841).

Is updating the firmware enough?

Not on its own. Backups and C-PLUG modules made before the update still hold the old passwords in recoverable form. Change the switch passwords after updating, and keep restricting access to backups and C-PLUG modules as Siemens recommends.

Why does NVD score 5.5 while Siemens scores 7.1?

NVD's vector assumes the attacker needs low privileges and keeps the scope unchanged. The Siemens vector assumes no privileges and a changed scope. Both rate the impact as confidentiality only and the attack vector as local (per NVD and Siemens SSA-646841).